Certificate holders

Subtype

CTC EcoPart 414

Certificate Holder
CTC AB
Box 309, Näsvägen
SE-341 26 Ljungby
Sweden
Registration number
012-066 / Issue 2
Certification Body
RISE CERT
Subtype title
CTC EcoPart 414
Driving energy
n/a
Heat Pump Type
Brine/Water
Refrigerant
R407c
Mass of Refrigerant

2,700 kg

Certification Date
n/a
Testing basis
EN 14511:2013, EN 14825:2013, EN12102:2013
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

CTC EcoPart 414 1x230V
Configure model
Model name
CTC EcoPart 414 1x230V
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

14.51 kW

13.45 kW

El input

3.19 kW

4.32 kW

COP

4.55

3.11

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

140 %

Prated

16.30 kW

15.19 kW

SCOP

4.60

3.70

Tbiv

-18 °C

-18 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

14.70 kW

13.80 kW

COP Tj = -7°C

4.84

3.59

Pdh Tj = +2°C

14.80 kW

14.10 kW

COP Tj = +2°C

4.98

3.94

Pdh Tj = +7°C

14.90 kW

14.30 kW

COP Tj = +7°C

5.08

4.26

Pdh Tj = 12°C

14.90 kW

14.50 kW

COP Tj = 12°C

5.11

4.49

Pdh Tj = Tbiv

14.60 kW

13.60 kW

COP Tj = Tbiv

4.67

3.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.51 kW

13.45 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.55

3.11

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.96

0.99

WTOL

65 °C

65 °C

Poff

18 W

18 W

PTO

97 W

32 W

PSB

18 W

18 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.80 kW

1.70 kW

Annual energy consumption Qhe

8758 kWh

10139 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

137 %

Prated

16.47 kW

16.12 kW

SCOP

4.60

3.60

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

14.60 kW

13.60 kW

COP Tj = -7°C

4.64

3.29

Pdh Tj = +2°C

14.70 kW

13.90 kW

COP Tj = +2°C

4.81

3.68

Pdh Tj = +7°C

14.80 kW

14.20 kW

COP Tj = +7°C

4.97

4.03

Pdh Tj = 12°C

14.90 kW

14.40 kW

COP Tj = 12°C

5.13

4.37

Pdh Tj = Tbiv

14.60 kW

13.60 kW

COP Tj = Tbiv

4.64

3.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.51 kW

13.45 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.55

3.11

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.96

0.99

WTOL

65 °C

65 °C

Poff

18 W

18 W

PTO

97 W

35 W

PSB

18 W

18 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.00 kW

2.70 kW

Annual energy consumption Qhe

7467 kWh

9158 kWh

CTC EcoPart 414 3x400V
Configure model
Model name
CTC EcoPart 414 3x400V
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

14.51 kW

13.45 kW

El input

3.19 kW

4.32 kW

COP

4.55

3.11

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

140 %

Prated

16.30 kW

15.19 kW

SCOP

4.60

3.70

Tbiv

-18 °C

-18 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

14.70 kW

13.80 kW

COP Tj = -7°C

4.84

3.59

Pdh Tj = +2°C

14.80 kW

14.10 kW

COP Tj = +2°C

4.98

3.94

Pdh Tj = +7°C

14.90 kW

14.30 kW

COP Tj = +7°C

5.08

4.26

Pdh Tj = 12°C

14.90 kW

14.50 kW

COP Tj = 12°C

5.11

4.49

Pdh Tj = Tbiv

14.60 kW

13.60 kW

COP Tj = Tbiv

4.67

3.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.51 kW

13.45 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.55

3.11

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.96

0.99

WTOL

65 °C

65 °C

Poff

18 W

18 W

PTO

97 W

32 W

PSB

18 W

18 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.80 kW

1.70 kW

Annual energy consumption Qhe

8758 kWh

10139 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

137 %

Prated

16.47 kW

16.12 kW

SCOP

4.60

3.60

Tbiv

-7 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

14.60 kW

13.60 kW

COP Tj = -7°C

4.64

3.29

Pdh Tj = +2°C

14.70 kW

13.90 kW

COP Tj = +2°C

4.81

3.68

Pdh Tj = +7°C

14.80 kW

14.20 kW

COP Tj = +7°C

4.97

4.03

Pdh Tj = 12°C

14.90 kW

14.40 kW

COP Tj = 12°C

5.13

4.37

Pdh Tj = Tbiv

14.60 kW

13.60 kW

COP Tj = Tbiv

4.64

3.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.51 kW

13.45 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.55

3.11

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.96

0.99

WTOL

65 °C

65 °C

Poff

18 W

18 W

PTO

97 W

35 W

PSB

18 W

18 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.00 kW

2.70 kW

Annual energy consumption Qhe

7467 kWh

9158 kWh