Certificate holders

Subtype

Sheen EVO/EVO 2.0 - 10.1, 12.1, 14.1

Certificate Holder
Clivet s.p.a.
Via camp lonc 25 c.ap.
I-32032 z.i. Villapaiera - Feltre (BL)
Italy
Registration number
ICIM-PDC-000060 / 01
Certification Body
ICIM S.p.A.
Subtype title
Sheen EVO/EVO 2.0 - 10.1, 12.1, 14.1
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

7,900 kg

Certification Date
20.01.2020
Testing basis
HP KEYMARK certification scheme rules rev. no. 7
Generate PDF Export model CSV Download certificate
  • Number of models 15

Models

WSAN-YSI 10.1
Configure model
Model name
WSAN-YSI 10.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Heat output

25.30 kW

El input

6.07 kW

COP

4.17

Average Climate

EN 12102-1

Sound power level outdoor

75 dB(A)

EN 14825

ηs

169 %

Prated

21.00 kW

SCOP

4.30

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

18.30 kW

COP Tj = -7°C

2.95

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

11.20 kW

COP Tj = +2°C

4.10

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

7.20 kW

COP Tj = +7°C

5.60

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

7.10 kW

COP Tj = 12°C

6.82

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

20.70 kW

COP Tj = Tbiv

2.73

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

20.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.73

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

54 °C

Poff

19 W

PTO

200 W

PSB

19 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

9946 kWh

WSAN-YSI 12.1
Configure model
Model name
WSAN-YSI 12.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Heat output

28.20 kW

El input

6.64 kW

COP

4.25

Average Climate

EN 12102-1

Sound power level outdoor

76 dB(A)

EN 14825

ηs

167 %

Prated

22.00 kW

SCOP

4.25

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

19.10 kW

COP Tj = -7°C

2.92

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

11.60 kW

COP Tj = +2°C

4.00

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

7.50 kW

COP Tj = +7°C

5.65

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

7.10 kW

COP Tj = 12°C

6.82

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

21.60 kW

COP Tj = Tbiv

2.70

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

WTOL

54 °C

Poff

19 W

PTO

200 W

PSB

19 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

10500 kWh

WSAN-YSI 14.1
Configure model
Model name
WSAN-YSI 14.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Heat output

32.00 kW

El input

7.69 kW

COP

4.16

Average Climate

EN 12102-1

Sound power level outdoor

76 dB(A)

EN 14825

ηs

167 %

Prated

24.00 kW

SCOP

4.24

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

20.90 kW

COP Tj = -7°C

2.86

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

12.70 kW

COP Tj = +2°C

3.98

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

8.20 kW

COP Tj = +7°C

5.75

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

7.10 kW

COP Tj = 12°C

6.82

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

23.60 kW

COP Tj = Tbiv

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

23.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

WTOL

54 °C

Poff

19 W

PTO

200 W

PSB

19 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

11514 kWh

WiSAN-YSE1 EXC-SC 10.1
Configure model
Model name
WiSAN-YSE1 EXC-SC 10.1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

26.10 kW

23.00 kW

El input

5.82 kW

9.06 kW

COP

4.48

2.54

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

73 dB(A)

73 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

127 %

Prated

19.24 kW

16.78 kW

SCOP

4.54

3.24

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

17.18 kW

13.04 kW

COP Tj = -7°C

2.65

1.93

Cdh Tj = -7 °C

0.980

Pdh Tj = +2°C

11.38 kW

9.50 kW

COP Tj = +2°C

4.72

3.25

Cdh Tj = +2 °C

0.980

Pdh Tj = +7°C

12.42 kW

11.10 kW

COP Tj = +7°C

5.65

4.40

Cdh Tj = +7 °C

0.980

Pdh Tj = 12°C

14.75 kW

13.45 kW

COP Tj = 12°C

7.42

6.15

Cdh Tj = +12 °C

0.980

Pdh Tj = Tbiv

17.18 kW

14.20 kW

COP Tj = Tbiv

2.65

2.02

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.67 kW

9.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.58

1.35

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

0.980

WTOL

35 °C

55 °C

Poff

50 W

50 W

PTO

100 W

100 W

PSB

50 W

50 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.76 kW

7.63 kW

Annual energy consumption Qhe

8838 kWh

10709 kWh

WiSAN-YSE1 EXC-SC 12.1
Configure model
Model name
WiSAN-YSE1 EXC-SC 12.1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

30.50 kW

27.70 kW

El input

7.04 kW

11.50 kW

COP

4.33

2.40

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

74 dB(A)

74 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

126 %

Prated

22.50 kW

19.53 kW

SCOP

4.49

3.22

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

19.90 kW

15.95 kW

COP Tj = -7°C

2.63

1.94

Cdh Tj = -7 °C

0.980

0.980

Pdh Tj = +2°C

12.43 kW

10.80 kW

COP Tj = +2°C

4.61

3.20

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

12.42 kW

11.47 kW

COP Tj = +7°C

5.68

4.41

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

14.76 kW

13.80 kW

COP Tj = 12°C

7.54

6.14

Cdh Tj = +12 °C

0.980

0.980

Pdh Tj = Tbiv

19.90 kW

16.52 kW

COP Tj = Tbiv

2.63

2.02

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.28 kW

10.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.63

1.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

0.980

WTOL

35 °C

55 °C

Poff

50 W

50 W

PTO

100 W

100 W

PSB

50 W

50 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

5.21 kW

9.53 kW

Annual energy consumption Qhe

10358 kWh

12516 kWh

WiSAN-YSE1 EXC-SC 14.1
Configure model
Model name
WiSAN-YSE1 EXC-SC 14.1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

37.00 kW

32.60 kW

El input

8.86 kW

14.00 kW

COP

4.22

2.33

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

75 dB(A)

75 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

124 %

Prated

25.50 kW

22.97 kW

SCOP

4.44

3.19

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

22.60 kW

18.82 kW

COP Tj = -7°C

2.63

1.89

Cdh Tj = -7 °C

0.980

0.980

Pdh Tj = +2°C

13.25 kW

12.44 kW

COP Tj = +2°C

4.50

3.15

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

12.44 kW

11.48 kW

COP Tj = +7°C

5.71

4.40

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

14.77 kW

13.82 kW

COP Tj = 12°C

7.51

6.36

Cdh Tj = +12 °C

0.980

0.980

Pdh Tj = Tbiv

22.60 kW

19.44 kW

COP Tj = Tbiv

2.63

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.38 kW

11.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.63

1.25

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

0.980

WTOL

35 °C

55 °C

Poff

50 W

50 W

PTO

100 W

100 W

PSB

50 W

50 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

7.17 kW

11.97 kW

Annual energy consumption Qhe

11895 kWh

14903 kWh

WiSAN-YSE1 EXC-EN 10.1
Configure model
Model name
WiSAN-YSE1 EXC-EN 10.1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

21.50 kW

17.60 kW

El input

4.76 kW

6.64 kW

COP

4.52

2.62

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

69 dB(A)

69 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

126 %

Prated

14.28 kW

14.49 kW

SCOP

4.41

3.24

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.63 kW

11.86 kW

COP Tj = -7°C

2.56

2.02

Cdh Tj = -7 °C

0.970

0.980

Pdh Tj = +2°C

10.50 kW

9.50 kW

COP Tj = +2°C

4.72

3.20

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

12.42 kW

11.10 kW

COP Tj = +7°C

5.65

4.40

Cdh Tj = +7 °C

0.970

0.980

Pdh Tj = 12°C

14.75 kW

13.45 kW

COP Tj = 12°C

7.42

6.15

Cdh Tj = +12 °C

0.970

0.980

Pdh Tj = Tbiv

12.63 kW

12.26 kW

COP Tj = Tbiv

2.56

2.09

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.39 kW

8.63 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.33

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.980

WTOL

35 °C

55 °C

Poff

50 W

50 W

PTO

100 W

100 W

PSB

50 W

50 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

2.89 kW

5.86 kW

Annual energy consumption Qhe

6681 kWh

9272 kWh

WiSAN-YSE1 EXC-EN 12.1
Configure model
Model name
WiSAN-YSE1 EXC-EN 12.1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

24.30 kW

19.70 kW

El input

5.54 kW

7.70 kW

COP

4.40

2.56

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

71 dB(A)

71 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

126 %

Prated

17.18 kW

15.92 kW

SCOP

4.38

3.23

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

15.20 kW

13.03 kW

COP Tj = -7°C

2.50

1.98

Cdh Tj = -7 °C

0.970

0.980

Pdh Tj = +2°C

10.57 kW

9.50 kW

COP Tj = +2°C

4.62

3.20

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

12.50 kW

11.47 kW

COP Tj = +7°C

2.60

4.41

Cdh Tj = +7 °C

0.970

0.980

Pdh Tj = 12°C

14.82 kW

13.80 kW

COP Tj = 12°C

7.32

6.14

Cdh Tj = +12 °C

0.970

0.980

Pdh Tj = Tbiv

15.20 kW

13.47 kW

COP Tj = Tbiv

2.50

2.07

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.41 kW

9.09 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.39

1.35

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.980

WTOL

35 °C

55 °C

Poff

50 W

50 W

PTO

100 W

100 W

PSB

50 W

50 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

2.77 kW

6.83 kW

Annual energy consumption Qhe

8100 kWh

10191 kWh

WiSAN-YSE1 EXC-EN 14.1
Configure model
Model name
WiSAN-YSE1 EXC-EN 14.1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

26.90 kW

21.80 kW

El input

6.17 kW

8.27 kW

COP

4.35

2.64

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

72 dB(A)

72 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

126 %

Prated

19.55 kW

17.21 kW

SCOP

4.35

3.22

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

17.29 kW

14.09 kW

COP Tj = -7°C

2.38

1.97

Cdh Tj = -7 °C

0.970

0.980

Pdh Tj = +2°C

10.68 kW

9.31 kW

COP Tj = +2°C

4.59

3.19

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

12.52 kW

11.10 kW

COP Tj = +7°C

5.60

4.40

Cdh Tj = +7 °C

0.970

0.980

Pdh Tj = 12°C

14.85 kW

13.45 kW

COP Tj = 12°C

7.30

6.15

Cdh Tj = +12 °C

0.970

0.980

Pdh Tj = Tbiv

17.29 kW

14.56 kW

COP Tj = Tbiv

2.38

2.00

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.06 kW

10.21 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.32

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.970

0.980

WTOL

35 °C

55 °C

Poff

50 W

50 W

PTO

100 W

100 W

PSB

50 W

50 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

3.49 kW

7.00 kW

Annual energy consumption Qhe

9282 kWh

11062 kWh

WiSAN-YSE1 PRM-SC 10.1
Configure model
Model name
WiSAN-YSE1 PRM-SC 10.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

27.90 kW

El input

6.39 kW

COP

4.36

Average Climate

EN 12102-1

Sound power level outdoor

75 dB(A)

EN 14825

ηs

169 %

Prated

20.48 kW

SCOP

4.29

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

18.12 kW

COP Tj = -7°C

2.40

Cdh Tj = -7 °C

0.980

Pdh Tj = +2°C

11.61 kW

COP Tj = +2°C

4.48

Cdh Tj = +2 °C

0.980

Pdh Tj = +7°C

12.42 kW

COP Tj = +7°C

5.37

Cdh Tj = +7 °C

0.980

Pdh Tj = 12°C

14.75 kW

COP Tj = 12°C

7.12

Cdh Tj = +12 °C

0.980

Pdh Tj = Tbiv

18.12 kW

COP Tj = Tbiv

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.47

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

WTOL

35 °C

Poff

50 W

PTO

100 W

PSB

50 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

2.90 kW

Annual energy consumption Qhe

9865 kWh

WiSAN-YSE1 PRM-SC 12.1
Configure model
Model name
WiSAN-YSE1 PRM-SC 12.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

32.20 kW

El input

8.05 kW

COP

4.01

Average Climate

EN 12102-1

Sound power level outdoor

76 dB(A)

EN 14825

ηs

166 %

Prated

23.40 kW

SCOP

4.23

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

20.70 kW

COP Tj = -7°C

2.50

Cdh Tj = -7 °C

0.980

Pdh Tj = +2°C

12.11 kW

COP Tj = +2°C

4.34

Cdh Tj = +2 °C

0.980

Pdh Tj = +7°C

12.34 kW

COP Tj = +7°C

5.39

Cdh Tj = +7 °C

0.980

Pdh Tj = 12°C

14.65 kW

COP Tj = 12°C

6.73

Cdh Tj = +12 °C

0.980

Pdh Tj = Tbiv

20.70 kW

COP Tj = Tbiv

2.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.34 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

WTOL

35 °C

Poff

50 W

PTO

100 W

PSB

50 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

6.06 kW

Annual energy consumption Qhe

11432 kWh

WiSAN-YSE1 PRM-SC 14.1
Configure model
Model name
WiSAN-YSE1 PRM-SC 14.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

38.00 kW

El input

10.30 kW

COP

3.70

Average Climate

EN 12102-1

Sound power level outdoor

77 dB(A)

EN 14825

ηs

162 %

Prated

25.90 kW

SCOP

4.11

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

22.95 kW

COP Tj = -7°C

2.59

Cdh Tj = -7 °C

0.980

Pdh Tj = +2°C

13.09 kW

COP Tj = +2°C

4.16

Cdh Tj = +2 °C

0.980

Pdh Tj = +7°C

12.39 kW

COP Tj = +7°C

5.17

Cdh Tj = +7 °C

0.980

Pdh Tj = 12°C

14.70 kW

COP Tj = 12°C

6.44

Cdh Tj = +12 °C

0.980

Pdh Tj = Tbiv

22.95 kW

COP Tj = Tbiv

2.59

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.49 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

WTOL

35 °C

Poff

50 W

PTO

100 W

PSB

50 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

7.45 kW

Annual energy consumption Qhe

13028 kWh

WiSAN-YSE1 PRM-EN 10.1
Configure model
Model name
WiSAN-YSE1 PRM-EN 10.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

21.10 kW

El input

4.86 kW

COP

4.35

Average Climate

EN 12102-1

Sound power level indoor

72 dB(A)

Sound power level outdoor

72 dB(A)

EN 14825

ηs

164 %

Prated

15.95 kW

SCOP

4.18

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

14.11 kW

COP Tj = -7°C

2.60

Cdh Tj = -7 °C

0.980

Pdh Tj = +2°C

10.50 kW

COP Tj = +2°C

4.48

Cdh Tj = +2 °C

0.980

Pdh Tj = +7°C

12.42 kW

COP Tj = +7°C

5.30

Cdh Tj = +7 °C

0.980

Pdh Tj = 12°C

14.75 kW

COP Tj = 12°C

6.51

Cdh Tj = +12 °C

0.980

Pdh Tj = Tbiv

14.11 kW

COP Tj = Tbiv

2.60

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

WTOL

35 °C

Poff

50 W

PTO

100 W

PSB

50 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

2.88 kW

Annual energy consumption Qhe

7886 kWh

WiSAN-YSE1 PRM-EN 12.1
Configure model
Model name
WiSAN-YSE1 PRM-EN 12.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

24.50 kW

El input

5.79 kW

COP

4.24

Average Climate

EN 12102-1

Sound power level outdoor

73 dB(A)

EN 14825

ηs

162 %

Prated

18.60 kW

SCOP

4.12

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

16.44 kW

COP Tj = -7°C

2.43

Cdh Tj = -7 °C

0.950

Pdh Tj = +2°C

11.20 kW

COP Tj = +2°C

4.38

Cdh Tj = +2 °C

0.950

Pdh Tj = +7°C

12.42 kW

COP Tj = +7°C

5.30

Cdh Tj = +7 °C

0.950

Pdh Tj = 12°C

14.75 kW

COP Tj = 12°C

6.51

Cdh Tj = +12 °C

0.950

Pdh Tj = Tbiv

16.44 kW

COP Tj = Tbiv

2.43

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.35

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.950

WTOL

35 °C

Poff

50 W

PTO

100 W

PSB

50 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

3.22 kW

Annual energy consumption Qhe

9320 kWh

WiSAN-YSE1 PRM-EN 14.1
Configure model
Model name
WiSAN-YSE1 PRM-EN 14.1
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

27.50 kW

El input

6.51 kW

COP

4.22

Average Climate

EN 12102-1

Sound power level outdoor

73 dB(A)

EN 14825

ηs

159 %

Prated

20.60 kW

SCOP

4.05

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

18.20 kW

COP Tj = -7°C

2.30

Cdh Tj = -7 °C

0.950

Pdh Tj = +2°C

12.00 kW

COP Tj = +2°C

4.28

Cdh Tj = +2 °C

0.950

Pdh Tj = +7°C

12.52 kW

COP Tj = +7°C

5.22

Cdh Tj = +7 °C

0.950

Pdh Tj = 12°C

14.85 kW

COP Tj = 12°C

6.51

Cdh Tj = +12 °C

0.950

Pdh Tj = Tbiv

18.20 kW

COP Tj = Tbiv

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.09 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.28

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.950

WTOL

35 °C

Poff

50 W

PTO

100 W

PSB

50 W

PCK

10 W

Supplementary Heater: Type of energy input

n/a

Supplementary Heater: PSUP

3.48 kW

Annual energy consumption Qhe

10501 kWh