2,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.39 kW
12.59 kW
El input
2.65 kW
4.16 kW
COP
4.68
3.02
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
63 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
10.51 kW
10.35 kW
SCOP
4.51
3.31
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.29 kW
9.15 kW
COP Tj = -7°C
2.93
2.01
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.93 kW
5.59 kW
COP Tj = +2°C
4.58
3.36
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
6.86 kW
6.59 kW
COP Tj = +7°C
6.11
4.56
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
7.73 kW
7.56 kW
COP Tj = 12°C
7.91
6.20
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.29 kW
9.15 kW
COP Tj = Tbiv
2.93
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.19 kW
9.79 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
56 °C
56 °C
Poff
18 W
18 W
PTO
19 W
19 W
PSB
18 W
18 W
PCK
41 W
41 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.32 kW
0.56 kW
Annual energy consumption Qhe
4817 kWh
6455 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
11.92 kW
12.13 kW
El input
2.60 kW
4.06 kW
COP
4.58
2.99
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
138 %
Prated
10.69 kW
10.33 kW
SCOP
4.84
3.53
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.46 kW
9.14 kW
COP Tj = -7°C
3.02
2.24
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.00 kW
5.63 kW
COP Tj = +2°C
4.72
3.37
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
6.93 kW
6.63 kW
COP Tj = +7°C
6.27
4.58
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
7.81 kW
7.66 kW
COP Tj = 12°C
8.61
6.81
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.46 kW
9.14 kW
COP Tj = Tbiv
3.02
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.67 kW
9.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
56 °C
56 °C
Poff
8 W
8 W
PTO
8 W
8 W
PSB
8 W
8 W
PCK
41 W
41 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.02 kW
0.90 kW
Annual energy consumption Qhe
4562 kWh
6040 kWh