Login

Subtype

DC Inverter Heat Pump R290-60

Certificate Holder
Power World Machinery Equipment Co. Ltd
No.24, The Fourth Industrial Zone, HouTing Street
Shenzhen
China
Registration number
041-K032-10
Certification Body
BRE Global Limited
Subtype title
DC Inverter Heat Pump R290-60
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,400 kg

Certification Date
30.06.2023
Testing basis
Heat Pump Keymark Scheme Rules Rev 12
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

PW060-DKZLRS-E
Configure model
Model name
PW060-DKZLRS-E
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.78 kW

12.25 kW

El input

2.76 kW

3.88 kW

COP

4.63

3.16

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

60 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

139 %

Prated

14.05 kW

13.47 kW

SCOP

4.69

3.55

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.43 kW

11.91 kW

COP Tj = -7°C

3.34

2.38

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.57 kW

7.29 kW

COP Tj = +2°C

4.52

3.49

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.14 kW

7.66 kW

COP Tj = +7°C

6.38

4.73

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

8.98 kW

8.89 kW

COP Tj = 12°C

8.11

6.50

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.43 kW

11.91 kW

COP Tj = Tbiv

3.34

2.38

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.01 kW

13.29 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.76

2.08

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

13 W

13 W

PTO

39 W

39 W

PSB

13 W

13 W

PCK

54 W

54 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.04 kW

0.18 kW

Annual energy consumption Qhe

6189 kWh

7844 kWh