1,150 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.93 kW
9.04 kW
El input
1.77 kW
3.02 kW
COP
5.04
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
132 %
Prated
9.95 kW
9.23 kW
SCOP
4.65
3.37
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.80 kW
8.16 kW
COP Tj = -7°C
3.37
2.21
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.44 kW
4.99 kW
COP Tj = +2°C
4.59
3.24
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.15 kW
5.58 kW
COP Tj = +7°C
5.80
4.81
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.94 kW
6.44 kW
COP Tj = 12°C
7.97
6.49
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.80 kW
8.16 kW
COP Tj = Tbiv
3.37
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.93 kW
9.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
7 W
7 W
PTO
24 W
24 W
PSB
7 W
7 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.02 kW
0.00 kW
Annual energy consumption Qhe
4421 kWh
5655 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.72 kW
8.97 kW
El input
2.04 kW
3.14 kW
COP
4.27
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
135 %
Prated
10.27 kW
12.17 kW
SCOP
4.60
3.44
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.08 kW
10.77 kW
COP Tj = -7°C
3.23
2.39
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.54 kW
6.69 kW
COP Tj = +2°C
4.52
3.33
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
6.73 kW
5.52 kW
COP Tj = +7°C
6.16
4.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.85 kW
6.58 kW
COP Tj = 12°C
8.09
6.25
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.08 kW
10.77 kW
COP Tj = Tbiv
3.23
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.14 kW
8.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.73
1.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
7 W
7 W
PTO
24 W
24 W
PSB
7 W
7 W
PCK
43 W
43 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.13 kW
3.44 kW
Annual energy consumption Qhe
4614 kWh
7302 kWh