Login

Subtype

R32 Hydrosplit, IWT 12 14 16 kW 1 phase & 3 phases

Certificate Holder
LG Electronics Inc.
84, Wanam-ro, seongsan-gu
51554 Changwon-si
South Korea
Registration number
011-1W0466
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
R32 Hydrosplit, IWT 12 14 16 kW 1 phase & 3 phases
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,100 kg

Certification Date
14.04.2021
Testing basis
European KEYMARK Scheme for Heat Pumps Rev. 8 (as of 2020-09)
Generate PDF Export model CSV
  • Number of models 6

Models

HU121MRB U30 / HN1616Y NB1
Configure model
Model name
HU121MRB U30 / HN1616Y NB1
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.00 kW

11.00 kW

El input

2.38 kW

3.79 kW

COP

5.04

2.90

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

137 %

Prated

11.50 kW

12.00 kW

SCOP

4.60

3.50

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.20 kW

10.20 kW

COP Tj = -7°C

3.01

2.20

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.20 kW

6.30 kW

COP Tj = +2°C

4.42

3.38

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

6.04

4.67

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

5.00 kW

4.60 kW

COP Tj = 12°C

8.44

6.66

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

11.50 kW

10.20 kW

COP Tj = Tbiv

2.65

2.20

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.50 kW

10.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.92

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

65 °C

65 °C

Poff

60 W

60 W

PTO

60 W

60 W

PSB

60 W

60 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

Electricity

Supplementary Heater: PSUP

0.00 kW

1.20 kW

Annual energy consumption Qhe

5165 kWh

6788 kWh

Operating test

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

120 %

COP

2.74

Heating up time

1:25 h:min

Standby power input

69.0 W

Reference hot water temperature

49.0 °C

Mixed water at 40°C

222 l

Operating test

EN 16147

Temperature operating range

passed

Safety devices checking test

passed

Condensate draining

passed

HU141MRB U30 / HN1616Y NB1
Configure model
Model name
HU141MRB U30 / HN1616Y NB1
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.00 kW

11.50 kW

El input

2.86 kW

4.03 kW

COP

4.89

2.85

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

136 %

Prated

12.00 kW

12.00 kW

SCOP

4.57

3.47

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.60 kW

10.40 kW

COP Tj = -7°C

2.94

2.16

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.50 kW

6.30 kW

COP Tj = +2°C

4.45

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.70 kW

4.70 kW

COP Tj = +7°C

5.95

4.66

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

5.00 kW

4.60 kW

COP Tj = 12°C

8.12

6.62

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.00 kW

10.40 kW

COP Tj = Tbiv

2.60

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.00 kW

10.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.86

WTOL

65 °C

65 °C

Poff

60 W

60 W

PTO

60 W

60 W

PSB

60 W

60 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

Electricity

Supplementary Heater: PSUP

0.00 kW

1.10 kW

Annual energy consumption Qhe

5425 kWh

6991 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

120 %

COP

2.74

Heating up time

1:25 h:min

Standby power input

69.0 W

Reference hot water temperature

49.0 °C

Mixed water at 40°C

222 l

HU161MRB U30 / HN1616Y NB1
Configure model
Model name
HU161MRB U30 / HN1616Y NB1
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

12.00 kW

El input

3.33 kW

4.29 kW

COP

4.80

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

135 %

Prated

12.00 kW

12.00 kW

SCOP

4.55

3.45

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.90 kW

10.60 kW

COP Tj = -7°C

2.88

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.70 kW

6.50 kW

COP Tj = +2°C

4.45

3.34

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.00 kW

5.20 kW

COP Tj = +7°C

5.97

4.65

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

5.30 kW

4.60 kW

COP Tj = 12°C

8.11

6.58

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.30 kW

10.60 kW

COP Tj = Tbiv

2.56

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.30 kW

11.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.85

WTOL

65 °C

65 °C

Poff

60 W

60 W

PTO

60 W

60 W

PSB

60 W

60 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

Electricity

Supplementary Heater: PSUP

0.00 kW

0.90 kW

Annual energy consumption Qhe

5586 kWh

7187 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

120 %

COP

2.74

Heating up time

1:25 h:min

Standby power input

69.0 W

Reference hot water temperature

49.0 °C

Mixed water at 40°C

222 l

HU123MRB U30 / HN1616Y NB1
Configure model
Model name
HU123MRB U30 / HN1616Y NB1
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.00 kW

11.00 kW

El input

2.38 kW

3.79 kW

COP

5.04

2.90

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

137 %

Prated

11.50 kW

12.00 kW

SCOP

4.60

3.50

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.20 kW

10.20 kW

COP Tj = -7°C

3.01

2.20

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.20 kW

6.30 kW

COP Tj = +2°C

4.42

3.38

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.50 kW

4.60 kW

COP Tj = +7°C

6.04

4.67

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

5.00 kW

4.60 kW

COP Tj = 12°C

8.44

6.66

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

11.50 kW

10.20 kW

COP Tj = Tbiv

2.65

2.20

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.50 kW

10.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.92

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

65 °C

65 °C

Poff

60 W

60 W

PTO

60 W

60 W

PSB

60 W

60 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

Electricity

Supplementary Heater: PSUP

0.00 kW

1.20 kW

Annual energy consumption Qhe

5165 kWh

6788 kWh

Operating test

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

120 %

COP

2.74

Heating up time

1:25 h:min

Standby power input

69.0 W

Reference hot water temperature

49.0 °C

Mixed water at 40°C

222 l

Operating test

EN 16147

Temperature operating range

passed

Safety devices checking test

passed

Condensate draining

passed

HU143MRB U30 / HN1616Y NB1
Configure model
Model name
HU143MRB U30 / HN1616Y NB1
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.00 kW

11.50 kW

El input

2.86 kW

4.03 kW

COP

4.89

2.85

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

136 %

Prated

12.00 kW

12.00 kW

SCOP

4.57

3.47

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.60 kW

10.40 kW

COP Tj = -7°C

2.94

2.16

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.50 kW

6.30 kW

COP Tj = +2°C

4.45

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.70 kW

4.70 kW

COP Tj = +7°C

5.95

4.66

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

5.00 kW

4.60 kW

COP Tj = 12°C

8.12

6.62

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.00 kW

10.40 kW

COP Tj = Tbiv

2.60

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.00 kW

10.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.86

WTOL

65 °C

65 °C

Poff

60 W

60 W

PTO

60 W

60 W

PSB

60 W

60 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

Electricity

Supplementary Heater: PSUP

0.00 kW

1.10 kW

Annual energy consumption Qhe

5425 kWh

6991 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

120 %

COP

2.74

Heating up time

1:25 h:min

Standby power input

69.0 W

Reference hot water temperature

49.0 °C

Mixed water at 40°C

222 l

HU163MRB U30 / HN1616Y NB1
Configure model
Model name
HU163MRB U30 / HN1616Y NB1
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

12.00 kW

El input

3.33 kW

4.29 kW

COP

4.80

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

135 %

Prated

12.00 kW

12.00 kW

SCOP

4.55

3.45

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.90 kW

10.60 kW

COP Tj = -7°C

2.88

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.70 kW

6.50 kW

COP Tj = +2°C

4.45

3.34

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.00 kW

5.20 kW

COP Tj = +7°C

5.97

4.65

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

5.30 kW

4.60 kW

COP Tj = 12°C

8.11

6.58

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.30 kW

10.60 kW

COP Tj = Tbiv

2.56

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.30 kW

11.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.85

WTOL

65 °C

65 °C

Poff

60 W

60 W

PTO

60 W

60 W

PSB

60 W

60 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

Electricity

Supplementary Heater: PSUP

0.00 kW

0.90 kW

Annual energy consumption Qhe

5586 kWh

7187 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

120 %

COP

2.74

Heating up time

1:25 h:min

Standby power input

69.0 W

Reference hot water temperature

49.0 °C

Mixed water at 40°C

222 l