Certificate holders

Subtype

TTL 15 AS, TTL 15 ACS

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0048
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTL 15 AS, TTL 15 ACS
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

4,200 kg

Certification Date
01.11.2016
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 2

Models

TTL 15 AS
Configure model
Model name
TTL 15 AS
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.68 kW

3.74 kW

El input

1.11 kW

1.37 kW

COP

4.23

2.73

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

151 %

122 %

Prated

8.00 kW

8.00 kW

SCOP

3.84

3.20

Tbiv

-8 °C

-8 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.80 kW

7.10 kW

COP Tj = -7°C

2.49

2.18

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.30 kW

4.20 kW

COP Tj = +2°C

4.04

3.30

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.50 kW

4.20 kW

COP Tj = +7°C

5.08

4.07

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

4.40 kW

4.00 kW

COP Tj = 12°C

6.30

5.14

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.10 kW

7.40 kW

COP Tj = Tbiv

2.42

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.60 kW

7.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.97

WTOL

65 °C

65 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

4303 kWh

5300 kWh

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

153 %

120 %

Prated

4.00 kW

4.00 kW

SCOP

3.91

2.99

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.20 kW

4.00 kW

COP Tj = +2°C

3.48

2.50

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.30 kW

3.90 kW

COP Tj = +7°C

4.46

3.16

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

4.30 kW

3.80 kW

COP Tj = 12°C

5.89

4.57

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.20 kW

4.00 kW

COP Tj = Tbiv

3.48

2.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.20 kW

9.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.15

1.98

WTOL

65 °C

65 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1367 kWh

1750 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

137 %

118 %

Prated

11.00 kW

12.00 kW

SCOP

3.51

3.05

Tbiv

-10 °C

-10 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.80 kW

7.00 kW

COP Tj = -7°C

2.72

2.45

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.30 kW

4.20 kW

COP Tj = +2°C

4.45

3.70

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.50 kW

4.30 kW

COP Tj = +7°C

5.44

4.53

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

4.40 kW

4.10 kW

COP Tj = 12°C

6.30

5.44

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.70 kW

7.90 kW

COP Tj = Tbiv

2.50

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.10 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.25

2.10

WTOL

65 °C

65 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11.20 kW

11.61 kW

Annual energy consumption Qhe

7727 kWh

9481 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.10

9.70

COP Tj = -15°C (if TOL<-20°C)

2.25

2.10

Cdh Tj = -15 °C

0.90

0.90

TTL 15 ACS
Configure model
Model name
TTL 15 ACS
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.68 kW

3.74 kW

El input

1.11 kW

1.37 kW

COP

4.23

2.73

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

159 %

127 %

Prated

8.00 kW

8.00 kW

SCOP

4.04

3.34

Tbiv

-8 °C

-8 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.80 kW

7.10 kW

COP Tj = -7°C

2.49

2.18

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.30 kW

4.20 kW

COP Tj = +2°C

4.04

3.30

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.50 kW

4.20 kW

COP Tj = +7°C

5.08

4.07

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

4.40 kW

4.00 kW

COP Tj = 12°C

6.30

5.14

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.10 kW

7.40 kW

COP Tj = Tbiv

2.42

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.60 kW

7.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.97

WTOL

65 °C

65 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

4086 kWh

5084 kWh

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

190 %

142 %

Prated

4.00 kW

4.00 kW

SCOP

4.83

3.50

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.20 kW

4.00 kW

COP Tj = +2°C

3.48

2.50

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.30 kW

3.90 kW

COP Tj = +7°C

4.46

3.16

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

4.30 kW

3.80 kW

COP Tj = 12°C

5.89

4.57

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.20 kW

4.00 kW

COP Tj = Tbiv

3.48

2.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.20 kW

9.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.15

1.98

WTOL

65 °C

65 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1106 kWh

1489 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

140 %

119 %

Prated

11.00 kW

12.00 kW

SCOP

3.57

3.09

Tbiv

-10 °C

-10 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.80 kW

7.00 kW

COP Tj = -7°C

2.72

2.45

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.30 kW

4.20 kW

COP Tj = +2°C

4.45

3.70

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.50 kW

4.30 kW

COP Tj = +7°C

5.44

4.53

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

4.40 kW

4.10 kW

COP Tj = 12°C

6.30

5.44

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.70 kW

7.90 kW

COP Tj = Tbiv

2.50

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.10 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.25

2.10

WTOL

65 °C

65 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11.20 kW

11.61 kW

Annual energy consumption Qhe

7597 kWh

9351 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.10

9.70

COP Tj = -15°C (if TOL<-20°C)

2.25

2.10

Cdh Tj = -15 °C

0.90

0.90