Certificate holders

Subtype

TTF 13 basic

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0047
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTF 13 basic
Driving energy
n/a
Heat Pump Type
Brine/Water
Refrigerant
R410A
Mass of Refrigerant

2,500 kg

Certification Date
01.11.2016
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 2

Models

TTF 13 basic, all climates
Configure model
Model name
TTF 13 basic, all climates
Application
Heating (low temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

12.59 kW

El input

2.85 kW

COP

4.42

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Sound power level indoor

53 dB(A)

EN 14825

ηs

189 %

Prated

13.00 kW

SCOP

4.92

Tbiv

-10 °C

TOL

-20 °C

Pdh Tj = -7°C

12.60 kW

COP Tj = -7°C

4.48

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

12.70 kW

COP Tj = +2°C

4.84

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

12.80 kW

COP Tj = +7°C

5.21

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

12.90 kW

COP Tj = 12°C

5.63

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

12.60 kW

COP Tj = Tbiv

4.42

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.42

WTOL

60 °C

Poff

0 W

PTO

78 W

PSB

3 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

5285 kWh

Warmer Climate

EN 14825

ηs

189 %

Prated

13.00 kW

SCOP

4.94

Tbiv

2 °C

TOL

0 °C

Pdh Tj = +2°C

12.60 kW

COP Tj = +2°C

4.42

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

12.70 kW

COP Tj = +7°C

4.76

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

12.90 kW

COP Tj = 12°C

5.34

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

12.60 kW

COP Tj = Tbiv

4.42

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.42

WTOL

60 °C

Poff

0 W

PTO

78 W

PSB

3 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

3407 kWh

Colder Climate

EN 14825

ηs

196 %

Prated

16.00 kW

SCOP

5.10

Tbiv

-15 °C

TOL

-22 °C

Pdh Tj = -7°C

12.80 kW

COP Tj = -7°C

5.02

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

12.80 kW

COP Tj = +2°C

5.31

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

12.90 kW

COP Tj = +7°C

5.56

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

12.90 kW

COP Tj = 12°C

5.60

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

12.70 kW

COP Tj = Tbiv

4.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.90

WTOL

60 °C

Poff

0 W

PTO

78 W

PSB

3 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

3.02 kW

Annual energy consumption Qhe

7542 kWh

Pdh Tj = -15°C (if TOL<-20°C)

12.70

COP Tj = -15°C (if TOL<-20°C)

4.90

Cdh Tj = -15 °C

0.90

TTF 13 basic, average climates
Configure model
Model name
TTF 13 basic, average climates
Application
Heating (medium temp)
Units
Indoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.59 kW

11.60 kW

El input

2.85 kW

4.52 kW

COP

4.42

2.57

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

122 %

Prated

13.00 kW

12.00 kW

SCOP

4.92

3.26

Tbiv

-10 °C

-10 °C

TOL

-20 °C

-10 °C

Pdh Tj = -7°C

12.60 kW

11.70 kW

COP Tj = -7°C

4.48

2.69

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

12.70 kW

12.00 kW

COP Tj = +2°C

4.84

3.20

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

12.80 kW

12.30 kW

COP Tj = +7°C

5.21

3.60

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

12.90 kW

12.50 kW

COP Tj = 12°C

5.63

4.09

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

12.60 kW

11.60 kW

COP Tj = Tbiv

4.42

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.60 kW

11.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.42

2.57

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

78 W

78 W

PSB

3 W

3 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5285 kWh

7350 kWh