Certificate holders

Subtype

TTF 52

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0188
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTF 52
Driving energy
n/a
Heat Pump Type
Brine/Water
Refrigerant
R410A
Mass of Refrigerant

12,500 kg

Certification Date
04.09.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

TTF 52
Configure model
Model name
TTF 52
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

55.83 kW

52.18 kW

El input

11.61 kW

17.45 kW

COP

4.81

2.99

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

58 dB(A)

63 dB(A)

Sound power level outdoor

58 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

138 %

Prated

56.00 kW

52.00 kW

SCOP

5.18

3.65

Tbiv

2 °C

2 °C

TOL

0 °C

0 °C

Pdh Tj = +2°C

55.80 kW

55.20 kW

COP Tj = +2°C

4.81

2.99

Pdh Tj = +7°C

56.20 kW

53.30 kW

COP Tj = +7°C

5.12

3.39

Pdh Tj = 12°C

56.80 kW

54.90 kW

COP Tj = 12°C

5.65

4.19

Pdh Tj = Tbiv

55.80 kW

52.20 kW

COP Tj = Tbiv

4.81

2.99

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

55.80 kW

52.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

2.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

99 W

99 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

14419 kWh

19157 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

58 dB(A)

63 dB(A)

Sound power level outdoor

58 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

207 %

144 %

Prated

69.00 kW

65.00 kW

SCOP

5.38

3.80

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

56.50 kW

53.80 kW

COP Tj = -7°C

5.36

3.62

Pdh Tj = +2°C

56.80 kW

54.60 kW

COP Tj = +2°C

5.63

4.03

Pdh Tj = +7°C

57.00 kW

55.30 kW

COP Tj = +7°C

5.84

4.42

Pdh Tj = 12°C

57.00 kW

55.70 kW

COP Tj = 12°C

5.88

4.74

Pdh Tj = Tbiv

56.40 kW

53.30 kW

COP Tj = Tbiv

5.25

3.39

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

55.80 kW

52.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

2.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

99 W

99 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.28 kW

13.12 kW

Annual energy consumption Qhe

31644 kWh

42330 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

58 dB(A)

63 dB(A)

Sound power level outdoor

58 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

200 %

138 %

Prated

56.00 kW

52.00 kW

SCOP

5.20

3.65

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

55.90 kW

52.50 kW

COP Tj = -7°C

4.87

3.12

Pdh Tj = +2°C

56.30 kW

53.80 kW

COP Tj = +2°C

5.20

3.64

Pdh Tj = +7°C

56.70 kW

54.60 kW

COP Tj = +7°C

5.53

4.03

Pdh Tj = 12°C

57.00 kW

55.40 kW

COP Tj = 12°C

5.90

4.52

Pdh Tj = Tbiv

55.80 kW

52.20 kW

COP Tj = Tbiv

4.81

2.99

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

55.80 kW

52.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

2.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

99 W

99 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

22209 kWh

29469 kWh