Certificate holders

Subtype

IDEAL HEATING Alféa Excellia A.I. 16 Tri

Certificate Holder
Groupe Atlantic
44 boulevard des Etats-Unis
85000 La Roche Sur Yon
France
Registration number
012-SC0137-19 / Issue 3
Certification Body
RISE CERT
Subtype title
IDEAL HEATING Alféa Excellia A.I. 16 Tri
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

2,500 kg

Certification Date
04.04.2020
Testing basis
n/a
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

IDEAL HEATING Alféa Excellia A.I. Tri 16
Configure model
Model name
IDEAL HEATING Alféa Excellia A.I. Tri 16
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

15.17 kW

12.24 kW

El input

3.70 kW

4.93 kW

COP

4.10

2.48

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

69 dB(A)

69 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

149 %

117 %

Prated

13.60 kW

13.00 kW

SCOP

3.80

3.00

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.00 kW

11.50 kW

COP Tj = -7°C

2.40

1.80

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.30 kW

7.00 kW

COP Tj = +2°C

3.60

2.90

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.30 kW

5.80 kW

COP Tj = +7°C

5.50

4.10

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

7.40 kW

7.10 kW

COP Tj = 12°C

7.20

5.50

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.00 kW

11.50 kW

COP Tj = Tbiv

2.40

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.60 kW

10.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.60

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

14 W

14 W

PTO

88 W

32 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.00 kW

2.70 kW

Annual energy consumption Qhe

7408 kWh

9062 kWh