Certificate holders

Subtype

OCHSNER SWK

Certificate Holder
OCHSNER Energie Technik GmbH
Krackowizerstraße 4
4020 Linz
Austria
Registration number
012-C700000
Certification Body
RISE CERT
Subtype title
OCHSNER SWK
Driving energy
Electricity
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R410A
Mass of Refrigerant

0,950 kg

Certification Date
11.12.2019
Testing basis
EN14511:2018;EN14825:2016;EN12102:2017
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

OCHSNER SWK007P8d
Configure model
Model name
OCHSNER SWK007P8d
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

El input

0.96 kW

1.74 kW

COP

4.65

2.90

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

32 dB(A)

32 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

214 %

150 %

Prated

7.11 kW

6.39 kW

SCOP

5.56

3.96

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.29 kW

5.65 kW

COP Tj = -7°C

4.85

3.09

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

3.83 kW

3.44 kW

COP Tj = +2°C

5.70

4.03

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

2.46 kW

2.21 kW

COP Tj = +7°C

6.15

4.55

Cdh Tj = +7 °C

0.96

0.97

Pdh Tj = 12°C

2.16 kW

2.07 kW

COP Tj = 12°C

6.01

4.54

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

7.11 kW

6.39 kW

COP Tj = Tbiv

4.43

2.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.11 kW

6.39 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.43

2.81

WTOL

65 °C

65 °C

Poff

12 W

10 W

PTO

15 W

13 W

PSB

15 W

13 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2597 kWh

3291 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

223 %

157 %

Prated

7.11 kW

6.39 kW

SCOP

5.77

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

4.30 kW

3.87 kW

COP Tj = -7°C

5.67

3.84

Cdh Tj = -7 °C

0.98

0.99

Pdh Tj = +2°C

2.62 kW

2.35 kW

COP Tj = +2°C

6.21

4.51

Cdh Tj = +2 °C

0.97

0.98

Pdh Tj = +7°C

2.17 kW

2.07 kW

COP Tj = +7°C

6.09

4.65

Cdh Tj = +7 °C

0.96

0.97

Pdh Tj = 12°C

2.15 kW

2.09 kW

COP Tj = 12°C

5.84

4.54

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

7.11 kW

6.39 kW

COP Tj = Tbiv

4.43

2.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.11 kW

6.39 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.43

2.81

WTOL

65 °C

65 °C

Poff

12 W

10 W

PTO

15 W

13 W

PSB

15 W

13 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3008 kWh

3802 kWh

Pdh Tj = -15°C (if TOL<-20°C)

5.80

5.21

COP Tj = -15°C (if TOL<-20°C)

5.05

3.33

Cdh Tj = -15 °C

0.99

0.99

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

El input

1.58 kW

2.35 kW

COP

5.96

3.63

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

32 dB(A)

32 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

305 %

211 %

Prated

9.43 kW

8.51 kW

SCOP

7.82

5.47

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.34 kW

7.53 kW

COP Tj = -7°C

6.48

4.03

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

5.08 kW

4.58 kW

COP Tj = +2°C

7.93

5.47

Cdh Tj = +2 °C

0.99

1.00

Pdh Tj = +7°C

3.26 kW

2.95 kW

COP Tj = +7°C

8.76

6.55

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

2.91 kW

2.78 kW

COP Tj = 12°C

8.65

6.84

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.43 kW

8.51 kW

COP Tj = Tbiv

5.96

3.63

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.43 kW

8.51 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.96

3.63

WTOL

65 °C

65 °C

Poff

8 W

8 W

PTO

4 W

4 W

PSB

4 W

4 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2463 kWh

3186 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

317 %

219 %

Prated

9.43 kW

8.51 kW

SCOP

8.12

5.68

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

5.71 kW

5.15 kW

COP Tj = -7°C

7.77

5.12

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

3.47 kW

3.14 kW

COP Tj = +2°C

8.76

6.31

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

2.91 kW

2.78 kW

COP Tj = +7°C

8.76

6.85

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

2.89 kW

2.79 kW

COP Tj = 12°C

8.39

7.06

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.43 kW

8.51 kW

COP Tj = Tbiv

5.96

3.63

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.43 kW

8.51 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.96

3.63

WTOL

65 °C

65 °C

Poff

8 W

8 W

PTO

4 W

4 W

PSB

4 W

4 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2847 kWh

3676 kWh

Pdh Tj = -15°C (if TOL<-20°C)

7.69

6.94

COP Tj = -15°C (if TOL<-20°C)

6.87

4.37

Cdh Tj = -15 °C

1.00

1.00