1,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.00 kW
8.00 kW
El input
1.74 kW
2.86 kW
COP
4.60
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
67 dB(A)
69 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
125 %
Prated
7.00 kW
6.00 kW
SCOP
4.50
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.90 kW
5.10 kW
COP Tj = -7°C
2.65
1.84
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.59 kW
3.10 kW
COP Tj = +2°C
4.30
3.10
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
3.20 kW
2.00 kW
COP Tj = +7°C
7.00
4.65
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.50 kW
2.20 kW
COP Tj = 12°C
9.70
6.55
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
5.90 kW
5.10 kW
COP Tj = Tbiv
2.65
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.40 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.50
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
0 W
0 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.60 kW
1.50 kW
Annual energy consumption Qhe
3068 kWh
3724 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.00 kW
8.00 kW
El input
1.74 kW
2.86 kW
COP
4.60
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.94 kW
1.4 kW
Cooling capacity
6.5
7
EER
3.35
5
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.5 kW
7 kW
SEER
5.27
8.35
Pdc Tj = 35°C
6.5 kW
7 kW
EER Tj = 35°C
3.35
5
Pdc Tj = 30°C
4.79 kW
5.16 kW
EER Tj = 30°C
4.5
6.4
Cdc Tj = 30 °C
1
1
Pdc Tj = 25°C
2.9 kW
3.32 kW
EER Tj = 25°C
6
10
Cdc Tj = 25 °C
1
1
Pdc Tj = 20°C
3.4 kW
3.6 kW
EER Tj = 20°C
7.5
13.5
Cdc Tj = 20 °C
0.9
0.9
Poff
12 W
12 W
PTO
0 W
0 W
PSB
12 W
12 W
PCK
0 W
0 W
Annual energy consumption Qce
740 kWh
503 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
67 dB(A)
69 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
127 %
Prated
7.00 kW
6.00 kW
SCOP
4.55
3.25
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.90 kW
5.10 kW
COP Tj = -7°C
2.65
1.84
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.59 kW
3.10 kW
COP Tj = +2°C
4.30
3.10
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
3.20 kW
2.00 kW
COP Tj = +7°C
7.00
4.65
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.50 kW
2.20 kW
COP Tj = 12°C
9.70
6.55
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
5.90 kW
5.10 kW
COP Tj = Tbiv
2.65
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.40 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.50
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
0 W
0 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.60 kW
1.50 kW
Annual energy consumption Qhe
3024 kWh
3680 kWh