0,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.77 kW
5.57 kW
El input
1.14 kW
1.65 kW
COP
5.07
3.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
54 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
143 %
Prated
6.93 kW
6.40 kW
SCOP
4.85
3.65
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.13 kW
5.67 kW
COP Tj = -7°C
3.09
2.29
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.83 kW
3.59 kW
COP Tj = +2°C
4.67
3.64
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.29 kW
3.02 kW
COP Tj = +7°C
6.81
4.99
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.89 kW
3.62 kW
COP Tj = 12°C
9.50
6.28
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.13 kW
5.67 kW
COP Tj = Tbiv
3.09
2.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.64 kW
5.09 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
56 °C
56 °C
Poff
20 W
20 W
PTO
23 W
23 W
PSB
20 W
20 W
PCK
30 W
30 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.29 kW
1.32 kW
Annual energy consumption Qhe
2953 kWh
3622 kWh