1,840 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
12.00 kW
El input
2.44 kW
3.87 kW
COP
4.95
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
174 %
Prated
11.11 kW
12.51 kW
SCOP
6.53
4.43
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.11 kW
12.08 kW
COP Tj = +2°C
3.59
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.14 kW
8.04 kW
COP Tj = +7°C
5.87
3.86
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.56 kW
3.75 kW
COP Tj = 12°C
7.94
5.70
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.14 kW
8.04 kW
COP Tj = Tbiv
5.87
3.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.11 kW
12.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.59
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.44 kW
Annual energy consumption Qhe
2292 kWh
3776 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
160 %
118 %
Prated
11.38 kW
10.32 kW
SCOP
4.08
3.02
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.05 kW
6.63 kW
COP Tj = -7°C
3.48
2.63
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
4.68 kW
4.07 kW
COP Tj = +2°C
4.96
3.60
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.14 kW
2.78 kW
COP Tj = +7°C
6.10
4.54
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.57 kW
3.33 kW
COP Tj = 12°C
7.87
6.25
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
9.28 kW
8.42 kW
COP Tj = Tbiv
2.59
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.01 kW
4.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.98
1.13
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.37 kW
6.12 kW
Annual energy consumption Qhe
6870 kWh
8419 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.28
8.42
COP Tj = -15°C (if TOL<-20°C)
2.59
1.84
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
135 %
Prated
12.00 kW
11.58 kW
SCOP
4.81
3.45
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.61 kW
10.25 kW
COP Tj = -7°C
2.88
2.01
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.69 kW
6.52 kW
COP Tj = +2°C
4.65
3.44
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.44 kW
4.36 kW
COP Tj = +7°C
6.62
4.59
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.74 kW
3.30 kW
COP Tj = 12°C
8.47
6.05
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
10.61 kW
10.25 kW
COP Tj = Tbiv
2.88
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.75 kW
9.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
1.79
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.26 kW
2.50 kW
Annual energy consumption Qhe
5152 kWh
6927 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.56 kW
5.52 kW
COP
4.50
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
249 %
176 %
Prated
13.09 kW
14.17 kW
SCOP
6.33
4.48
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.09 kW
13.38 kW
COP Tj = +2°C
3.35
2.29
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
8.42 kW
9.11 kW
COP Tj = +7°C
5.36
3.89
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.88 kW
4.06 kW
COP Tj = 12°C
8.11
5.86
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.42 kW
9.11 kW
COP Tj = Tbiv
5.36
3.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.09 kW
13.38 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.29
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.79 kW
Annual energy consumption Qhe
2781 kWh
4231 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
158 %
122 %
Prated
13.76 kW
11.79 kW
SCOP
4.02
3.12
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.31 kW
7.64 kW
COP Tj = -7°C
3.37
2.65
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.27 kW
4.43 kW
COP Tj = +2°C
4.86
3.79
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.62 kW
2.98 kW
COP Tj = +7°C
6.49
4.81
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.35 kW
3.43 kW
COP Tj = 12°C
7.40
6.29
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
11.22 kW
9.62 kW
COP Tj = Tbiv
2.43
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.89 kW
5.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.97
1.23
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.87 kW
6.57 kW
Annual energy consumption Qhe
8431 kWh
9309 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.22
9.62
COP Tj = -15°C (if TOL<-20°C)
2.43
1.86
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
133 %
Prated
15.21 kW
13.02 kW
SCOP
4.62
3.41
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.45 kW
11.52 kW
COP Tj = -7°C
2.72
1.99
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.57 kW
7.18 kW
COP Tj = +2°C
4.41
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.70 kW
4.68 kW
COP Tj = +7°C
6.56
4.61
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.78 kW
3.32 kW
COP Tj = 12°C
8.51
6.07
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
13.45 kW
11.52 kW
COP Tj = Tbiv
2.72
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.52 kW
10.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.80
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.68 kW
2.67 kW
Annual energy consumption Qhe
6804 kWh
7895 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
11.90 kW
El input
2.44 kW
3.90 kW
COP
4.95
3.05
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
174 %
Prated
11.11 kW
12.51 kW
SCOP
6.53
4.43
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.11 kW
12.08 kW
COP Tj = +2°C
3.59
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.14 kW
8.04 kW
COP Tj = +7°C
5.87
3.86
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.56 kW
3.75 kW
COP Tj = 12°C
7.94
5.70
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.14 kW
8.04 kW
COP Tj = Tbiv
5.87
3.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.11 kW
12.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.59
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.44 kW
Annual energy consumption Qhe
2292 kWh
3776 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
160 %
118 %
Prated
11.38 kW
10.32 kW
SCOP
4.08
3.02
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.05 kW
6.63 kW
COP Tj = -7°C
3.48
2.63
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
4.68 kW
4.07 kW
COP Tj = +2°C
4.96
3.60
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.14 kW
2.78 kW
COP Tj = +7°C
6.10
4.54
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.57 kW
3.33 kW
COP Tj = 12°C
7.87
6.25
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
9.28 kW
8.42 kW
COP Tj = Tbiv
2.59
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.01 kW
4.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.98
1.13
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.37 kW
6.12 kW
Annual energy consumption Qhe
6870 kWh
8419 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.28
8.42
COP Tj = -15°C (if TOL<-20°C)
2.59
1.84
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
135 %
Prated
12.00 kW
11.58 kW
SCOP
4.81
3.45
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.61 kW
10.25 kW
COP Tj = -7°C
2.88
2.01
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.69 kW
6.52 kW
COP Tj = +2°C
4.65
3.44
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.44 kW
4.36 kW
COP Tj = +7°C
6.62
4.59
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.74 kW
3.30 kW
COP Tj = 12°C
8.47
6.05
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
10.61 kW
10.25 kW
COP Tj = Tbiv
2.88
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.75 kW
9.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
1.79
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.26 kW
2.50 kW
Annual energy consumption Qhe
5152 kWh
6927 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.90 kW
16.00 kW
El input
3.53 kW
5.61 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
249 %
176 %
Prated
13.09 kW
14.17 kW
SCOP
6.33
4.48
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.09 kW
13.38 kW
COP Tj = +2°C
3.35
2.29
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
8.42 kW
9.11 kW
COP Tj = +7°C
5.36
3.89
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.88 kW
4.06 kW
COP Tj = 12°C
8.11
5.86
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.42 kW
9.11 kW
COP Tj = Tbiv
5.36
3.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.09 kW
13.38 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.29
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.79 kW
Annual energy consumption Qhe
2781 kWh
4231 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
158 %
122 %
Prated
13.76 kW
11.79 kW
SCOP
4.02
3.12
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.31 kW
7.64 kW
COP Tj = -7°C
3.37
2.65
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.27 kW
4.43 kW
COP Tj = +2°C
4.86
3.79
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.62 kW
2.98 kW
COP Tj = +7°C
6.49
4.81
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.35 kW
3.43 kW
COP Tj = 12°C
7.40
6.29
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
11.22 kW
9.62 kW
COP Tj = Tbiv
2.43
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.89 kW
5.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.97
1.23
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.87 kW
6.57 kW
Annual energy consumption Qhe
8431 kWh
9309 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.22
9.62
COP Tj = -15°C (if TOL<-20°C)
2.43
1.86
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
133 %
Prated
15.21 kW
13.02 kW
SCOP
4.62
3.41
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.45 kW
11.52 kW
COP Tj = -7°C
2.72
1.99
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.57 kW
7.18 kW
COP Tj = +2°C
4.41
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.70 kW
4.68 kW
COP Tj = +7°C
6.56
4.61
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.78 kW
3.32 kW
COP Tj = 12°C
8.51
6.07
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
13.45 kW
11.52 kW
COP Tj = Tbiv
2.72
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.52 kW
10.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.80
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.68 kW
2.67 kW
Annual energy consumption Qhe
6804 kWh
7895 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
12.00 kW
El input
2.44 kW
3.87 kW
COP
4.95
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
174 %
Prated
11.11 kW
12.51 kW
SCOP
6.53
4.42
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.11 kW
12.08 kW
COP Tj = +2°C
3.59
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.14 kW
8.04 kW
COP Tj = +7°C
5.87
3.86
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.56 kW
3.75 kW
COP Tj = 12°C
7.94
5.70
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.14 kW
8.04 kW
COP Tj = Tbiv
5.87
3.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.11 kW
12.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.59
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.44 kW
Annual energy consumption Qhe
2296 kWh
3780 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
160 %
118 %
Prated
11.38 kW
10.32 kW
SCOP
4.08
3.02
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.05 kW
6.63 kW
COP Tj = -7°C
3.48
2.63
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
4.68 kW
4.07 kW
COP Tj = +2°C
4.96
3.60
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.14 kW
2.78 kW
COP Tj = +7°C
6.10
4.54
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.57 kW
3.33 kW
COP Tj = 12°C
7.87
6.25
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
9.28 kW
8.42 kW
COP Tj = Tbiv
2.59
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.01 kW
4.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.98
1.13
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.37 kW
6.12 kW
Annual energy consumption Qhe
6871 kWh
8420 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.28
8.42
COP Tj = -15°C (if TOL<-20°C)
2.59
1.84
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
135 %
Prated
12.00 kW
11.58 kW
SCOP
4.81
3.45
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.61 kW
10.25 kW
COP Tj = -7°C
2.88
2.01
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.69 kW
6.52 kW
COP Tj = +2°C
4.65
3.44
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.44 kW
4.36 kW
COP Tj = +7°C
6.62
4.59
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.74 kW
3.30 kW
COP Tj = 12°C
8.47
6.05
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
10.61 kW
10.25 kW
COP Tj = Tbiv
2.88
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.75 kW
9.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
1.79
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.26 kW
2.50 kW
Annual energy consumption Qhe
5153 kWh
6928 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.56 kW
5.52 kW
COP
4.50
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
248 %
176 %
Prated
13.09 kW
14.17 kW
SCOP
6.33
4.47
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.09 kW
13.38 kW
COP Tj = +2°C
3.35
2.29
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
8.42 kW
9.11 kW
COP Tj = +7°C
5.36
3.89
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.88 kW
4.06 kW
COP Tj = 12°C
8.11
5.86
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.42 kW
9.11 kW
COP Tj = Tbiv
5.36
3.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.09 kW
13.38 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.29
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.79 kW
Annual energy consumption Qhe
2786 kWh
4236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
158 %
122 %
Prated
13.76 kW
11.79 kW
SCOP
4.02
3.12
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.31 kW
7.64 kW
COP Tj = -7°C
3.37
2.65
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.27 kW
4.43 kW
COP Tj = +2°C
4.86
3.79
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.62 kW
2.98 kW
COP Tj = +7°C
6.49
4.81
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.35 kW
3.43 kW
COP Tj = 12°C
7.40
6.29
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
11.22 kW
9.62 kW
COP Tj = Tbiv
2.43
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.89 kW
5.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.97
1.23
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.87 kW
6.57 kW
Annual energy consumption Qhe
8431 kWh
9310 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.22
9.62
COP Tj = -15°C (if TOL<-20°C)
2.43
1.86
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
133 %
Prated
15.21 kW
13.02 kW
SCOP
4.62
3.41
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.45 kW
11.52 kW
COP Tj = -7°C
2.72
1.99
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.57 kW
7.18 kW
COP Tj = +2°C
4.41
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.70 kW
4.68 kW
COP Tj = +7°C
6.56
4.61
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.78 kW
3.32 kW
COP Tj = 12°C
8.51
6.07
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
13.45 kW
11.52 kW
COP Tj = Tbiv
2.72
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.52 kW
10.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.80
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.68 kW
2.67 kW
Annual energy consumption Qhe
6805 kWh
7896 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
11.90 kW
El input
2.44 kW
3.90 kW
COP
4.95
3.05
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
174 %
Prated
11.11 kW
12.51 kW
SCOP
6.53
4.42
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.11 kW
12.08 kW
COP Tj = +2°C
3.59
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.14 kW
8.04 kW
COP Tj = +7°C
5.87
3.86
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.56 kW
3.75 kW
COP Tj = 12°C
7.94
5.70
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.14 kW
8.04 kW
COP Tj = Tbiv
5.87
3.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.11 kW
12.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.59
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.44 kW
Annual energy consumption Qhe
2296 kWh
3780 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
160 %
118 %
Prated
11.38 kW
10.32 kW
SCOP
4.08
3.02
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.05 kW
6.63 kW
COP Tj = -7°C
3.48
2.63
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
4.68 kW
4.07 kW
COP Tj = +2°C
4.96
3.60
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.14 kW
2.78 kW
COP Tj = +7°C
6.10
4.54
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.57 kW
3.33 kW
COP Tj = 12°C
7.87
6.25
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
9.28 kW
8.42 kW
COP Tj = Tbiv
2.59
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.01 kW
4.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.98
1.13
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.37 kW
6.12 kW
Annual energy consumption Qhe
6871 kWh
8420 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.28
8.42
COP Tj = -15°C (if TOL<-20°C)
2.59
1.84
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
135 %
Prated
12.00 kW
11.58 kW
SCOP
4.81
3.45
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.61 kW
10.25 kW
COP Tj = -7°C
2.88
2.01
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.69 kW
6.52 kW
COP Tj = +2°C
4.65
3.44
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.44 kW
4.36 kW
COP Tj = +7°C
6.62
4.59
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.74 kW
3.30 kW
COP Tj = 12°C
8.47
6.05
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
10.61 kW
10.25 kW
COP Tj = Tbiv
2.88
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.75 kW
9.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
1.79
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.26 kW
2.50 kW
Annual energy consumption Qhe
5153 kWh
6928 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.90 kW
16.00 kW
El input
3.53 kW
5.61 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
248 %
176 %
Prated
13.09 kW
14.17 kW
SCOP
6.33
4.47
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.09 kW
13.38 kW
COP Tj = +2°C
3.35
2.29
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
8.42 kW
9.11 kW
COP Tj = +7°C
5.36
3.89
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.88 kW
4.06 kW
COP Tj = 12°C
8.11
5.86
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.42 kW
9.11 kW
COP Tj = Tbiv
5.36
3.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.09 kW
13.38 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.29
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.79 kW
Annual energy consumption Qhe
2786 kWh
4236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
158 %
122 %
Prated
13.76 kW
11.79 kW
SCOP
4.02
3.12
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.31 kW
7.64 kW
COP Tj = -7°C
3.37
2.65
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.27 kW
4.43 kW
COP Tj = +2°C
4.86
3.79
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.62 kW
2.98 kW
COP Tj = +7°C
6.49
4.81
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.35 kW
3.43 kW
COP Tj = 12°C
7.40
6.29
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
11.22 kW
9.62 kW
COP Tj = Tbiv
2.43
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.89 kW
5.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.97
1.23
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.87 kW
6.57 kW
Annual energy consumption Qhe
8431 kWh
9310 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.22
9.62
COP Tj = -15°C (if TOL<-20°C)
2.43
1.86
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
133 %
Prated
15.21 kW
13.02 kW
SCOP
4.62
3.41
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.45 kW
11.52 kW
COP Tj = -7°C
2.72
1.99
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.57 kW
7.18 kW
COP Tj = +2°C
4.41
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.70 kW
4.68 kW
COP Tj = +7°C
6.56
4.61
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.78 kW
3.32 kW
COP Tj = 12°C
8.51
6.07
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
13.45 kW
11.52 kW
COP Tj = Tbiv
2.72
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.52 kW
10.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.80
WTOL
65 °C
65 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.68 kW
2.67 kW
Annual energy consumption Qhe
6805 kWh
7896 kWh