3,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.98 kW
8.88 kW
El input
2.09 kW
2.99 kW
COP
4.77
2.97
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
228 %
170 %
Prated
12 kW
12 kW
SCOP
5.77
4.32
Tbiv
4 °C
4 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.6 kW
9.87 kW
COP Tj = +2°C
3.42
2.61
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
7.51 kW
7.68 kW
COP Tj = +7°C
5.37
3.74
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
6.17 kW
5.94 kW
COP Tj = 12°C
7.09
5.48
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
10.24 kW
10.28 kW
COP Tj = Tbiv
3.78
2.87
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.6 kW
9.87 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.42
2.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.4 kW
2.13 kW
Annual energy consumption Qhe
2778 kWh
3712 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
126 %
Prated
10 kW
10 kW
SCOP
3.95
3.23
Tbiv
-15 °C
-13 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
6.11 kW
6.12 kW
COP Tj = -7°C
3.63
2.9
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.48 kW
4.23 kW
COP Tj = +2°C
4.56
3.76
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
5.26 kW
5.01 kW
COP Tj = +7°C
5.43
4.5
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.14 kW
5.97 kW
COP Tj = 12°C
7.1
5.86
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
7.7 kW
7.71 kW
COP Tj = Tbiv
2.67
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.2 kW
6.91 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
10 kW
10 kW
Annual energy consumption Qhe
6248 kWh
7631 kWh
Pdh Tj = -15°C (if TOL<-20°C)
7.7
7.39
COP Tj = -15°C (if TOL<-20°C)
2.67
2.07
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
135 %
Prated
10 kW
10 kW
SCOP
4.66
3.45
Tbiv
-9 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.84 kW
8.62 kW
COP Tj = -7°C
3.14
2.14
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
5.36 kW
5.61 kW
COP Tj = +2°C
4.68
3.49
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
5.21 kW
4.83 kW
COP Tj = +7°C
5.46
4.22
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.20 kW
5.89 kW
COP Tj = 12°C
7.44
5.83
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
9.03 kW
8.62 kW
COP Tj = Tbiv
2.88
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.76 kW
7.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.24 kW
2.29 kW
Annual energy consumption Qhe
4435 kWh
5985 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
138 %
COP
3.33
Heating up time
01:26 h:min
Standby power input
40 W
Reference hot water temperature
50.6 °C
Mixed water at 40°C
255 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
104 %
COP
2.5
Heating up time
02:08 h:min
Standby power input
50 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
120 %
COP
2.87
Heating up time
01:53 h:min
Standby power input
50 W
Reference hot water temperature
52.7 °C
Mixed water at 40°C
264 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.98 kW
8.88 kW
El input
2.09 kW
2.99 kW
COP
4.77
2.97
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
228 %
170 %
Prated
12 kW
12 kW
SCOP
5.77
4.32
Tbiv
4 °C
4 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.6 kW
9.87 kW
COP Tj = +2°C
3.42
2.61
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
7.51 kW
7.68 kW
COP Tj = +7°C
5.37
3.74
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
6.17 kW
5.94 kW
COP Tj = 12°C
7.09
5.48
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
10.24 kW
10.28 kW
COP Tj = Tbiv
3.78
2.87
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.6 kW
9.87 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.42
2.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
2.4 kW
2.13 kW
Annual energy consumption Qhe
2778 kWh
3712 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
126 %
Prated
10 kW
10 kW
SCOP
3.95
3.23
Tbiv
-15 °C
-13 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
6.11 kW
6.12 kW
COP Tj = -7°C
3.63
2.9
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.48 kW
4.23 kW
COP Tj = +2°C
4.56
3.76
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
5.26 kW
5.01 kW
COP Tj = +7°C
5.43
4.5
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.14 kW
5.97 kW
COP Tj = 12°C
7.1
5.86
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
7.7 kW
7.71 kW
COP Tj = Tbiv
2.67
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.2 kW
6.91 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
10 kW
10 kW
Annual energy consumption Qhe
6248 kWh
7631 kWh
Pdh Tj = -15°C (if TOL<-20°C)
7.7
7.39
COP Tj = -15°C (if TOL<-20°C)
2.67
2.07
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
135 %
Prated
10 kW
10 kW
SCOP
4.66
3.45
Tbiv
-9 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.84 kW
8.62 kW
COP Tj = -7°C
3.14
2.14
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
5.36 kW
5.61 kW
COP Tj = +2°C
4.68
3.49
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
5.21 kW
4.83 kW
COP Tj = +7°C
5.46
4.22
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.20 kW
5.89 kW
COP Tj = 12°C
7.44
5.83
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
9.03 kW
8.62 kW
COP Tj = Tbiv
2.88
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.76 kW
7.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
1.24 kW
2.29 kW
Annual energy consumption Qhe
4435 kWh
5985 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.6 kW
10.80 kW
El input
2.58 kW
3.75 kW
COP
4.5
2.88
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
229 %
168 %
Prated
13 kW
13 kW
SCOP
5.79
4.27
Tbiv
3 °C
3 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.9 kW
11.3 kW
COP Tj = +2°C
3.28
2.48
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
8.66 kW
8.67 kW
COP Tj = +7°C
5.22
3.61
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
6.15 kW
5.97 kW
COP Tj = 12°C
7.13
5.51
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
11.3 kW
11.57 kW
COP Tj = Tbiv
3.46
2.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.9 kW
11.3 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.1 kW
1.7 kW
Annual energy consumption Qhe
2999 kWh
4068 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
126 %
Prated
11 kW
11 kW
SCOP
3.97
3.23
Tbiv
-15 °C
-13 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
6.96 kW
6.95 kW
COP Tj = -7°C
3.61
2.76
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.5 kW
4.44 kW
COP Tj = +2°C
4.6
4.02
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
5.28 kW
5.01 kW
COP Tj = +7°C
5.56
4.54
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.15 kW
5.97 kW
COP Tj = 12°C
7.09
5.89
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
9.57 kW
8.16 kW
COP Tj = Tbiv
2.45
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.9 kW
7.15 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.05
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
11 kW
11 kW
Annual energy consumption Qhe
6834 kWh
8388 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.57
7.78
COP Tj = -15°C (if TOL<-20°C)
2.45
1.96
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
136 %
Prated
11 kW
11 kW
SCOP
4.56
3.48
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.22 kW
9.51 kW
COP Tj = -7°C
3.02
2.10
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
6.14 kW
6.06 kW
COP Tj = +2°C
4.56
3.52
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
5.22 kW
5.01 kW
COP Tj = +7°C
5.46
4.35
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.17 kW
5.97 kW
COP Tj = 12°C
7.21
5.69
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
10.76 kW
9.51 kW
COP Tj = Tbiv
2.62
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.76 kW
8.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.62
1.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
2.11 kW
Annual energy consumption Qhe
4983 kWh
6527 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
138 %
COP
3.33
Heating up time
01:26 h:min
Standby power input
40 W
Reference hot water temperature
50.6 °C
Mixed water at 40°C
255 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
104 %
COP
2.5
Heating up time
02:08 h:min
Standby power input
50 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
120 %
COP
2.87
Heating up time
01:53 h:min
Standby power input
50 W
Reference hot water temperature
52.7 °C
Mixed water at 40°C
264 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.6 kW
10.80 kW
El input
2.58 kW
3.75 kW
COP
4.5
2.88
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
229 %
168 %
Prated
13 kW
13 kW
SCOP
5.79
4.27
Tbiv
3 °C
3 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.9 kW
11.3 kW
COP Tj = +2°C
3.28
2.48
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
8.66 kW
8.67 kW
COP Tj = +7°C
5.22
3.61
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
6.15 kW
5.97 kW
COP Tj = 12°C
7.13
5.51
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
11.3 kW
11.57 kW
COP Tj = Tbiv
3.46
2.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.9 kW
11.3 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
2.1 kW
1.7 kW
Annual energy consumption Qhe
2999 kWh
4068 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
126 %
Prated
11 kW
11 kW
SCOP
3.97
3.23
Tbiv
-15 °C
-13 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
6.96 kW
6.95 kW
COP Tj = -7°C
3.61
2.76
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.5 kW
4.44 kW
COP Tj = +2°C
4.6
4.02
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
5.28 kW
5.01 kW
COP Tj = +7°C
5.56
4.54
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.15 kW
5.97 kW
COP Tj = 12°C
7.09
5.89
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
9.57 kW
8.16 kW
COP Tj = Tbiv
2.45
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.9 kW
7.15 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.05
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
11 kW
11 kW
Annual energy consumption Qhe
6834 kWh
8388 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.57
7.78
COP Tj = -15°C (if TOL<-20°C)
2.45
1.96
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
136 %
Prated
11 kW
11 kW
SCOP
4.56
3.48
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.22 kW
9.51 kW
COP Tj = -7°C
3.02
2.10
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
6.14 kW
6.06 kW
COP Tj = +2°C
4.56
3.52
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
5.22 kW
5.01 kW
COP Tj = +7°C
5.46
4.35
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.17 kW
5.97 kW
COP Tj = 12°C
7.21
5.69
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
10.76 kW
9.51 kW
COP Tj = Tbiv
2.62
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.76 kW
8.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.62
1.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
2.11 kW
Annual energy consumption Qhe
4983 kWh
6527 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.58 kW
12.70 kW
El input
3.41 kW
4.54 kW
COP
4.28
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
229 %
168 %
Prated
14 kW
14 kW
SCOP
5.79
4.27
Tbiv
3 °C
3 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.2 kW
11.85 kW
COP Tj = +2°C
3.16
2.38
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
8.88 kW
9.05 kW
COP Tj = +7°C
5.21
3.58
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
6.16 kW
5.97 kW
COP Tj = 12°C
7.19
5.56
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
12.6 kW
12.3 kW
COP Tj = Tbiv
3.33
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.2 kW
11.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.16
2.38
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.8 kW
2.15 kW
Annual energy consumption Qhe
3228 kWh
4384 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
122 %
Prated
12 kW
12 kW
SCOP
3.96
3.12
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
7.62 kW
7.48 kW
COP Tj = -7°C
3.56
2.68
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.53 kW
4.64 kW
COP Tj = +2°C
4.64
3.86
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
5.26 kW
5.01 kW
COP Tj = +7°C
5.43
4.57
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.15 kW
5.98 kW
COP Tj = 12°C
7.13
5.91
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
10.18 kW
8.85 kW
COP Tj = Tbiv
2.42
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.69 kW
7.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.06
1.7
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
12 kW
12 kW
Annual energy consumption Qhe
7474 kWh
9483 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.18
8.31
COP Tj = -15°C (if TOL<-20°C)
2.42
1.88
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
138 %
Prated
12 kW
12 kW
SCOP
4.53
3.53
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.98 kW
10.26 kW
COP Tj = -7°C
2.73
2.10
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
6.71 kW
6.60 kW
COP Tj = +2°C
4.71
3.59
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
5.26 kW
5.09 kW
COP Tj = +7°C
5.40
4.48
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.11 kW
6.06 kW
COP Tj = 12°C
6.75
5.60
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
11.49 kW
10.26 kW
COP Tj = Tbiv
2.56
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.49 kW
9.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.54
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
2.96 kW
Annual energy consumption Qhe
5475 kWh
7031 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
138 %
COP
3.33
Heating up time
01:26 h:min
Standby power input
40 W
Reference hot water temperature
50.6 °C
Mixed water at 40°C
255 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
104 %
COP
2.5
Heating up time
02:08 h:min
Standby power input
50 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
120 %
COP
2.87
Heating up time
01:53 h:min
Standby power input
50 W
Reference hot water temperature
52.7 °C
Mixed water at 40°C
264 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.58 kW
12.70 kW
El input
3.41 kW
4.54 kW
COP
4.28
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
229 %
168 %
Prated
14 kW
14 kW
SCOP
5.79
4.27
Tbiv
3 °C
3 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.2 kW
11.85 kW
COP Tj = +2°C
3.16
2.38
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
8.88 kW
9.05 kW
COP Tj = +7°C
5.21
3.58
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
6.16 kW
5.97 kW
COP Tj = 12°C
7.19
5.56
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
12.6 kW
12.3 kW
COP Tj = Tbiv
3.33
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.2 kW
11.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.16
2.38
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
1.8 kW
2.15 kW
Annual energy consumption Qhe
3228 kWh
4384 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
122 %
Prated
12 kW
12 kW
SCOP
3.96
3.12
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
7.62 kW
7.48 kW
COP Tj = -7°C
3.56
2.68
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.53 kW
4.64 kW
COP Tj = +2°C
4.64
3.86
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
5.26 kW
5.01 kW
COP Tj = +7°C
5.43
4.57
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.15 kW
5.98 kW
COP Tj = 12°C
7.13
5.91
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
10.18 kW
8.85 kW
COP Tj = Tbiv
2.42
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.69 kW
7.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.06
1.7
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
12 kW
12 kW
Annual energy consumption Qhe
7474 kWh
9483 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.18
8.31
COP Tj = -15°C (if TOL<-20°C)
2.42
1.88
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
42 dB(A)
42 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
138 %
Prated
12 kW
12 kW
SCOP
4.53
3.53
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.98 kW
10.26 kW
COP Tj = -7°C
2.73
2.10
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
6.71 kW
6.60 kW
COP Tj = +2°C
4.71
3.59
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
5.26 kW
5.09 kW
COP Tj = +7°C
5.40
4.48
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
6.11 kW
6.06 kW
COP Tj = 12°C
6.75
5.60
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
11.49 kW
10.26 kW
COP Tj = Tbiv
2.56
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.49 kW
9.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.54
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
0 W
0 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
2.96 kW
Annual energy consumption Qhe
5475 kWh
7031 kWh