Certificate holders

Subtype

DAIKIN ALTHERMA LT SPLIT / ROTEX HPSU BI-BLOC 16 KW (3PH)

Certificate Holder
DAIKIN Europe N.V.
Zandvoordestraat 300
B-8400 Oostende
Belgium
Reg. No.
011-1W0078
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
DAIKIN ALTHERMA LT SPLIT / ROTEX HPSU BI-BLOC 16 KW (3PH)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410a
Mass Of Refrigerant

3,400 kg

Certification Date
31.03.2017
Testing basis
HP KEYMARK certification scheme rules rev. no. 1.1
Generate PDF Export model CSV
  • Number of models 9

Models

ERLQ016CW1 / EHBH16CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

ERLQ016CW1 / EHBX16CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

ERLQ016CW1 / EHVH16S18CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

87 %

COP

2.14

Heating up time

1:04 h:min

Standby power input

50.0 W

Reference hot water temperature

50.1 °C

Mixed water at 40°C

224 l

ERLQ016CW1 / EHVH16S26CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

98 %

COP

2.02

Heating up time

1:25 h:min

Standby power input

45.1 W

Reference hot water temperature

50.2 °C

Mixed water at 40°C

338 l

ERLQ016CW1 / EHVX16S18CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

87 %

COP

2.14

Heating up time

1:04 h:min

Standby power input

50.0 W

Reference hot water temperature

50.1 °C

Mixed water at 40°C

224 l

ERLQ016CW1 / EHVX16S26CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

98 %

COP

2.02

Heating up time

1:25 h:min

Standby power input

45.1 W

Reference hot water temperature

50.2 °C

Mixed water at 40°C

338 l

ERLQ016CW1 / EHVZ16S18CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

15.90 kW

15.04 kW

El input

3.77 kW

5.37 kW

COP

4.22

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

87 %

COP

2.14

Heating up time

1:04 h:min

Standby power input

50.0 W

Reference hot water temperature

50.1 °C

Mixed water at 40°C

224 l

RRLQ016CW1 / RHBH16CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Cdh

1.00

1.00

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Cdh

1.00

1.00

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Cdh

0.94

1.00

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Cdh

0.92

0.93

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh

RRLQ016CW1 / RHBX16CB *
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.04 kW

El input

3.76 kW

5.37 kW

COP

4.25

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

119 %

Prated

16.00 kW

13.90 kW

SCOP

3.80

3.06

Tbiv

-4 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

12.20 kW

COP Tj = -7°C

2.33

1.78

Pdh Tj = +2°C

8.62 kW

7.61 kW

COP Tj = +2°C

3.74

3.12

Pdh Tj = +7°C

5.74 kW

4.83 kW

COP Tj = +7°C

6.77

4.40

Pdh Tj = 12°C

6.50 kW

5.38 kW

COP Tj = 12°C

8.97

6.36

Pdh Tj = Tbiv

12.10 kW

12.20 kW

COP Tj = Tbiv

2.56

1.78

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.71

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

4.35 kW

0.58 kW

Annual energy consumption Qhe

8270 kWh

8970 kWh