1,630 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.80 kW
9.50 kW
El input
2.16 kW
3.33 kW
COP
4.53
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
139 %
Prated
8.70 kW
8.60 kW
SCOP
4.73
3.54
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.70 kW
7.60 kW
COP Tj = -7°C
3.08
2.14
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.70 kW
4.60 kW
COP Tj = +2°C
4.63
3.46
Cdh Tj = +2 °C
0.980
0.980
Pdh Tj = +7°C
3.80 kW
3.60 kW
COP Tj = +7°C
6.41
4.74
Cdh Tj = +7 °C
0.970
0.970
Pdh Tj = 12°C
4.30 kW
4.20 kW
COP Tj = 12°C
7.11
6.40
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
7.70 kW
7.60 kW
COP Tj = Tbiv
3.08
2.14
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
7.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
1.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
55 °C
55 °C
Poff
4 W
4 W
PTO
20 W
21 W
PSB
8 W
8 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.40 kW
0.90 kW
Annual energy consumption Qhe
3796 kWh
5014 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
140 %
COP
3.50
Heating up time
1:25 h:min
Standby power input
35.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
315 l