Login

Subtype

Intelligent Inverter Heat Pump 8 R32

Certificate Holder
FoxAIR Sp z.o.o.
ul. Konarskiego 18C
44-100 Gliwice
Poland
Registration number
041-K041-01
Certification Body
BRE Global Limited
Subtype title
Intelligent Inverter Heat Pump 8 R32
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,100 kg

Certification Date
12.01.2023
Testing basis
Heat Pump Keymark Scheme Rules Rev 11
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

BL-8-1
Configure model
Model name
BL-8-1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.99 kW

5.13 kW

El input

1.21 kW

1.87 kW

COP

4.97

2.74

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

55 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

130 %

Prated

5.29 kW

5.00 kW

SCOP

4.75

3.33

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.68 kW

5.00 kW

COP Tj = -7°C

3.28

2.20

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.86 kW

3.09 kW

COP Tj = +2°C

4.52

3.26

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

2.45 kW

2.73 kW

COP Tj = +7°C

5.87

4.03

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

2.85 kW

2.70 kW

COP Tj = 12°C

8.72

6.34

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

4.68 kW

5.00 kW

COP Tj = Tbiv

3.28

2.20

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.92 kW

4.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.79

1.71

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

53 °C

53 °C

Poff

13 W

13 W

PTO

13 W

13 W

PSB

13 W

13 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.38 kW

1.32 kW

Annual energy consumption Qhe

2302 kWh

3503 kWh