4,000 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
23.00 kW
22.00 kW
El input
4.90 kW
7.12 kW
COP
4.65
3.09
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
150 %
Prated
28.00 kW
28.00 kW
SCOP
5.03
3.95
Tbiv
-16 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
23.80 kW
22.70 kW
COP Tj = -7°C
4.98
3.73
Pdh Tj = +2°C
12.00 kW
11.60 kW
COP Tj = +2°C
5.28
4.26
Pdh Tj = +7°C
12.10 kW
11.80 kW
COP Tj = +7°C
5.38
4.57
Pdh Tj = 12°C
12.10 kW
11.90 kW
COP Tj = 12°C
5.08
4.74
Pdh Tj = Tbiv
23.70 kW
22.40 kW
COP Tj = Tbiv
4.78
3.46
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
23.50 kW
22.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.57
3.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
60 W
60 W
PSB
7 W
7 W
PCK
70 W
70 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.50 kW
6.00 kW
Annual energy consumption Qhe
13740 kWh
17514 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
143 %
Prated
28.00 kW
28.00 kW
SCOP
4.83
3.78
Tbiv
-6 °C
-5 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
23.60 kW
22.20 kW
COP Tj = -7°C
4.70
3.27
Pdh Tj = +2°C
23.80 kW
22.80 kW
COP Tj = +2°C
4.91
3.83
Pdh Tj = +7°C
12.00 kW
11.70 kW
COP Tj = +7°C
5.26
4.31
Pdh Tj = 12°C
12.10 kW
11.80 kW
COP Tj = 12°C
5.26
4.58
Pdh Tj = Tbiv
23.60 kW
22.40 kW
COP Tj = Tbiv
4.73
3.45
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
23.50 kW
22.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.57
3.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
30 W
30 W
PSB
7 W
7 W
PCK
70 W
70 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.50 kW
6.00 kW
Annual energy consumption Qhe
11996 kWh
15287 kWh