2,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.25 kW
14.85 kW
El input
3.26 kW
5.41 kW
COP
4.67
2.74
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
69 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
135 %
Prated
15.51 kW
14.66 kW
SCOP
4.57
3.45
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.72 kW
12.97 kW
COP Tj = -7°C
3.31
2.21
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
8.35 kW
7.94 kW
COP Tj = +2°C
4.49
3.50
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.76 kW
7.68 kW
COP Tj = +7°C
5.88
4.42
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
10.68 kW
8.83 kW
COP Tj = 12°C
7.39
5.96
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
13.72 kW
12.97 kW
COP Tj = Tbiv
3.31
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.57 kW
14.41 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.74
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
50 °C
50 °C
Poff
5 W
5 W
PTO
13 W
13 W
PSB
5 W
5 W
PCK
31 W
31 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.25 kW
Annual energy consumption Qhe
7016 kWh
8780 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
17.99 kW
17.49 kW
El input
4.15 kW
4.77 kW
COP
4.34
3.67
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
130 %
Prated
16.22 kW
16.52 kW
SCOP
4.53
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.35 kW
14.61 kW
COP Tj = -7°C
3.38
2.16
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
8.78 kW
8.90 kW
COP Tj = +2°C
4.49
3.37
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.86 kW
7.47 kW
COP Tj = +7°C
5.49
4.23
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
9.40 kW
9.13 kW
COP Tj = 12°C
7.20
5.67
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.35 kW
14.61 kW
COP Tj = Tbiv
3.38
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.16 kW
12.99 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
50 °C
50 °C
Poff
5 W
5 W
PTO
14 W
14 W
PSB
5 W
5 W
PCK
32 W
32 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.06 kW
3.53 kW
Annual energy consumption Qhe
7404 kWh
10257 kWh