1,720 kg
Heating
EN 14511-2
Heat output
7.50 kW
El input
1.55 kW
COP
4.84
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level indoor
44 dB(A)
Sound power level outdoor
0 dB(A)
EN 14825
ηs
204 %
Prated
8.00 kW
SCOP
5.31
Tbiv
2 °C
TOL
0 °C
Pdh Tj = -7°C
0.00 kW
COP Tj = -7°C
0.00
Pdh Tj = +2°C
7.50 kW
COP Tj = +2°C
4.84
Pdh Tj = +7°C
7.60 kW
COP Tj = +7°C
5.17
Pdh Tj = 12°C
7.70 kW
COP Tj = 12°C
5.73
Pdh Tj = Tbiv
7.50 kW
COP Tj = Tbiv
4.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.84
Rated airflow rate
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
WTOL
65 °C
Poff
0 W
PTO
54 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
1888 kWh
Colder Climate
EN 12102-1
Sound power level indoor
44 dB(A)
Sound power level outdoor
0 dB(A)
EN 14825
ηs
211 %
Prated
9.00 kW
SCOP
5.48
Tbiv
-15 °C
TOL
-22 °C
Pdh Tj = -7°C
7.60 kW
COP Tj = -7°C
5.42
Pdh Tj = +2°C
7.70 kW
COP Tj = +2°C
5.70
Pdh Tj = +7°C
7.70 kW
COP Tj = +7°C
5.93
Pdh Tj = 12°C
7.70 kW
COP Tj = 12°C
5.97
Pdh Tj = Tbiv
7.60 kW
COP Tj = Tbiv
5.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.31
Rated airflow rate
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
WTOL
65 °C
Poff
0 W
PTO
54 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
1.80 kW
Annual energy consumption Qhe
4184 kWh
Average Climate
EN 12102-1
Sound power level indoor
44 dB(A)
Sound power level outdoor
0 dB(A)
EN 14825
ηs
205 %
Prated
8.00 kW
SCOP
5.32
Tbiv
-10 °C
TOL
-10 °C
Pdh Tj = -7°C
7.50 kW
COP Tj = -7°C
4.90
Cdh Tj = -7 °C
0.90
Pdh Tj = +2°C
7.60 kW
COP Tj = +2°C
5.25
Cdh Tj = +2 °C
0.90
Pdh Tj = +7°C
7.60 kW
COP Tj = +7°C
5.60
Cdh Tj = +7 °C
0.90
Pdh Tj = 12°C
7.70 kW
COP Tj = 12°C
5.99
Cdh Tj = +12 °C
0.90
Pdh Tj = Tbiv
7.50 kW
COP Tj = Tbiv
4.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.84
Rated airflow rate
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
WTOL
65 °C
Poff
0 W
PTO
54 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
2912 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.50 kW
6.91 kW
El input
1.55 kW
2.35 kW
COP
4.84
2.94
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
52 dB(A)
Sound power level outdoor
0 dB(A)
0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
205 %
139 %
Prated
8.00 kW
7.00 kW
SCOP
5.32
3.67
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.50 kW
7.00 kW
COP Tj = -7°C
4.90
3.07
Pdh Tj = +2°C
7.60 kW
7.20 kW
COP Tj = +2°C
5.25
3.61
Pdh Tj = +7°C
7.60 kW
7.30 kW
COP Tj = +7°C
5.60
4.02
Pdh Tj = 12°C
7.70 kW
7.40 kW
COP Tj = 12°C
5.99
4.52
Pdh Tj = Tbiv
7.50 kW
6.90 kW
COP Tj = Tbiv
4.84
2.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.50 kW
6.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.84
2.94
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
54 W
54 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2912 kWh
3891 kWh