Certificate holders

Subtype

Vitocal 3xx-G C16

Certificate Holder
Viessmann Climate Solutions SE
Viessmannstr. 1
35107 Allendorf/Eder
Germany
Registration number
011-1W0212
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Vitocal 3xx-G C16
Driving energy
Electricity
Heat Pump Type
Brine/Water
Refrigerant
R410A
Mass of Refrigerant

3,250 kg

Certification Date
18.08.2020
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 2

Models

VITOCAL 300-G BWC 301.C16
Configure model
Model name
VITOCAL 300-G BWC 301.C16
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.51 kW

6.78 kW

El input

1.51 kW

2.83 kW

COP

5.00

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

215 %

155 %

Prated

14.00 kW

15.30 kW

SCOP

5.59

4.08

Tbiv

-10 °C

-10 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

14.00 kW

15.30 kW

COP Tj = +2°C

4.48

2.97

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

9.03 kW

10.43 kW

COP Tj = +7°C

5.42

3.72

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

4.12 kW

4.68 kW

COP Tj = 12°C

5.96

4.75

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

14.00 kW

15.30 kW

COP Tj = Tbiv

4.48

2.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.00 kW

15.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.48

2.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

15 W

15 W

PSB

0 W

0 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.70 kW

Annual energy consumption Qhe

3341 kWh

5183 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

224 %

162 %

Prated

14.15 kW

15.28 kW

SCOP

6.79

4.25

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.57 kW

9.88 kW

COP Tj = -7°C

5.62

3.91

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

5.24 kW

6.08 kW

COP Tj = +2°C

6.13

4.64

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

3.79 kW

4.02 kW

COP Tj = +7°C

6.00

4.91

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

3.82 kW

3.81 kW

COP Tj = 12°C

5.83

5.32

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

14.15 kW

15.28 kW

COP Tj = Tbiv

4.47

2.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.15 kW

15.28 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.47

2.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

15 W

15 W

PSB

0 W

0 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.72 kW

Annual energy consumption Qhe

5953 kWh

9187 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.55

12.76

COP Tj = -15°C (if TOL<-20°C)

5.01

3.40

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

13.00 kW

ηs

217 %

159 %

Prated

13.09 kW

15.29 kW

SCOP

5.63

4.17

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.43 kW

14.21 kW

COP Tj = -7°C

4.81

3.21

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

7.24 kW

8.74 kW

COP Tj = +2°C

5.68

4.14

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.88 kW

5.75 kW

COP Tj = +7°C

6.06

4.72

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

3.85 kW

3.80 kW

COP Tj = 12°C

6.00

5.24

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

13.09 kW

15.29 kW

COP Tj = Tbiv

4.56

2.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.09 kW

15.29 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.56

2.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

15 W

15 W

PSB

0 W

0 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.71 kW

Backup Heater

0.00 kW

Annual energy consumption Qhe

4763 kWh

7914 kWh

VITOCAL 300-G BWC 301.C16 SC
Configure model
Model name
VITOCAL 300-G BWC 301.C16 SC
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.51 kW

6.78 kW

El input

1.51 kW

2.83 kW

COP

5.00

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

215 %

155 %

Prated

14.00 kW

15.30 kW

SCOP

5.59

4.08

Tbiv

-10 °C

-10 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

14.00 kW

15.30 kW

COP Tj = +2°C

4.48

2.97

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

9.03 kW

10.43 kW

COP Tj = +7°C

5.42

3.72

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

4.12 kW

4.68 kW

COP Tj = 12°C

5.96

4.75

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

14.00 kW

15.30 kW

COP Tj = Tbiv

4.48

2.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.00 kW

15.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.48

2.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

15 W

15 W

PSB

0 W

0 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.70 kW

Annual energy consumption Qhe

3341 kWh

5183 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

224 %

162 %

Prated

14.15 kW

15.28 kW

SCOP

6.79

4.25

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.57 kW

9.88 kW

COP Tj = -7°C

5.62

3.91

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

5.24 kW

6.08 kW

COP Tj = +2°C

6.13

4.64

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

3.79 kW

4.02 kW

COP Tj = +7°C

6.00

4.91

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

3.82 kW

3.81 kW

COP Tj = 12°C

5.83

5.32

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

14.15 kW

15.28 kW

COP Tj = Tbiv

4.47

2.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.15 kW

15.28 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.47

2.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

15 W

15 W

PSB

0 W

0 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.72 kW

Annual energy consumption Qhe

5953 kWh

9187 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.55

12.76

COP Tj = -15°C (if TOL<-20°C)

5.01

3.40

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

13.00 kW

ηs

217 %

159 %

Prated

13.09 kW

15.29 kW

SCOP

5.63

4.17

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.43 kW

14.21 kW

COP Tj = -7°C

4.81

3.21

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

7.24 kW

8.74 kW

COP Tj = +2°C

5.68

4.14

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.88 kW

5.75 kW

COP Tj = +7°C

6.06

4.72

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

3.85 kW

3.80 kW

COP Tj = 12°C

6.00

5.24

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

13.09 kW

15.29 kW

COP Tj = Tbiv

4.56

2.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.09 kW

15.29 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.56

2.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

15 W

15 W

PSB

0 W

0 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.71 kW

Backup Heater

0.00 kW

Annual energy consumption Qhe

4763 kWh

7914 kWh