1,720 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
9.46 kW
4.77 kW
El input
2.27 kW
1.71 kW
COP
4.16
2.79
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
161 %
117 %
Prated
7.60 kW
6.90 kW
SCOP
4.10
3.01
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.72 kW
6.10 kW
COP Tj = -7°C
2.58
1.96
Pdh Tj = +2°C
4.09 kW
3.72 kW
COP Tj = +2°C
3.95
2.88
Pdh Tj = +7°C
2.63 kW
2.39 kW
COP Tj = +7°C
6.03
4.01
Pdh Tj = 12°C
2.91 kW
3.08 kW
COP Tj = 12°C
6.42
5.93
Pdh Tj = Tbiv
6.72 kW
6.10 kW
COP Tj = Tbiv
2.58
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.21 kW
5.53 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.36
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.87
0.90
WTOL
55 °C
55 °C
Poff
5 W
5 W
PTO
60 W
50 W
PSB
5 W
5 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.40 kW
1.50 kW
Annual energy consumption Qhe
3827 kWh
4736 kWh