Aqua Thermal Super 110 140

Certificate Holder
GD Midea Heating & Ventilating Equipment Co., Ltd.
Penglai Industry Road
528311 Beijiao, Shunde, Foshan
China
Registration number
041-K007-31
Certification Body
BRE Global Limited
Subtype title
Aqua Thermal Super 110 140
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

15,500 kg

Certification Date
10.10.2023
Testing basis
Heat Pump KEYMARK certification Scheme rules v12
Generate PDF Export model CSV Download certificate
  • Number of models 4

Models

MH-SU110-RN8L
Configure model
Model name
MH-SU110-RN8L
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

112 kW

110 kW

El input

27 kW

29.9 kW

COP

4.15

3.68

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

80 dB(A)

80 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

127 %

Prated

95 kW

80 kW

SCOP

4.25

3.25

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

85.48 kW

69.31 kW

COP Tj = -7°C

3.03

2.01

Cdh Tj = -7 °C

0.9

0.9

Pdh Tj = +2°C

50.02 kW

41.99 kW

COP Tj = +2°C

3.73

3.1

Cdh Tj = +2 °C

0.9

0.9

Pdh Tj = +7°C

33.85 kW

28.27 kW

COP Tj = +7°C

6.23

4.52

Cdh Tj = +7 °C

0.9

0.9

Pdh Tj = 12°C

39.27 kW

37.99 kW

COP Tj = 12°C

8.02

6.03

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

85.48 kW

69.31 kW

COP Tj = Tbiv

3.03

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

94.45 kW

79.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.38

1.76

WTOL

65 °C

65 °C

Poff

140 W

140 W

PTO

700 W

700 W

PSB

140 W

140 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.55 kW

0.29 kW

Annual energy consumption Qhe

46188 kWh

50858 kWh

MH-SU110M-RN8L
Configure model
Model name
MH-SU110M-RN8L
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

112 kW

110 kW

El input

28.52 kW

31.21 kW

COP

3.97

3.55

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

83 dB(A)

83 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

166 %

126 %

Prated

95 kW

80 kW

SCOP

4.23

3.23

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

85.48 kW

69.25 kW

COP Tj = -7°C

2.99

2.01

Cdh Tj = -7 °C

0.9

0.9

Pdh Tj = +2°C

49.88 kW

41.9 kW

COP Tj = +2°C

3.72

3.1

Cdh Tj = +2 °C

0.9

0.9

Pdh Tj = +7°C

33.76 kW

28.17 kW

COP Tj = +7°C

6.24

4.4

Cdh Tj = +7 °C

0.9

0.9

Pdh Tj = 12°C

39.22 kW

37.89 kW

COP Tj = 12°C

7.94

6.07

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

85.48 kW

69.25 kW

COP Tj = Tbiv

2.99

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

94.65 kW

79.73 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.76

WTOL

65 °C

65 °C

Poff

140 W

140 W

PTO

700 W

700 W

PSB

140 W

140 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.35 kW

0.27 kW

Annual energy consumption Qhe

46383 kWh

51163 kWh

MH-SU140-RN8L
Configure model
Model name
MH-SU140-RN8L
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

142 kW

140 kW

El input

38.17 kW

44.73 kW

COP

3.72

3.13

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

92 dB(A)

92 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

127 %

Prated

95 kW

80 kW

SCOP

4.25

3.25

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

85.48 kW

69.31 kW

COP Tj = -7°C

3.03

2.01

Cdh Tj = -7 °C

0.9

0.9

Pdh Tj = +2°C

50.02 kW

41.99 kW

COP Tj = +2°C

3.73

3.1

Cdh Tj = +2 °C

0.9

0.9

Pdh Tj = +7°C

33.85 kW

28.27 kW

COP Tj = +7°C

6.23

4.52

Cdh Tj = +7 °C

0.9

0.9

Pdh Tj = 12°C

39.27 kW

37.99 kW

COP Tj = 12°C

8.02

6.03

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

85.48 kW

69.31 kW

COP Tj = Tbiv

3.03

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

94.45 kW

79.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.38

1.76

WTOL

65 °C

65 °C

Poff

140 W

140 W

PTO

700 W

700 W

PSB

140 W

140 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.55 kW

0.29 kW

Annual energy consumption Qhe

46188 kWh

50858 kWh

MH-SU140M-RN8L
Configure model
Model name
MH-SU140M-RN8L
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

142 kW

140 kW

El input

40.54 kW

47.1 kW

COP

3.53

2.99

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

93 dB(A)

93 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

166 %

126 %

Prated

95 kW

80 kW

SCOP

4.23

3.23

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

85.48 kW

69.25 kW

COP Tj = -7°C

2.99

2.01

Cdh Tj = -7 °C

0.9

0.9

Pdh Tj = +2°C

49.88 kW

41.9 kW

COP Tj = +2°C

3.72

3.1

Cdh Tj = +2 °C

0.9

0.9

Pdh Tj = +7°C

33.76 kW

28.17 kW

COP Tj = +7°C

6.24

4.4

Cdh Tj = +7 °C

0.9

0.9

Pdh Tj = 12°C

39.22 kW

37.89 kW

COP Tj = 12°C

7.94

6.07

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

85.48 kW

69.25 kW

COP Tj = Tbiv

2.99

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

94.65 kW

79.73 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.76

WTOL

65 °C

65 °C

Poff

140 W

140 W

PTO

700 W

700 W

PSB

140 W

140 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.35 kW

0.27 kW

Annual energy consumption Qhe

46383 kWh

51163 kWh