2,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.00 kW
9.00 kW
El input
2.33 kW
3.05 kW
COP
4.30
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
137 %
Prated
7.50 kW
7.80 kW
SCOP
4.87
3.49
Tbiv
-8 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.63 kW
6.92 kW
COP Tj = -7°C
2.85
2.00
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.24 kW
4.38 kW
COP Tj = +2°C
4.85
3.45
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.47 kW
3.28 kW
COP Tj = +7°C
6.95
4.85
Cdh Tj = +7 °C
0.940
0.950
Pdh Tj = 12°C
4.05 kW
3.96 kW
COP Tj = 12°C
8.10
6.90
Cdh Tj = +12 °C
0.940
0.950
Pdh Tj = Tbiv
6.96 kW
6.92 kW
COP Tj = Tbiv
2.50
2.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.94 kW
5.44 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.00
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
28 W
28 W
PTO
31 W
31 W
PSB
31 W
31 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.56 kW
2.36 kW
Annual energy consumption Qhe
3183 kWh
4613 kWh