2,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.61 kW
15.15 kW
El input
3.39 kW
4.83 kW
COP
4.90
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
131 %
Prated
12.74 kW
14.44 kW
SCOP
4.57
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.27 kW
12.77 kW
COP Tj = -7°C
3.32
2.26
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.88 kW
7.82 kW
COP Tj = +2°C
4.33
3.17
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
8.12 kW
6.99 kW
COP Tj = +7°C
5.63
4.20
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
8.57 kW
5.89 kW
COP Tj = 12°C
6.94
5.63
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
11.27 kW
12.77 kW
COP Tj = Tbiv
3.32
2.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.79 kW
14.54 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.02
1.97
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
56 °C
56 °C
Poff
23 W
23 W
PTO
23 W
23 W
PSB
23 W
23 W
PCK
58 W
58 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5756 kWh
8931 kWh