1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.72 kW
3.64 kW
COP
4.30
3.30
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201 %
154 %
Prated
11.70 kW
11.70 kW
SCOP
5.11
3.92
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.40 kW
10.40 kW
COP Tj = -7°C
3.12
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.30 kW
6.30 kW
COP Tj = +2°C
5.02
3.90
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.10 kW
4.20 kW
COP Tj = +7°C
6.70
5.05
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.45
6.75
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.70 kW
10.40 kW
COP Tj = Tbiv
2.80
2.34
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
11.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.30 kW
Annual energy consumption Qhe
4735 kWh
6162 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.00 kW
El input
3.11 kW
3.38 kW
COP
4.50
3.25
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
155 %
Prated
11.00 kW
11.00 kW
SCOP
5.38
3.96
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.70 kW
9.70 kW
COP Tj = -7°C
3.30
2.45
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.90 kW
5.90 kW
COP Tj = +2°C
5.18
3.84
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.80 kW
3.80 kW
COP Tj = +7°C
7.38
5.40
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.15
6.15
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.70 kW
11.00 kW
COP Tj = Tbiv
3.30
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.70 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.20
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
n/a
Supplementary Heater: PSUP
0.30 kW
0.00 kW
Annual energy consumption Qhe
4223 kWh
5741 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
10.00 kW
El input
2.55 kW
3.23 kW
COP
4.70
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
49 dB(A)
49 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
156 %
Prated
10.00 kW
10.00 kW
SCOP
5.45
3.97
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.90 kW
8.90 kW
COP Tj = -7°C
3.54
2.54
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.40 kW
5.40 kW
COP Tj = +2°C
5.17
3.92
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.50 kW
3.50 kW
COP Tj = +7°C
7.37
5.22
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.24
5.58
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.00 kW
10.00 kW
COP Tj = Tbiv
3.21
2.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.21
2.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3789 kWh
5211 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.72 kW
3.64 kW
COP
4.30
3.30
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201 %
154 %
Prated
11.70 kW
11.70 kW
SCOP
5.11
3.92
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.40 kW
10.40 kW
COP Tj = -7°C
3.12
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.30 kW
6.30 kW
COP Tj = +2°C
5.02
3.90
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.10 kW
4.20 kW
COP Tj = +7°C
6.70
5.05
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.45
6.75
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.70 kW
10.40 kW
COP Tj = Tbiv
2.80
2.34
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
11.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.30 kW
Annual energy consumption Qhe
4735 kWh
6162 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.00 kW
El input
3.11 kW
3.38 kW
COP
4.50
3.25
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
155 %
Prated
11.00 kW
11.00 kW
SCOP
5.38
3.96
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.70 kW
9.70 kW
COP Tj = -7°C
3.30
2.45
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.90 kW
5.90 kW
COP Tj = +2°C
5.18
3.84
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.80 kW
3.80 kW
COP Tj = +7°C
7.38
5.40
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.15
6.15
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.70 kW
11.00 kW
COP Tj = Tbiv
3.30
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.70 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.20
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
n/a
Supplementary Heater: PSUP
0.30 kW
0.00 kW
Annual energy consumption Qhe
4223 kWh
5741 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
10.00 kW
El input
2.55 kW
3.23 kW
COP
4.70
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
49 dB(A)
49 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
156 %
Prated
10.00 kW
10.00 kW
SCOP
5.45
3.97
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.90 kW
8.90 kW
COP Tj = -7°C
3.54
2.54
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.40 kW
5.40 kW
COP Tj = +2°C
5.17
3.92
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.50 kW
3.50 kW
COP Tj = +7°C
7.37
5.22
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.24
5.58
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.00 kW
10.00 kW
COP Tj = Tbiv
3.21
2.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.21
2.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3789 kWh
5211 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
9.00 kW
El input
1.84 kW
2.81 kW
COP
4.90
3.20
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
49 dB(A)
49 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
206 %
147 %
Prated
9.00 kW
9.00 kW
SCOP
5.23
3.75
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.00 kW
8.00 kW
COP Tj = -7°C
3.48
2.50
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.90 kW
4.90 kW
COP Tj = +2°C
5.04
3.72
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.10 kW
3.10 kW
COP Tj = +7°C
6.75
4.85
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
8.80
5.00
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
3.20
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.20
2.28
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3554 kWh
4965 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.72 kW
3.64 kW
COP
4.30
3.30
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201 %
154 %
Prated
11.70 kW
11.70 kW
SCOP
5.11
3.92
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.40 kW
10.40 kW
COP Tj = -7°C
3.12
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.30 kW
6.30 kW
COP Tj = +2°C
5.02
3.90
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.10 kW
4.20 kW
COP Tj = +7°C
6.70
5.05
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.45
6.75
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.70 kW
10.40 kW
COP Tj = Tbiv
2.80
2.34
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
11.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.30 kW
Annual energy consumption Qhe
4735 kWh
6162 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.00 kW
El input
3.11 kW
3.38 kW
COP
4.50
3.25
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
155 %
Prated
11.00 kW
11.00 kW
SCOP
5.38
3.96
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.70 kW
9.70 kW
COP Tj = -7°C
3.30
2.45
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.90 kW
5.90 kW
COP Tj = +2°C
5.18
3.84
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.80 kW
3.80 kW
COP Tj = +7°C
7.38
5.40
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.15
6.15
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.70 kW
11.00 kW
COP Tj = Tbiv
3.30
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.70 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.20
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
n/a
Supplementary Heater: PSUP
0.30 kW
0.00 kW
Annual energy consumption Qhe
4223 kWh
5741 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
10.00 kW
El input
2.55 kW
3.23 kW
COP
4.70
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
49 dB(A)
49 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
156 %
Prated
10.00 kW
10.00 kW
SCOP
5.45
3.97
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.90 kW
8.90 kW
COP Tj = -7°C
3.54
2.54
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.40 kW
5.40 kW
COP Tj = +2°C
5.17
3.92
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.50 kW
3.50 kW
COP Tj = +7°C
7.37
5.22
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.24
5.58
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.00 kW
10.00 kW
COP Tj = Tbiv
3.21
2.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.21
2.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3789 kWh
5211 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.72 kW
3.64 kW
COP
4.30
3.30
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201 %
154 %
Prated
11.70 kW
11.70 kW
SCOP
5.11
3.92
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.40 kW
10.40 kW
COP Tj = -7°C
3.12
2.34
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.30 kW
6.30 kW
COP Tj = +2°C
5.02
3.90
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.10 kW
4.20 kW
COP Tj = +7°C
6.70
5.05
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.45
6.75
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.70 kW
10.40 kW
COP Tj = Tbiv
2.80
2.34
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
11.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.30 kW
Annual energy consumption Qhe
4735 kWh
6162 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.00 kW
El input
3.11 kW
3.38 kW
COP
4.50
3.25
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
155 %
Prated
11.00 kW
11.00 kW
SCOP
5.38
3.96
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.70 kW
9.70 kW
COP Tj = -7°C
3.30
2.45
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.90 kW
5.90 kW
COP Tj = +2°C
5.18
3.84
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.80 kW
3.80 kW
COP Tj = +7°C
7.38
5.40
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.15
6.15
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.70 kW
11.00 kW
COP Tj = Tbiv
3.30
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.70 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.20
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
n/a
Supplementary Heater: PSUP
0.30 kW
0.00 kW
Annual energy consumption Qhe
4223 kWh
5741 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
10.00 kW
El input
2.55 kW
3.23 kW
COP
4.70
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
49 dB(A)
49 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
156 %
Prated
10.00 kW
10.00 kW
SCOP
5.45
3.97
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.90 kW
8.90 kW
COP Tj = -7°C
3.54
2.54
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.40 kW
5.40 kW
COP Tj = +2°C
5.17
3.92
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.50 kW
3.50 kW
COP Tj = +7°C
7.37
5.22
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
9.24
5.58
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.00 kW
10.00 kW
COP Tj = Tbiv
3.21
2.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.21
2.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3789 kWh
5211 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
9.00 kW
El input
1.84 kW
2.81 kW
COP
4.90
3.20
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
49 dB(A)
49 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
206 %
147 %
Prated
9.00 kW
9.00 kW
SCOP
5.23
3.75
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.00 kW
8.00 kW
COP Tj = -7°C
3.48
2.50
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.90 kW
4.90 kW
COP Tj = +2°C
5.04
3.72
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.10 kW
3.10 kW
COP Tj = +7°C
6.75
4.85
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.60 kW
COP Tj = 12°C
8.80
5.00
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
3.20
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.20
2.28
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
30 W
30 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3554 kWh
4965 kWh