2,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.43 kW
3.93 kW
COP
4.94
3.05
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
149 %
Prated
12.00 kW
12.00 kW
SCOP
4.78
3.80
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.70 kW
10.30 kW
COP Tj = -7°C
2.98
2.11
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.10 kW
6.80 kW
COP Tj = +2°C
4.38
3.81
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.10 kW
4.30 kW
COP Tj = +7°C
7.03
5.01
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
3.40 kW
3.60 kW
COP Tj = 12°C
9.49
7.32
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
10.70 kW
10.30 kW
COP Tj = Tbiv
2.98
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.20 kW
9.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.62
1.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.80 kW
2.20 kW
Annual energy consumption Qhe
5194 kWh
6388 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
273 %
180 %
Prated
12.00 kW
12.00 kW
SCOP
6.90
4.58
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.60 kW
12.20 kW
COP Tj = +2°C
3.65
2.27
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
7.30 kW
8.10 kW
COP Tj = +7°C
5.74
3.74
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.30 kW
3.50 kW
COP Tj = 12°C
9.38
6.29
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
11.60 kW
12.20 kW
COP Tj = Tbiv
3.65
2.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.60 kW
12.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.65
2.27
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2236 kWh
3558 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
181 %
129 %
Prated
11.00 kW
12.00 kW
SCOP
4.60
3.30
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.90 kW
7.80 kW
COP Tj = -7°C
3.88
2.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.10 kW
4.40 kW
COP Tj = +2°C
5.71
3.95
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.70 kW
2.80 kW
COP Tj = +7°C
7.20
5.55
Cdh Tj = +7 °C
0.930
0.950
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
8.77
7.45
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.20 kW
9.90 kW
COP Tj = Tbiv
2.74
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
7.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.10 kW
5.00 kW
Annual energy consumption Qhe
6044 kWh
9034 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.20
9.90
COP Tj = -15°C (if TOL<-20°C)
2.74
1.96
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.49 kW
4.12 kW
COP
4.82
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
150 %
Prated
12.00 kW
12.00 kW
SCOP
4.58
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.80 kW
10.50 kW
COP Tj = -7°C
3.01
2.02
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
6.70 kW
6.60 kW
COP Tj = +2°C
4.50
3.76
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.50 kW
4.50 kW
COP Tj = +7°C
5.82
5.51
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
3.30 kW
3.50 kW
COP Tj = 12°C
7.45
7.06
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
10.80 kW
10.50 kW
COP Tj = Tbiv
3.01
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.90 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.51
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.10 kW
0.50 kW
Annual energy consumption Qhe
5517 kWh
6391 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
244 %
169 %
Prated
12.00 kW
12.00 kW
SCOP
6.18
4.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.70 kW
12.30 kW
COP Tj = +2°C
3.43
2.51
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
7.50 kW
7.90 kW
COP Tj = +7°C
5.41
3.50
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
7.85
5.80
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
11.70 kW
12.30 kW
COP Tj = Tbiv
3.43
2.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
12.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.43
2.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2531 kWh
3822 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
159 %
117 %
Prated
11.00 kW
12.00 kW
SCOP
4.05
3.00
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.00 kW
7.80 kW
COP Tj = -7°C
3.40
2.55
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
5.04
3.71
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.00 kW
2.90 kW
COP Tj = +7°C
6.04
4.61
Cdh Tj = +7 °C
0.950
0.960
Pdh Tj = 12°C
3.30 kW
3.30 kW
COP Tj = 12°C
7.23
5.24
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
9.00 kW
9.60 kW
COP Tj = Tbiv
2.42
1.79
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.40 kW
5.30 kW
Annual energy consumption Qhe
6685 kWh
9548 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.00
9.60
COP Tj = -15°C (if TOL<-20°C)
2.42
1.79
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.20 kW
13.80 kW
El input
2.99 kW
4.67 kW
COP
4.75
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
147 %
Prated
13.00 kW
13.00 kW
SCOP
4.70
3.75
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
11.80 kW
COP Tj = -7°C
2.71
2.10
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
7.10 kW
6.80 kW
COP Tj = +2°C
4.39
3.81
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.40 kW
4.80 kW
COP Tj = +7°C
6.89
4.77
Cdh Tj = +7 °C
0.960
0.980
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
10.30
7.36
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.50 kW
11.80 kW
COP Tj = Tbiv
2.71
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.50 kW
9.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.38
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
3.40 kW
Annual energy consumption Qhe
5682 kWh
7352 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
268 %
186 %
Prated
14.00 kW
14.00 kW
SCOP
6.78
4.73
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
14.00 kW
14.20 kW
COP Tj = +2°C
3.38
2.30
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.40 kW
8.40 kW
COP Tj = +7°C
5.57
3.73
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.80 kW
4.20 kW
COP Tj = 12°C
9.32
6.75
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
14.00 kW
14.20 kW
COP Tj = Tbiv
3.38
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.00 kW
14.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.38
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2755 kWh
4008 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
184 %
132 %
Prated
12.00 kW
13.00 kW
SCOP
4.68
3.38
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.90 kW
7.80 kW
COP Tj = -7°C
3.88
2.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.50 kW
5.20 kW
COP Tj = +2°C
5.93
4.23
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.70 kW
2.90 kW
COP Tj = +7°C
7.20
5.24
Cdh Tj = +7 °C
0.930
0.950
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
8.98
7.55
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.70 kW
10.70 kW
COP Tj = Tbiv
2.72
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
7.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.10 kW
6.00 kW
Annual energy consumption Qhe
6257 kWh
9572 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.70
COP Tj = -15°C (if TOL<-20°C)
2.72
1.99
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.20 kW
13.80 kW
El input
3.09 kW
4.84 kW
COP
4.60
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
150 %
Prated
13.00 kW
13.00 kW
SCOP
4.55
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.60 kW
11.80 kW
COP Tj = -7°C
2.89
2.21
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
6.70 kW
6.90 kW
COP Tj = +2°C
4.50
3.65
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.50 kW
4.50 kW
COP Tj = +7°C
5.82
5.51
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
3.40 kW
3.50 kW
COP Tj = 12°C
7.53
7.06
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
11.60 kW
11.80 kW
COP Tj = Tbiv
2.89
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.10 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.28
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
1.40 kW
Annual energy consumption Qhe
5927 kWh
7176 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
240 %
159 %
Prated
14.00 kW
15.00 kW
SCOP
6.08
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.70 kW
14.60 kW
COP Tj = +2°C
2.90
2.31
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.50 kW
8.80 kW
COP Tj = +7°C
5.36
3.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.70 kW
3.90 kW
COP Tj = 12°C
7.86
5.47
Cdh Tj = +12 °C
0.950
0.970
Pdh Tj = Tbiv
13.70 kW
14.60 kW
COP Tj = Tbiv
2.90
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.70 kW
14.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2995 kWh
4801 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
158 %
118 %
Prated
12.00 kW
13.00 kW
SCOP
4.03
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.00 kW
7.80 kW
COP Tj = -7°C
3.40
2.55
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
5.04
3.71
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.00 kW
2.90 kW
COP Tj = +7°C
6.06
4.61
Cdh Tj = +7 °C
0.950
0.960
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
6.17
5.03
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
9.70 kW
10.40 kW
COP Tj = Tbiv
2.38
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.40 kW
6.30 kW
Annual energy consumption Qhe
7293 kWh
10373 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.40
COP Tj = -15°C (if TOL<-20°C)
2.38
1.82
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.70 kW
15.40 kW
El input
3.45 kW
5.31 kW
COP
4.55
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
146 %
Prated
14.00 kW
14.00 kW
SCOP
4.68
3.73
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.20 kW
12.30 kW
COP Tj = -7°C
2.68
2.18
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
7.10 kW
6.80 kW
COP Tj = +2°C
4.39
3.81
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.70 kW
4.80 kW
COP Tj = +7°C
6.86
4.77
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
10.30
7.36
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
12.20 kW
12.30 kW
COP Tj = Tbiv
2.68
2.18
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.20 kW
8.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.38
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.80 kW
5.50 kW
Annual energy consumption Qhe
6072 kWh
7675 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
267 %
186 %
Prated
14.00 kW
14.00 kW
SCOP
6.75
4.73
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
14.20 kW
14.20 kW
COP Tj = +2°C
3.35
2.30
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.40 kW
8.40 kW
COP Tj = +7°C
5.57
3.73
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.80 kW
4.20 kW
COP Tj = 12°C
9.32
6.75
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
14.20 kW
14.20 kW
COP Tj = Tbiv
3.35
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.20 kW
14.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2800 kWh
4008 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
184 %
132 %
Prated
12.00 kW
13.00 kW
SCOP
4.68
3.38
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.90 kW
7.80 kW
COP Tj = -7°C
3.88
2.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.50 kW
5.20 kW
COP Tj = +2°C
5.93
4.23
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.70 kW
2.90 kW
COP Tj = +7°C
7.20
5.24
Cdh Tj = +7 °C
0.930
0.950
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
8.98
7.55
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.70 kW
10.70 kW
COP Tj = Tbiv
2.71
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
7.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.10 kW
6.00 kW
Annual energy consumption Qhe
6257 kWh
9572 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.70
COP Tj = -15°C (if TOL<-20°C)
2.71
1.99
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.70 kW
15.40 kW
El input
3.57 kW
5.60 kW
COP
4.40
2.75
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
150 %
Prated
13.00 kW
14.00 kW
SCOP
4.55
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.60 kW
12.10 kW
COP Tj = -7°C
2.89
2.16
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
6.70 kW
6.90 kW
COP Tj = +2°C
4.50
3.65
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.50 kW
4.50 kW
COP Tj = +7°C
5.82
5.51
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
3.40 kW
3.50 kW
COP Tj = 12°C
7.53
7.06
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
11.60 kW
12.10 kW
COP Tj = Tbiv
2.89
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.10 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.29
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.50 kW
Annual energy consumption Qhe
5927 kWh
7404 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
241 %
159 %
Prated
14.00 kW
15.00 kW
SCOP
6.10
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.70 kW
14.60 kW
COP Tj = +2°C
2.90
2.31
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.50 kW
8.80 kW
COP Tj = +7°C
5.36
3.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.70 kW
3.90 kW
COP Tj = 12°C
7.86
5.47
Cdh Tj = +12 °C
0.950
0.970
Pdh Tj = Tbiv
13.70 kW
14.60 kW
COP Tj = Tbiv
2.90
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.70 kW
14.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2995 kWh
4801 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
158 %
118 %
Prated
12.00 kW
13.00 kW
SCOP
4.03
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.00 kW
7.80 kW
COP Tj = -7°C
3.40
2.55
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
5.04
3.71
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.00 kW
2.90 kW
COP Tj = +7°C
6.06
4.61
Cdh Tj = +7 °C
0.950
0.960
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
6.17
5.02
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
9.70 kW
10.40 kW
COP Tj = Tbiv
2.38
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.40 kW
6.30 kW
Annual energy consumption Qhe
7293 kWh
10373 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.40
COP Tj = -15°C (if TOL<-20°C)
2.38
1.82
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.43 kW
3.93 kW
COP
4.94
3.05
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
149 %
Prated
12.00 kW
12.00 kW
SCOP
4.78
3.80
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.70 kW
10.30 kW
COP Tj = -7°C
2.98
2.11
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.10 kW
6.80 kW
COP Tj = +2°C
4.38
3.81
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.10 kW
4.30 kW
COP Tj = +7°C
7.03
5.01
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
3.40 kW
3.60 kW
COP Tj = 12°C
9.49
7.32
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
10.70 kW
10.30 kW
COP Tj = Tbiv
2.98
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.20 kW
9.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.62
1.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.80 kW
2.20 kW
Annual energy consumption Qhe
5194 kWh
6388 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
273 %
180 %
Prated
12.00 kW
12.00 kW
SCOP
6.90
4.58
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.60 kW
12.20 kW
COP Tj = +2°C
3.65
2.27
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
7.30 kW
8.10 kW
COP Tj = +7°C
5.74
3.74
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.30 kW
3.50 kW
COP Tj = 12°C
9.38
6.29
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
11.60 kW
12.20 kW
COP Tj = Tbiv
3.65
2.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.60 kW
12.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.65
2.27
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2236 kWh
3558 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
181 %
129 %
Prated
11.00 kW
12.00 kW
SCOP
4.60
3.30
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.90 kW
7.80 kW
COP Tj = -7°C
3.88
2.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.10 kW
4.40 kW
COP Tj = +2°C
5.71
3.95
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.70 kW
2.80 kW
COP Tj = +7°C
7.20
5.55
Cdh Tj = +7 °C
0.930
0.950
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
8.77
7.45
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.20 kW
9.90 kW
COP Tj = Tbiv
2.74
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
7.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.10 kW
5.00 kW
Annual energy consumption Qhe
6044 kWh
9034 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.20
9.90
COP Tj = -15°C (if TOL<-20°C)
2.74
1.96
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.49 kW
4.12 kW
COP
4.82
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
150 %
Prated
12.00 kW
12.00 kW
SCOP
4.58
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.80 kW
10.50 kW
COP Tj = -7°C
3.01
2.02
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
6.70 kW
6.60 kW
COP Tj = +2°C
4.50
3.76
Cdh Tj = +2 °C
0.970
0.990
Pdh Tj = +7°C
4.50 kW
4.50 kW
COP Tj = +7°C
5.82
5.51
Cdh Tj = +7 °C
0.960
0.980
Pdh Tj = 12°C
3.30 kW
3.50 kW
COP Tj = 12°C
7.45
7.06
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
10.80 kW
10.50 kW
COP Tj = Tbiv
3.01
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.90 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.51
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.10 kW
0.50 kW
Annual energy consumption Qhe
5517 kWh
6391 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
244 %
169 %
Prated
12.00 kW
12.00 kW
SCOP
6.18
4.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.70 kW
12.30 kW
COP Tj = +2°C
3.43
2.51
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
7.50 kW
7.90 kW
COP Tj = +7°C
5.41
3.50
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
7.85
5.80
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
11.70 kW
12.30 kW
COP Tj = Tbiv
3.43
2.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
12.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.43
2.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2531 kWh
3822 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
159 %
117 %
Prated
11.00 kW
12.00 kW
SCOP
4.05
3.00
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.00 kW
7.80 kW
COP Tj = -7°C
3.40
2.55
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
5.04
3.71
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.00 kW
2.90 kW
COP Tj = +7°C
6.04
4.61
Cdh Tj = +7 °C
0.950
0.960
Pdh Tj = 12°C
3.30 kW
3.30 kW
COP Tj = 12°C
7.23
5.24
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
9.00 kW
9.60 kW
COP Tj = Tbiv
2.42
1.79
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.40 kW
5.30 kW
Annual energy consumption Qhe
6685 kWh
9548 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.00
9.60
COP Tj = -15°C (if TOL<-20°C)
2.42
1.79
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.20 kW
13.80 kW
El input
2.99 kW
4.67 kW
COP
4.75
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
147 %
Prated
13.00 kW
13.00 kW
SCOP
4.70
3.75
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
11.80 kW
COP Tj = -7°C
2.71
2.10
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
7.10 kW
6.80 kW
COP Tj = +2°C
4.39
3.81
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.40 kW
4.80 kW
COP Tj = +7°C
6.89
4.77
Cdh Tj = +7 °C
0.960
0.980
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
10.30
7.36
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.50 kW
11.80 kW
COP Tj = Tbiv
2.71
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.50 kW
9.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.38
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
3.40 kW
Annual energy consumption Qhe
5682 kWh
7352 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
268 %
186 %
Prated
14.00 kW
14.00 kW
SCOP
6.78
4.73
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
14.00 kW
14.20 kW
COP Tj = +2°C
3.38
2.30
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.40 kW
8.40 kW
COP Tj = +7°C
5.57
3.73
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.80 kW
4.20 kW
COP Tj = 12°C
9.32
6.75
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
14.00 kW
14.20 kW
COP Tj = Tbiv
3.38
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.00 kW
14.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.38
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2755 kWh
4008 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
184 %
132 %
Prated
12.00 kW
13.00 kW
SCOP
4.68
3.38
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.90 kW
7.80 kW
COP Tj = -7°C
3.88
2.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.50 kW
5.20 kW
COP Tj = +2°C
5.93
4.23
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.70 kW
2.90 kW
COP Tj = +7°C
7.20
5.24
Cdh Tj = +7 °C
0.930
0.950
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
8.98
7.55
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.70 kW
10.70 kW
COP Tj = Tbiv
2.72
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
7.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.10 kW
6.00 kW
Annual energy consumption Qhe
6257 kWh
9572 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.70
COP Tj = -15°C (if TOL<-20°C)
2.72
1.99
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.20 kW
13.80 kW
El input
3.09 kW
4.84 kW
COP
4.60
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
150 %
Prated
13.00 kW
13.00 kW
SCOP
4.55
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.60 kW
11.80 kW
COP Tj = -7°C
2.89
2.21
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
6.70 kW
6.90 kW
COP Tj = +2°C
4.50
3.65
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.50 kW
4.50 kW
COP Tj = +7°C
5.82
5.51
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
3.40 kW
3.50 kW
COP Tj = 12°C
7.53
7.06
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
11.60 kW
11.80 kW
COP Tj = Tbiv
2.89
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.10 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.28
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
1.40 kW
Annual energy consumption Qhe
5927 kWh
7176 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
240 %
159 %
Prated
14.00 kW
15.00 kW
SCOP
6.08
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.70 kW
14.60 kW
COP Tj = +2°C
2.90
2.31
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.50 kW
8.80 kW
COP Tj = +7°C
5.36
3.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.70 kW
3.90 kW
COP Tj = 12°C
7.86
5.47
Cdh Tj = +12 °C
0.940
0.970
Pdh Tj = Tbiv
13.70 kW
14.60 kW
COP Tj = Tbiv
2.90
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.70 kW
14.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2995 kWh
4801 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
158 %
118 %
Prated
12.00 kW
13.00 kW
SCOP
4.03
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.00 kW
7.80 kW
COP Tj = -7°C
3.40
2.55
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
5.04
3.71
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.00 kW
2.90 kW
COP Tj = +7°C
6.06
4.61
Cdh Tj = +7 °C
0.950
0.960
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
6.17
5.03
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
9.70 kW
10.40 kW
COP Tj = Tbiv
2.38
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.40 kW
6.30 kW
Annual energy consumption Qhe
7293 kWh
10373 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.40
COP Tj = -15°C (if TOL<-20°C)
2.38
1.82
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.70 kW
15.40 kW
El input
3.45 kW
5.31 kW
COP
4.55
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
146 %
Prated
14.00 kW
14.00 kW
SCOP
4.68
3.73
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.20 kW
12.30 kW
COP Tj = -7°C
2.68
2.18
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
7.10 kW
6.80 kW
COP Tj = +2°C
4.39
3.81
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.70 kW
4.80 kW
COP Tj = +7°C
6.86
4.77
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
10.30
7.36
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
12.20 kW
12.30 kW
COP Tj = Tbiv
2.68
2.18
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.20 kW
8.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.38
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.80 kW
5.50 kW
Annual energy consumption Qhe
6072 kWh
7675 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
267 %
186 %
Prated
14.00 kW
14.00 kW
SCOP
6.75
4.73
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
14.20 kW
14.20 kW
COP Tj = +2°C
3.35
2.30
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.40 kW
8.40 kW
COP Tj = +7°C
5.57
3.73
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.80 kW
4.20 kW
COP Tj = 12°C
9.32
6.75
Cdh Tj = +12 °C
0.940
0.960
Pdh Tj = Tbiv
14.20 kW
14.20 kW
COP Tj = Tbiv
3.35
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.20 kW
14.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2800 kWh
4008 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
184 %
132 %
Prated
12.00 kW
13.00 kW
SCOP
4.68
3.38
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.90 kW
7.80 kW
COP Tj = -7°C
3.88
2.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.50 kW
5.20 kW
COP Tj = +2°C
5.93
4.23
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.70 kW
2.90 kW
COP Tj = +7°C
7.20
5.24
Cdh Tj = +7 °C
0.930
0.950
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
8.98
7.55
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.70 kW
10.70 kW
COP Tj = Tbiv
2.71
1.99
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
7.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.10 kW
6.00 kW
Annual energy consumption Qhe
6257 kWh
9572 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.70
COP Tj = -15°C (if TOL<-20°C)
2.71
1.99
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.70 kW
15.40 kW
El input
3.57 kW
5.60 kW
COP
4.40
2.75
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
150 %
Prated
13.00 kW
14.00 kW
SCOP
4.55
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.60 kW
12.10 kW
COP Tj = -7°C
2.89
2.16
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
6.70 kW
6.90 kW
COP Tj = +2°C
4.50
3.65
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.50 kW
4.50 kW
COP Tj = +7°C
5.82
5.51
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
3.40 kW
3.50 kW
COP Tj = 12°C
7.53
7.06
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
11.60 kW
12.10 kW
COP Tj = Tbiv
2.89
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.10 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.29
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.50 kW
Annual energy consumption Qhe
5927 kWh
7404 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
241 %
159 %
Prated
14.00 kW
15.00 kW
SCOP
6.10
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.70 kW
14.60 kW
COP Tj = +2°C
2.90
2.31
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
8.50 kW
8.80 kW
COP Tj = +7°C
5.36
3.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
3.70 kW
3.90 kW
COP Tj = 12°C
7.86
5.47
Cdh Tj = +12 °C
0.950
0.970
Pdh Tj = Tbiv
13.70 kW
14.60 kW
COP Tj = Tbiv
2.90
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.70 kW
14.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2995 kWh
4801 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
158 %
118 %
Prated
12.00 kW
13.00 kW
SCOP
4.03
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.00 kW
7.80 kW
COP Tj = -7°C
3.40
2.55
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
5.04
3.71
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.00 kW
2.90 kW
COP Tj = +7°C
6.06
4.61
Cdh Tj = +7 °C
0.950
0.960
Pdh Tj = 12°C
3.20 kW
3.30 kW
COP Tj = 12°C
6.17
5.02
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
9.70 kW
10.40 kW
COP Tj = Tbiv
2.38
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.40 kW
6.30 kW
Annual energy consumption Qhe
7293 kWh
10373 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.70
10.40
COP Tj = -15°C (if TOL<-20°C)
2.38
1.82
Cdh Tj = -15 °C
0.990
0.990
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
110 %
COP
2.63
Heating up time
1:38 h:min
Standby power input
60.2 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
325 l
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
1:40 h:min
Standby power input
57.8 W
Reference hot water temperature
49.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
87 %
COP
2.08
Heating up time
2:15 h:min
Standby power input
72.9 W
Reference hot water temperature
48.0 °C
Mixed water at 40°C
330 l