Login

Subtype

Air Source Heat Pump 014

Certificate Holder
SolarEast Heat Pump Ltd.
No.73 Defu Road
528325 Guangdong Province,
China
Registration number
041-K042-03 / 01
Certification Body
BRE Global Limited
Subtype title
Air Source Heat Pump 014
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,800 kg

Certification Date
26.12.2022
Testing basis
Heat Pump Keymark Scheme Rules Rev 11
Generate PDF Export model CSV Download certificate
  • Number of models 4

Models

BLN-014TB1
Configure model
Model name
BLN-014TB1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.52 kW

14.83 kW

El input

3.17 kW

4.88 kW

COP

4.57

3.04

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

126 %

Prated

10.49 kW

9.96 kW

SCOP

4.51

3.22

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.28 kW

8.81 kW

COP Tj = -7°C

3.21

2.16

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.88 kW

5.38 kW

COP Tj = +2°C

4.36

3.15

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.45 kW

5.87 kW

COP Tj = +7°C

6.00

4.30

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

6.22 kW

6.75 kW

COP Tj = 12°C

8.03

6.07

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.28 kW

8.81 kW

COP Tj = Tbiv

3.21

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.00 kW

9.86 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.10

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

51 °C

51 °C

Poff

12 W

12 W

PTO

15 W

15 W

PSB

12 W

12 W

PCK

42 W

42 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.49 kW

0.10 kW

Annual energy consumption Qhe

4808 kWh

6390 kWh

BLN-014TB3
Configure model
Model name
BLN-014TB3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.75 kW

14.87 kW

El input

3.17 kW

4.87 kW

COP

4.66

3.05

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

68 dB(A)

69 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

127 %

Prated

10.71 kW

10.28 kW

SCOP

4.50

3.25

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.48 kW

9.10 kW

COP Tj = -7°C

3.28

2.24

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.81 kW

5.53 kW

COP Tj = +2°C

4.31

3.13

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.50 kW

5.98 kW

COP Tj = +7°C

5.94

4.38

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

6.32 kW

6.79 kW

COP Tj = 12°C

8.28

6.01

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.48 kW

9.10 kW

COP Tj = Tbiv

3.28

2.23

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.23 kW

10.28 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.05

2.19

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

51 °C

51 °C

Poff

15 W

15 W

PTO

17 W

17 W

PSB

15 W

15 W

PCK

40 W

40 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.48 kW

0.00 kW

Annual energy consumption Qhe

4919 kWh

6540 kWh

BLN-014TD1
Configure model
Model name
BLN-014TD1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.52 kW

14.83 kW

El input

3.17 kW

4.88 kW

COP

4.57

3.04

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

126 %

Prated

10.49 kW

9.96 kW

SCOP

4.51

3.22

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.28 kW

8.81 kW

COP Tj = -7°C

3.21

2.16

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.88 kW

5.38 kW

COP Tj = +2°C

4.36

3.15

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.45 kW

5.87 kW

COP Tj = +7°C

6.00

4.30

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

6.22 kW

6.75 kW

COP Tj = 12°C

8.03

6.07

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.28 kW

8.81 kW

COP Tj = Tbiv

3.21

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.00 kW

9.86 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.10

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

51 °C

51 °C

Poff

12 W

12 W

PTO

15 W

15 W

PSB

12 W

12 W

PCK

42 W

42 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

0.10 kW

Annual energy consumption Qhe

4808 kWh

6390 kWh

BLN-014TD3
Configure model
Model name
BLN-014TD3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.75 kW

14.87 kW

El input

3.17 kW

4.87 kW

COP

4.66

3.05

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

68 dB(A)

69 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

127 %

Prated

10.71 kW

10.28 kW

SCOP

4.50

3.25

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.48 kW

9.10 kW

COP Tj = -7°C

3.28

2.24

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.81 kW

5.53 kW

COP Tj = +2°C

4.31

3.13

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.50 kW

5.98 kW

COP Tj = +7°C

5.94

4.38

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

6.32 kW

6.79 kW

COP Tj = 12°C

8.28

6.01

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.48 kW

9.10 kW

COP Tj = Tbiv

3.28

2.24

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.23 kW

10.27 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.05

2.19

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

51 °C

51 °C

Poff

15 W

15 W

PTO

17 W

17 W

PSB

15 W

15 W

PCK

40 W

40 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.48 kW

0.01 kW

Annual energy consumption Qhe

4919 kWh

6540 kWh