4,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
18.60 kW
16.30 kW
El input
3.27 kW
4.81 kW
COP
5.60
3.20
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
53 dB(A)
53 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
179 %
Prated
18.30 kW
16.30 kW
SCOP
6.05
4.68
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
18.34 kW
16.60 kW
COP Tj = -7°C
5.66
3.63
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
18.56 kW
17.60 kW
COP Tj = +2°C
6.03
4.61
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
18.76 kW
18.20 kW
COP Tj = +7°C
6.39
5.40
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
18.96 kW
18.80 kW
COP Tj = 12°C
6.72
6.37
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
18.30 kW
16.30 kW
COP Tj = Tbiv
5.60
3.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.30 kW
16.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.60
3.39
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6249 kWh
7193 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
236 %
181 %
Prated
18.30 kW
16.30 kW
SCOP
6.09
4.73
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
18.30 kW
16.30 kW
COP Tj = +2°C
5.60
3.39
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
18.52 kW
17.20 kW
COP Tj = +7°C
5.95
4.18
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
18.82 kW
18.40 kW
COP Tj = 12°C
6.51
5.71
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
18.30 kW
16.30 kW
COP Tj = Tbiv
5.60
3.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.30 kW
16.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.60
3.39
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4012 kWh
4604 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
241 %
186 %
Prated
18.30 kW
16.30 kW
SCOP
6.22
4.86
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
18.59 kW
17.40 kW
COP Tj = -7°C
6.09
4.39
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
18.77 kW
18.10 kW
COP Tj = +2°C
6.41
5.26
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
18.90 kW
18.60 kW
COP Tj = +7°C
6.65
6.04
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
18.94 kW
19.00 kW
COP Tj = 12°C
6.59
6.70
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
18.30 kW
16.30 kW
COP Tj = Tbiv
5.60
3.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.30 kW
16.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.60
3.39
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7258 kWh
8276 kWh
Pdh Tj = -15°C (if TOL<-20°C)
0.01
0.01
COP Tj = -15°C (if TOL<-20°C)
0.01
0.01
Cdh Tj = -15 °C
1.00
1.00