2,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.80 kW
10.40 kW
El input
3.12 kW
3.70 kW
COP
4.42
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
130 %
Prated
13.30 kW
13.30 kW
SCOP
4.21
3.32
Tbiv
-7 °C
-5 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
9.50 kW
COP Tj = -7°C
2.73
1.98
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
6.90 kW
7.20 kW
COP Tj = +2°C
3.96
3.26
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
6.30 kW
6.40 kW
COP Tj = +7°C
5.86
4.78
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
7.20 kW
7.50 kW
COP Tj = 12°C
7.40
6.02
Cdh Tj = +12 °C
0.980
0.990
Pdh Tj = Tbiv
11.50 kW
10.50 kW
COP Tj = Tbiv
2.73
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.30 kW
8.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
1.76
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
10 W
10 W
PTO
15 W
15 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.00 kW
4.90 kW
Annual energy consumption Qhe
6522 kWh
8266 kWh