0,950 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
El input
0.96 kW
1.74 kW
COP
4.65
2.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
32 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
214 %
150 %
Prated
7.11 kW
6.39 kW
SCOP
5.56
3.96
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.29 kW
5.65 kW
COP Tj = -7°C
4.85
3.09
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.83 kW
3.44 kW
COP Tj = +2°C
5.70
4.03
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.46 kW
2.21 kW
COP Tj = +7°C
6.15
4.55
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
2.16 kW
2.07 kW
COP Tj = 12°C
6.01
4.54
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
7.11 kW
6.39 kW
COP Tj = Tbiv
4.43
2.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.11 kW
6.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.43
2.81
WTOL
65 °C
65 °C
Poff
12 W
10 W
PTO
15 W
13 W
PSB
15 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2597 kWh
3291 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
223 %
157 %
Prated
7.11 kW
6.39 kW
SCOP
5.77
4.12
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.30 kW
3.87 kW
COP Tj = -7°C
5.67
3.84
Cdh Tj = -7 °C
0.98
0.99
Pdh Tj = +2°C
2.62 kW
2.35 kW
COP Tj = +2°C
6.21
4.51
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.17 kW
2.07 kW
COP Tj = +7°C
6.09
4.65
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
2.15 kW
2.09 kW
COP Tj = 12°C
5.84
4.54
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
7.11 kW
6.39 kW
COP Tj = Tbiv
4.43
2.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.11 kW
6.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.43
2.81
WTOL
65 °C
65 °C
Poff
12 W
10 W
PTO
15 W
13 W
PSB
15 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3008 kWh
3802 kWh
Pdh Tj = -15°C (if TOL<-20°C)
5.80
5.21
COP Tj = -15°C (if TOL<-20°C)
5.05
3.33
Cdh Tj = -15 °C
0.99
0.99
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
El input
1.58 kW
2.35 kW
COP
5.96
3.63
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
32 dB(A)
32 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
305 %
211 %
Prated
9.43 kW
8.51 kW
SCOP
7.82
5.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.34 kW
7.53 kW
COP Tj = -7°C
6.48
4.03
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
5.08 kW
4.58 kW
COP Tj = +2°C
7.93
5.47
Cdh Tj = +2 °C
0.99
1.00
Pdh Tj = +7°C
3.26 kW
2.95 kW
COP Tj = +7°C
8.76
6.55
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
2.91 kW
2.78 kW
COP Tj = 12°C
8.65
6.84
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
9.43 kW
8.51 kW
COP Tj = Tbiv
5.96
3.63
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.43 kW
8.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.96
3.63
WTOL
65 °C
65 °C
Poff
8 W
8 W
PTO
4 W
4 W
PSB
4 W
4 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2463 kWh
3186 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
317 %
219 %
Prated
9.43 kW
8.51 kW
SCOP
8.12
5.68
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.71 kW
5.15 kW
COP Tj = -7°C
7.77
5.12
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.47 kW
3.14 kW
COP Tj = +2°C
8.76
6.31
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
2.91 kW
2.78 kW
COP Tj = +7°C
8.76
6.85
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
2.89 kW
2.79 kW
COP Tj = 12°C
8.39
7.06
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
9.43 kW
8.51 kW
COP Tj = Tbiv
5.96
3.63
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.43 kW
8.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.96
3.63
WTOL
65 °C
65 °C
Poff
8 W
8 W
PTO
4 W
4 W
PSB
4 W
4 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2847 kWh
3676 kWh
Pdh Tj = -15°C (if TOL<-20°C)
7.69
6.94
COP Tj = -15°C (if TOL<-20°C)
6.87
4.37
Cdh Tj = -15 °C
1.00
1.00