1,100 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1.01 kW
1.7 kW
COP
4.95
2.94
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
126 %
Prated
6.1 kW
6 kW
SCOP
4.44
3.22
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.4 kW
5.31 kW
COP Tj = -7°C
2.78
1.85
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.1 kW
3.7 kW
COP Tj = +2°C
4.43
3.13
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.27
4.66
Cdh Tj = +7 °C
0.972
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.11
6.53
Cdh Tj = +12 °C
0.971
0.975
Pdh Tj = Tbiv
6.1 kW
5.31 kW
COP Tj = Tbiv
2.26
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.1 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.2 kW
Annual energy consumption Qhe
2838 kWh
3850 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1.01 kW
1.7 kW
COP
4.95
2.94
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
128 %
Prated
6.1 kW
6 kW
SCOP
4.53
3.27
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.4 kW
5.31 kW
COP Tj = -7°C
2.78
1.85
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.1 kW
3.7 kW
COP Tj = +2°C
4.43
3.13
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.27
4.66
Cdh Tj = +7 °C
0.972
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.11
6.53
Cdh Tj = +12 °C
0.971
0.975
Pdh Tj = Tbiv
6.1 kW
5.31 kW
COP Tj = Tbiv
2.26
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.1 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.2 kW
Annual energy consumption Qhe
2783 kWh
3794 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1.01 kW
1.7 kW
COP
4.95
2.94
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
128 %
Prated
6.1 kW
6 kW
SCOP
4.53
3.27
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.4 kW
5.31 kW
COP Tj = -7°C
2.78
1.85
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.1 kW
3.7 kW
COP Tj = +2°C
4.43
3.13
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.27
4.66
Cdh Tj = +7 °C
0.972
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.11
6.53
Cdh Tj = +12 °C
0.971
0.975
Pdh Tj = Tbiv
6.1 kW
5.31 kW
COP Tj = Tbiv
2.26
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.1 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.2 kW
Annual energy consumption Qhe
2783 kWh
3794 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
133 %
Prated
6.6 kW
7 kW
SCOP
4.66
3.39
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
3.16
1.91
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.61
3.39
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.4
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
2929 kWh
4262 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
135 %
Prated
6.6 kW
7 kW
SCOP
4.74
3.44
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
3.16
1.91
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.61
3.39
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.4
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
2874 kWh
4207 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
135 %
Prated
6.6 kW
7 kW
SCOP
4.74
3.44
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
3.16
1.91
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.61
3.39
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.4
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
2874 kWh
4207 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
128 %
Prated
6.6 kW
7 kW
SCOP
4.44
3.29
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
2.86
1.81
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.35
3.25
Cdh Tj = +2 °C
0.985
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.23
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.23
1.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
3070 kWh
4401 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
130 %
Prated
6.6 kW
7 kW
SCOP
4.52
3.33
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
2.86
1.81
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.35
3.25
Cdh Tj = +2 °C
0.985
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.23
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.23
1.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
3015 kWh
4346 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
130 %
Prated
6.6 kW
7 kW
SCOP
4.52
3.33
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
2.86
1.81
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.35
3.25
Cdh Tj = +2 °C
0.985
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.23
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.23
1.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
3015 kWh
4346 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.5 kW
7.5 kW
El input
1.55 kW
2.68 kW
COP
4.85
2.8
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
133 %
Prated
7.8 kW
7.5 kW
SCOP
4.54
3.39
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.9 kW
6.63 kW
COP Tj = -7°C
2.99
1.8
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.5 kW
4.1 kW
COP Tj = +2°C
4.57
3.41
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.4 kW
3.5 kW
COP Tj = +7°C
5.84
4.79
Cdh Tj = +7 °C
0.974
0.979
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
6.98
6.9
Cdh Tj = +12 °C
0.972
0.973
Pdh Tj = Tbiv
7.8 kW
6.63 kW
COP Tj = Tbiv
2.34
1.8
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.8 kW
6.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.34
1.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.4 kW
Annual energy consumption Qhe
3548 kWh
4567 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.5 kW
7.5 kW
El input
1.55 kW
2.68 kW
COP
4.85
2.8
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
134 %
Prated
7.8 kW
7.5 kW
SCOP
4.61
3.43
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.9 kW
6.63 kW
COP Tj = -7°C
2.99
1.8
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.5 kW
4.1 kW
COP Tj = +2°C
4.57
3.41
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.4 kW
3.5 kW
COP Tj = +7°C
5.84
4.79
Cdh Tj = +7 °C
0.974
0.979
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
6.98
6.9
Cdh Tj = +12 °C
0.972
0.973
Pdh Tj = Tbiv
7.8 kW
6.63 kW
COP Tj = Tbiv
2.34
1.8
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.8 kW
6.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.34
1.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.4 kW
Annual energy consumption Qhe
3492 kWh
4512 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.5 kW
7.5 kW
El input
1.55 kW
2.68 kW
COP
4.85
2.8
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
174 %
127 %
Prated
7.8 kW
7.5 kW
SCOP
4.43
3.26
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.9 kW
6.63 kW
COP Tj = -7°C
2.79
1.68
Cdh Tj = -7 °C
0.994
0.996
Pdh Tj = +2°C
4.5 kW
4.1 kW
COP Tj = +2°C
4.43
3.23
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.4 kW
3.5 kW
COP Tj = +7°C
5.89
4.8
Cdh Tj = +7 °C
0.974
0.979
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.04
6.78
Cdh Tj = +12 °C
0.971
0.974
Pdh Tj = Tbiv
7.8 kW
6.63 kW
COP Tj = Tbiv
2.22
1.68
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.8 kW
6.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.4 kW
Annual energy consumption Qhe
3640 kWh
4758 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.5 kW
7.5 kW
El input
1.55 kW
2.68 kW
COP
4.85
2.8
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
129 %
Prated
7.8 kW
7.5 kW
SCOP
4.5
3.29
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.9 kW
6.63 kW
COP Tj = -7°C
2.79
1.68
Cdh Tj = -7 °C
0.994
0.996
Pdh Tj = +2°C
4.5 kW
4.1 kW
COP Tj = +2°C
4.43
3.23
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.4 kW
3.5 kW
COP Tj = +7°C
5.89
4.8
Cdh Tj = +7 °C
0.974
0.979
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.04
6.78
Cdh Tj = +12 °C
0.971
0.974
Pdh Tj = Tbiv
7.8 kW
6.63 kW
COP Tj = Tbiv
2.22
1.68
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.8 kW
6.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.4 kW
Annual energy consumption Qhe
3585 kWh
4703 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
145 %
COP
3.3
Heating up time
1:58 h:min
Standby power input
29 W
Reference hot water temperature
53 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1.01 kW
1.7 kW
COP
4.95
2.94
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.83 kW
1.15 kW
Cooling capacity
6
6
EER
3.28
5.21
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6 kW
6 kW
SEER
5.19
7.02
Pdc Tj = 35°C
6 kW
6 kW
EER Tj = 35°C
3.28
5.21
Cdc Tj = 35 °C
0.992
0.987
Pdc Tj = 30°C
4.42 kW
4.42 kW
EER Tj = 30°C
4.45
6.5
Cdc Tj = 30 °C
0.985
0.978
Pdc Tj = 25°C
2.84 kW
3.4 kW
EER Tj = 25°C
5.93
8.66
Cdc Tj = 25 °C
0.969
0.962
Pdc Tj = 20°C
2.8 kW
3.8 kW
EER Tj = 20°C
7.41
8.28
Cdc Tj = 20 °C
0.96
0.967
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
694 kWh
513 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
128 %
Prated
6.1 kW
6 kW
SCOP
4.53
3.27
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.4 kW
5.31 kW
COP Tj = -7°C
2.78
1.85
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.1 kW
3.7 kW
COP Tj = +2°C
4.43
3.13
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.27
4.66
Cdh Tj = +7 °C
0.972
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.11
6.53
Cdh Tj = +12 °C
0.971
0.975
Pdh Tj = Tbiv
6.1 kW
5.31 kW
COP Tj = Tbiv
2.26
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.1 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.2 kW
Annual energy consumption Qhe
2783 kWh
3794 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1.01 kW
1.7 kW
COP
4.95
2.94
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.83 kW
1.15 kW
Cooling capacity
6
6
EER
3.28
5.21
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6 kW
6 kW
SEER
5.19
7.02
Pdc Tj = 35°C
6 kW
6 kW
EER Tj = 35°C
3.28
5.21
Cdc Tj = 35 °C
0.992
0.987
Pdc Tj = 30°C
4.42 kW
4.42 kW
EER Tj = 30°C
4.45
6.5
Cdc Tj = 30 °C
0.985
0.978
Pdc Tj = 25°C
2.84 kW
3.4 kW
EER Tj = 25°C
5.93
8.66
Cdc Tj = 25 °C
0.969
0.962
Pdc Tj = 20°C
2.8 kW
3.8 kW
EER Tj = 20°C
7.41
8.28
Cdc Tj = 20 °C
0.96
0.967
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
694 kWh
513 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
128 %
Prated
6.1 kW
6 kW
SCOP
4.53
3.27
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.4 kW
5.31 kW
COP Tj = -7°C
2.78
1.85
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.1 kW
3.7 kW
COP Tj = +2°C
4.43
3.13
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.27
4.66
Cdh Tj = +7 °C
0.972
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.11
6.53
Cdh Tj = +12 °C
0.971
0.975
Pdh Tj = Tbiv
6.1 kW
5.31 kW
COP Tj = Tbiv
2.26
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.1 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.2 kW
Annual energy consumption Qhe
2783 kWh
3794 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.09 kW
1.32 kW
Cooling capacity
6.7
6.7
EER
3.2
5.06
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.7 kW
6.7 kW
SEER
5.16
6.97
Pdc Tj = 35°C
6.7 kW
6.7 kW
EER Tj = 35°C
3.2
5.06
Cdc Tj = 35 °C
0.993
0.989
Pdc Tj = 30°C
4.94 kW
4.94 kW
EER Tj = 30°C
4.35
6.38
Cdc Tj = 30 °C
0.987
0.981
Pdc Tj = 25°C
3.17 kW
3.6 kW
EER Tj = 25°C
5.96
8.53
Cdc Tj = 25 °C
0.972
0.964
Pdc Tj = 20°C
2.8 kW
3.8 kW
EER Tj = 20°C
7.2
8.12
Cdc Tj = 20 °C
0.961
0.968
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
779 kWh
577 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
133 %
Prated
6.6 kW
7 kW
SCOP
4.66
3.39
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
3.16
1.91
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.61
3.39
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.4
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
2929 kWh
4262 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.09 kW
1.32 kW
Cooling capacity
6.7
6.7
EER
3.2
5.06
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.7 kW
6.7 kW
SEER
5.16
6.97
Pdc Tj = 35°C
6.7 kW
6.7 kW
EER Tj = 35°C
3.2
5.06
Cdc Tj = 35 °C
0.993
0.989
Pdc Tj = 30°C
4.94 kW
4.94 kW
EER Tj = 30°C
4.35
6.38
Cdc Tj = 30 °C
0.987
0.981
Pdc Tj = 25°C
3.17 kW
3.6 kW
EER Tj = 25°C
5.96
8.53
Cdc Tj = 25 °C
0.972
0.964
Pdc Tj = 20°C
2.8 kW
3.8 kW
EER Tj = 20°C
7.2
8.12
Cdc Tj = 20 °C
0.961
0.968
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
779 kWh
577 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
135 %
Prated
6.6 kW
7 kW
SCOP
4.74
3.44
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
3.16
1.91
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.61
3.39
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.4
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
2874 kWh
4207 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6 kW
6 kW
El input
1.18 kW
2 kW
COP
5.1
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.09 kW
1.32 kW
Cooling capacity
6.7
6.7
EER
3.2
5.06
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.7 kW
6.7 kW
SEER
5.16
6.97
Pdc Tj = 35°C
6.7 kW
6.7 kW
EER Tj = 35°C
3.2
5.06
Cdc Tj = 35 °C
0.993
0.989
Pdc Tj = 30°C
4.94 kW
4.94 kW
EER Tj = 30°C
4.35
6.38
Cdc Tj = 30 °C
0.987
0.981
Pdc Tj = 25°C
3.17 kW
3.6 kW
EER Tj = 25°C
5.96
8.53
Cdc Tj = 25 °C
0.972
0.964
Pdc Tj = 20°C
2.8 kW
3.8 kW
EER Tj = 20°C
7.2
8.12
Cdc Tj = 20 °C
0.961
0.968
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
779 kWh
577 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
135 %
Prated
6.6 kW
7 kW
SCOP
4.74
3.44
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.9 kW
6.2 kW
COP Tj = -7°C
3.16
1.91
Cdh Tj = -7 °C
0.992
0.995
Pdh Tj = +2°C
4.4 kW
3.8 kW
COP Tj = +2°C
4.61
3.39
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.4 kW
3.1 kW
COP Tj = +7°C
6.22
4.69
Cdh Tj = +7 °C
0.973
0.977
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
7.38
6.67
Cdh Tj = +12 °C
0.97
0.974
Pdh Tj = Tbiv
6.6 kW
6.2 kW
COP Tj = Tbiv
2.4
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
5.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.2 kW
Annual energy consumption Qhe
2874 kWh
4207 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.5 kW
7.5 kW
El input
1.55 kW
2.68 kW
COP
4.85
2.8
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.43 kW
1.82 kW
Cooling capacity
7.3
8.1
EER
3
4.44
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.3 kW
8.1 kW
SEER
5.08
6.74
Pdc Tj = 35°C
7.3 kW
8.1 kW
EER Tj = 35°C
3
4.44
Cdc Tj = 35 °C
0.994
0.992
Pdc Tj = 30°C
5.38 kW
5.97 kW
EER Tj = 30°C
4.24
6.05
Cdc Tj = 30 °C
0.988
0.985
Pdc Tj = 25°C
3.46 kW
4.2 kW
EER Tj = 25°C
5.94
8.29
Cdc Tj = 25 °C
0.974
0.97
Pdc Tj = 20°C
2.8 kW
3.9 kW
EER Tj = 20°C
7
7.72
Cdc Tj = 20 °C
0.963
0.97
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
863 kWh
722 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
133 %
Prated
7.8 kW
7.5 kW
SCOP
4.54
3.39
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.9 kW
6.63 kW
COP Tj = -7°C
2.99
1.8
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.5 kW
4.1 kW
COP Tj = +2°C
4.57
3.41
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.4 kW
3.5 kW
COP Tj = +7°C
5.84
4.79
Cdh Tj = +7 °C
0.974
0.979
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
6.98
6.9
Cdh Tj = +12 °C
0.972
0.973
Pdh Tj = Tbiv
7.8 kW
6.63 kW
COP Tj = Tbiv
2.34
1.8
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.8 kW
6.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.34
1.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.4 kW
Annual energy consumption Qhe
3548 kWh
4567 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.5 kW
7.5 kW
El input
1.55 kW
2.68 kW
COP
4.85
2.8
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.43 kW
1.82 kW
Cooling capacity
7.3
8.1
EER
3
4.44
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.3 kW
8.1 kW
SEER
5.08
6.74
Pdc Tj = 35°C
7.3 kW
8.1 kW
EER Tj = 35°C
3
4.44
Cdc Tj = 35 °C
0.994
0.992
Pdc Tj = 30°C
5.38 kW
5.97 kW
EER Tj = 30°C
4.24
6.05
Cdc Tj = 30 °C
0.988
0.985
Pdc Tj = 25°C
3.46 kW
4.2 kW
EER Tj = 25°C
5.94
8.29
Cdc Tj = 25 °C
0.974
0.97
Pdc Tj = 20°C
2.8 kW
3.9 kW
EER Tj = 20°C
7
7.72
Cdc Tj = 20 °C
0.963
0.97
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
863 kWh
722 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
134 %
Prated
7.8 kW
7.5 kW
SCOP
4.61
3.43
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.9 kW
6.63 kW
COP Tj = -7°C
2.99
1.8
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.5 kW
4.1 kW
COP Tj = +2°C
4.57
3.41
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.4 kW
3.5 kW
COP Tj = +7°C
5.84
4.79
Cdh Tj = +7 °C
0.974
0.979
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
6.98
6.9
Cdh Tj = +12 °C
0.972
0.973
Pdh Tj = Tbiv
7.8 kW
6.63 kW
COP Tj = Tbiv
2.34
1.8
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.8 kW
6.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.34
1.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.4 kW
Annual energy consumption Qhe
3492 kWh
4512 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.5 kW
7.5 kW
El input
1.55 kW
2.68 kW
COP
4.85
2.8
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.43 kW
1.82 kW
Cooling capacity
7.3
8.1
EER
3
4.44
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.3 kW
8.1 kW
SEER
5.08
6.74
Pdc Tj = 35°C
7.3 kW
8.1 kW
EER Tj = 35°C
3
4.44
Cdc Tj = 35 °C
0.994
0.992
Pdc Tj = 30°C
5.38 kW
5.97 kW
EER Tj = 30°C
4.24
6.05
Cdc Tj = 30 °C
0.988
0.985
Pdc Tj = 25°C
3.46 kW
4.2 kW
EER Tj = 25°C
5.94
8.29
Cdc Tj = 25 °C
0.974
0.97
Pdc Tj = 20°C
2.8 kW
3.9 kW
EER Tj = 20°C
7
7.72
Cdc Tj = 20 °C
0.963
0.97
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
863 kWh
722 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
134 %
Prated
7.8 kW
7.5 kW
SCOP
4.61
3.43
Tbiv
-10 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.9 kW
6.63 kW
COP Tj = -7°C
2.99
1.8
Cdh Tj = -7 °C
0.993
0.996
Pdh Tj = +2°C
4.5 kW
4.1 kW
COP Tj = +2°C
4.57
3.41
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.4 kW
3.5 kW
COP Tj = +7°C
5.84
4.79
Cdh Tj = +7 °C
0.974
0.979
Pdh Tj = 12°C
3.7 kW
3.9 kW
COP Tj = 12°C
6.98
6.9
Cdh Tj = +12 °C
0.972
0.973
Pdh Tj = Tbiv
7.8 kW
6.63 kW
COP Tj = Tbiv
2.34
1.8
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.8 kW
6.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.34
1.69
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.4 kW
Annual energy consumption Qhe
3492 kWh
4512 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
142 %
COP
3.47
Heating up time
1:48 h:min
Standby power input
23 W
Reference hot water temperature
53 °C
Mixed water at 40°C
236 l