2,170 kg
Heating
EN 14511-2
Heat output
13.32 kW
El input
3.47 kW
COP
3.83
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Sound power level indoor
44 dB(A)
Sound power level outdoor
78 dB(A)
EN 14825
ηs
151 %
Prated
9.00 kW
SCOP
3.85
Tbiv
-10 °C
TOL
-10 °C
Pdh Tj = -7°C
7.30 kW
COP Tj = -7°C
2.47
Cdh Tj = -7 °C
0.900
Pdh Tj = +2°C
4.60 kW
COP Tj = +2°C
3.49
Cdh Tj = +2 °C
0.900
Pdh Tj = +7°C
3.90 kW
COP Tj = +7°C
5.76
Cdh Tj = +7 °C
0.900
Pdh Tj = 12°C
4.40 kW
COP Tj = 12°C
7.50
Cdh Tj = +12 °C
0.900
Pdh Tj = Tbiv
9.10 kW
COP Tj = Tbiv
2.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
WTOL
50 °C
Poff
42 W
PTO
19 W
PSB
42 W
PCK
1 W
Supplementary Heater: Type of energy input
n/a
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
4899 kWh