9,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
35.00 kW
35.00 kW
El input
10.20 kW
14.08 kW
COP
3.43
2.48
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
76 dB(A)
76 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
140 %
127 %
Prated
26.90 kW
27.00 kW
SCOP
3.57
3.24
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
23.80 kW
23.80 kW
COP Tj = -7°C
2.60
2.08
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
15.30 kW
14.70 kW
COP Tj = +2°C
3.33
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
9.30 kW
13.90 kW
COP Tj = +7°C
5.20
4.60
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
8.70 kW
13.70 kW
COP Tj = 12°C
5.05
5.81
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
23.80 kW
23.80 kW
COP Tj = Tbiv
2.60
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
26.90 kW
27.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
70 °C
70 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
65 W
65 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15556 kWh
17161 kWh