1,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.39 kW
8.45 kW
El input
1.84 kW
2.93 kW
COP
4.56
2.88
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
129 %
Prated
7.91 kW
7.88 kW
SCOP
4.50
3.29
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.00 kW
6.97 kW
COP Tj = -7°C
2.86
2.16
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.43 kW
4.25 kW
COP Tj = +2°C
4.61
3.38
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.70 kW
4.41 kW
COP Tj = +7°C
6.02
4.13
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.32 kW
5.14 kW
COP Tj = 12°C
8.05
5.71
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.00 kW
6.97 kW
COP Tj = Tbiv
2.86
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.45 kW
7.15 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.58
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
56 °C
56 °C
Poff
8 W
8 W
PTO
12 W
12 W
PSB
8 W
8 W
PCK
44 W
44 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.46 kW
0.73 kW
Annual energy consumption Qhe
3632 kWh
4950 kWh