DAIKIN ALTHERMA 3 LT SPLIT 11KW (180L)

Certificate Holder
DAIKIN Europe N.V.
Zandvoordestraat 300
B-8400 Oostende
Belgium
Reg. No.
011-1W0319
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
DAIKIN ALTHERMA 3 LT SPLIT 11KW (180L)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass Of Refrigerant

3,500 kg

Certification Date
06.03.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 14

Models

EPGA11DV / EAVX16S18D6V(G)
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l

EPGA11DV / EAVX16S18D9W(G)
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l

EPGA11DV / EABX16D6V
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

EPGA11DV / EABX16D9W
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

EPGA11DV / EABH16D6V
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

129 %

Prated

11.00 kW

13.00 kW

SCOP

4.38

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5189 kWh

7845 kWh

EPGA11DV / EAVH16S18D6V(G)
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

129 %

Prated

11.00 kW

13.00 kW

SCOP

4.38

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5189 kWh

7845 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l

EPGA11DV / EAVZ16S18D6V
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

129 %

Prated

11.00 kW

13.00 kW

SCOP

4.38

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5189 kWh

7845 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l

EPGA11DV / EAVZ16S18D9W
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

129 %

Prated

11.00 kW

13.00 kW

SCOP

4.38

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5189 kWh

7845 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l

EPGA11DV / EAVH16S18D9W(G)
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

129 %

Prated

11.00 kW

13.00 kW

SCOP

4.38

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5189 kWh

7845 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l

EPGA11DV / EABH16D9W
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

129 %

Prated

11.00 kW

13.00 kW

SCOP

4.38

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5189 kWh

7845 kWh

EPGA11DV / EABH16D6V + cooling kit
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

EPGA11DV / EABH16D9W + cooling kit
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

EPGA11DV / EAVH16S18D6V(G) + cooling kit
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l

EPGA11DV / EAVH16S18D9W(G) + cooling kit
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.10 kW

15.84 kW

El input

2.16 kW

5.17 kW

COP

5.15

3.06

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

130 %

Prated

11.00 kW

13.00 kW

SCOP

4.44

3.32

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

11.50 kW

COP Tj = -7°C

3.07

2.25

Cdh

1.00

1.00

Pdh Tj = +2°C

6.30 kW

6.50 kW

COP Tj = +2°C

4.15

3.14

Cdh

1.00

1.00

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

5.86

4.27

Cdh

0.96

0.96

Pdh Tj = 12°C

5.30 kW

5.20 kW

COP Tj = 12°C

7.88

5.75

Cdh

0.95

0.95

Pdh Tj = Tbiv

11.00 kW

12.50 kW

COP Tj = Tbiv

2.80

2.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

2.11

WTOL

35 °C

55 °C

Poff

21 W

21 W

PTO

41 W

41 W

PSB

21 W

21 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

electrical

electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5112 kWh

7768 kWh

Cooling

EN 14511-2

+7°C/+12°C

El input

3.30 kW

Cooling capacity

10.66

EER

3.23

EN 14825

+7°C/+12°C

Pdesignc

10.7 kW

SEER

5.1

Pdc Tj = 35°C

10.66 kW

EER Tj = 35°C

3.23

Pdc Tj = 30°C

7.87 kW

EER Tj = 30°C

4.32

Cdc

1

Pdc Tj = 25°C

5.16 kW

EER Tj = 25°C

6.16

Cdc

1

Pdc Tj = 20°C

7.86 kW

EER Tj = 20°C

6.65

Cdc

1

Poff

21 W

PTO

41 W

PSB

21 W

PCK

0 W

Annual energy consumption Qce

1260 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

104 %

COP

2.51

Heating up time

0:57 h:min

Standby power input

32.8 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

240 l