1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.72 kW
8.04 kW
El input
1.09 kW
3.16 kW
COP
5.26
2.54
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
46 dB(A)
Sound power level outdoor
53 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
130 %
Prated
6.39 kW
5.97 kW
SCOP
4.61
3.32
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.65 kW
5.28 kW
COP Tj = -7°C
3.19
1.94
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.52 kW
3.41 kW
COP Tj = +2°C
4.43
3.34
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.36 kW
3.15 kW
COP Tj = +7°C
6.36
4.60
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.96 kW
3.73 kW
COP Tj = 12°C
8.37
6.49
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.65 kW
5.28 kW
COP Tj = Tbiv
3.19
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.32 kW
4.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.82
1.71
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
57 °C
57 °C
Poff
10 W
10 W
PTO
19 W
19 W
PSB
10 W
10 W
PCK
27 W
27 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.07 kW
1.17 kW
Annual energy consumption Qhe
2864 kWh
3720 kWh