0,900 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
5.64 kW
kW
El input
1.43 kW
kW
COP
3.94
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
%
Prated
6.00 kW
kW
SCOP
4.07
Tbiv
-7 °C
°C
TOL
-10 °C
°C
Pdh Tj = -7°C
5.70 kW
kW
COP Tj = -7°C
3.90
Cdh Tj = -7 °C
0.990
Pdh Tj = +2°C
5.80 kW
kW
COP Tj = +2°C
4.10
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
5.70 kW
kW
COP Tj = +7°C
4.30
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
5.70 kW
kW
COP Tj = 12°C
4.40
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
5.70 kW
kW
COP Tj = Tbiv
3.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.60 kW
kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.90
WTOL
50 °C
°C
Poff
2 W
W
PTO
9 W
W
PSB
4 W
W
PCK
0 W
W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.80 kW
kW
Annual energy consumption Qhe
3369 kWh
kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.14 kW
6.57 kW
El input
1.44 kW
2.01 kW
COP
4.86
3.26
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
211 %
151 %
Prated
8.00 kW
8.00 kW
SCOP
5.48
3.90
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.40 kW
6.80 kW
COP Tj = -7°C
5.20
3.30
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
7.60 kW
3.90 kW
COP Tj = +2°C
5.50
4.00
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
7.70 kW
7.10 kW
COP Tj = +7°C
5.80
4.40
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
7.70 kW
7.20 kW
COP Tj = 12°C
6.10
4.90
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
7.40 kW
6.80 kW
COP Tj = Tbiv
5.20
3.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.00
3.10
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
9 W
9 W
PSB
4 W
4 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
1.00 kW
Annual energy consumption Qhe
3138 kWh
3973 kWh