3,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.90 kW
11.70 kW
El input
2.35 kW
3.43 kW
COP
5.50
3.23
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
53 dB(A)
53 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
227 %
176 %
Prated
12.90 kW
11.70 kW
SCOP
5.88
4.60
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.92 kW
11.88 kW
COP Tj = -7°C
5.55
3.63
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
13.06 kW
12.48 kW
COP Tj = +2°C
5.89
4.56
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
13.18 kW
12.84 kW
COP Tj = +7°C
6.22
5.29
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
13.30 kW
13.20 kW
COP Tj = 12°C
6.49
6.16
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
12.90 kW
11.70 kW
COP Tj = Tbiv
5.49
3.41
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.90 kW
11.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.49
3.41
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4535 kWh
5250 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
228 %
177 %
Prated
12.90 kW
11.70 kW
SCOP
5.90
4.63
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.90 kW
11.70 kW
COP Tj = +2°C
5.49
3.41
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
13.03 kW
12.24 kW
COP Tj = +7°C
5.82
4.15
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
13.22 kW
12.96 kW
COP Tj = 12°C
6.33
5.57
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
12.90 kW
11.70 kW
COP Tj = Tbiv
5.49
3.41
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.90 kW
11.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.49
3.41
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2920 kWh
3373 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
233 %
183 %
Prated
12.90 kW
11.70 kW
SCOP
6.04
4.77
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
13.08 kW
12.36 kW
COP Tj = -7°C
5.95
4.35
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
13.08 kW
12.78 kW
COP Tj = +2°C
6.24
5.16
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
13.26 kW
13.08 kW
COP Tj = +7°C
6.45
5.88
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
13.28 kW
13.32 kW
COP Tj = 12°C
6.35
6.43
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
12.90 kW
11.70 kW
COP Tj = Tbiv
5.49
3.41
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.90 kW
11.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.49
3.41
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5269 kWh
6049 kWh
Pdh Tj = -15°C (if TOL<-20°C)
0.01
0.01
COP Tj = -15°C (if TOL<-20°C)
0.01
0.01
Cdh Tj = -15 °C
1.00
1.00