17,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
78.37 kW
75.56 kW
El input
18.57 kW
29.87 kW
COP
4.22
2.53
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
211 %
154 %
Prated
64.53 kW
58.46 kW
SCOP
5.35
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
64.53 kW
58.46 kW
COP Tj = +2°C
3.25
2.2
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
41.62 kW
36.56 kW
COP Tj = +7°C
4.96
3.2
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36 kW
33.33 kW
COP Tj = 12°C
6.5
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
64.53 kW
58.46 kW
COP Tj = Tbiv
3.25
2.2
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
64.53 kW
58.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.25
2.2
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
16214 kWh
19936 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
148 %
110 %
Prated
48.11 kW
57.26 kW
SCOP
3.77
2.83
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
28.89 kW
35.07 kW
COP Tj = -7°C
3.19
2.21
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.23 kW
27.2 kW
COP Tj = +2°C
5.04
3.93
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
32.98 kW
31.06 kW
COP Tj = +7°C
5.83
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.06 kW
34.62 kW
COP Tj = 12°C
6.6
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
39.25 kW
42.19 kW
COP Tj = Tbiv
2.08
1.79
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
31.92 kW
39.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.58
1.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
48.11 kW
57.26 kW
Annual energy consumption Qhe
31462 kWh
49913 kWh
Pdh Tj = -15°C (if TOL<-20°C)
39.25
42.19
COP Tj = -15°C (if TOL<-20°C)
2.08
1.79
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
125 %
Prated
53.4 kW
58.2 kW
SCOP
4.22
3.2
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
47.21 kW
47.66 kW
COP Tj = -7°C
2.70
1.96
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.76 kW
29.59 kW
COP Tj = +2°C
4.30
3.12
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.04 kW
39.10 kW
COP Tj = +7°C
5.39
4.42
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.87 kW
33.21 kW
COP Tj = 12°C
6.74
6.07
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
47.21 kW
49.09 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
44.78 kW
45.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.59 kW
12.98 kW
Annual energy consumption Qhe
25852 kWh
36978 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
78.37 kW
75.56 kW
El input
18.57 kW
29.87 kW
COP
4.22
2.53
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
211 %
154 %
Prated
64.53 kW
58.46 kW
SCOP
5.35
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
64.53 kW
58.46 kW
COP Tj = +2°C
3.25
2.2
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
41.62 kW
36.56 kW
COP Tj = +7°C
4.96
3.2
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36 kW
33.33 kW
COP Tj = 12°C
6.5
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
64.53 kW
58.46 kW
COP Tj = Tbiv
3.25
2.2
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
64.53 kW
58.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.25
2.2
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
16214 kWh
19936 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
148 %
110 %
Prated
48.11 kW
57.26 kW
SCOP
3.77
2.83
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
28.89 kW
35.07 kW
COP Tj = -7°C
3.19
2.21
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.23 kW
27.2 kW
COP Tj = +2°C
5.04
3.93
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
32.98 kW
31.06 kW
COP Tj = +7°C
5.83
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.06 kW
34.62 kW
COP Tj = 12°C
6.6
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
39.25 kW
42.19 kW
COP Tj = Tbiv
2.08
1.79
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
31.92 kW
39.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.58
1.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
48.11 kW
57.26 kW
Annual energy consumption Qhe
31462 kWh
49913 kWh
Pdh Tj = -15°C (if TOL<-20°C)
39.25
42.19
COP Tj = -15°C (if TOL<-20°C)
2.08
1.79
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
125 %
Prated
53.4 kW
58.2 kW
SCOP
4.22
3.2
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
47.21 kW
47.66 kW
COP Tj = -7°C
2.70
1.96
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.76 kW
29.59 kW
COP Tj = +2°C
4.30
3.12
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.04 kW
39.10 kW
COP Tj = +7°C
5.39
4.42
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.87 kW
33.21 kW
COP Tj = 12°C
6.74
6.07
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
47.21 kW
49.09 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
44.78 kW
45.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.59 kW
12.98 kW
Annual energy consumption Qhe
25852 kWh
36978 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
78.37 kW
75.56 kW
El input
18.57 kW
29.87 kW
COP
4.22
2.53
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
211 %
154 %
Prated
64.53 kW
58.46 kW
SCOP
5.35
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
64.53 kW
58.46 kW
COP Tj = +2°C
3.25
2.2
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
41.62 kW
36.56 kW
COP Tj = +7°C
4.96
3.2
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36 kW
33.33 kW
COP Tj = 12°C
6.5
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
64.53 kW
58.46 kW
COP Tj = Tbiv
3.25
2.2
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
64.53 kW
58.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.25
2.2
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
16214 kWh
19936 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
148 %
110 %
Prated
48.11 kW
57.26 kW
SCOP
3.77
2.83
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
28.89 kW
35.07 kW
COP Tj = -7°C
3.19
2.21
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.23 kW
27.2 kW
COP Tj = +2°C
5.04
3.93
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
32.98 kW
31.06 kW
COP Tj = +7°C
5.83
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.06 kW
34.62 kW
COP Tj = 12°C
6.6
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
39.25 kW
42.19 kW
COP Tj = Tbiv
2.08
1.79
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
31.92 kW
39.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.58
1.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
48.11 kW
57.26 kW
Annual energy consumption Qhe
31462 kWh
49913 kWh
Pdh Tj = -15°C (if TOL<-20°C)
39.25
42.19
COP Tj = -15°C (if TOL<-20°C)
2.08
1.79
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
125 %
Prated
53.4 kW
58.2 kW
SCOP
4.22
3.2
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
47.21 kW
47.66 kW
COP Tj = -7°C
2.70
1.96
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.76 kW
29.59 kW
COP Tj = +2°C
4.30
3.12
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.04 kW
39.10 kW
COP Tj = +7°C
5.39
4.42
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.87 kW
33.21 kW
COP Tj = 12°C
6.74
6.07
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
47.21 kW
49.09 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
44.78 kW
45.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.59 kW
12.98 kW
Annual energy consumption Qhe
25852 kWh
36978 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
78.37 kW
75.56 kW
El input
18.57 kW
29.87 kW
COP
4.22
2.53
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
211 %
154 %
Prated
64.53 kW
58.46 kW
SCOP
5.35
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
64.53 kW
58.46 kW
COP Tj = +2°C
3.25
2.2
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
41.62 kW
36.56 kW
COP Tj = +7°C
4.96
3.2
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36 kW
33.33 kW
COP Tj = 12°C
6.5
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
64.53 kW
58.46 kW
COP Tj = Tbiv
3.25
2.2
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
64.53 kW
58.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.25
2.2
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
16214 kWh
19936 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
148 %
110 %
Prated
48.11 kW
57.26 kW
SCOP
3.77
2.83
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
28.89 kW
35.07 kW
COP Tj = -7°C
3.19
2.21
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.23 kW
27.2 kW
COP Tj = +2°C
5.04
3.93
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
32.98 kW
31.06 kW
COP Tj = +7°C
5.83
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.06 kW
34.62 kW
COP Tj = 12°C
6.6
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
39.25 kW
42.19 kW
COP Tj = Tbiv
2.08
1.79
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
31.92 kW
39.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.58
1.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
48.11 kW
57.26 kW
Annual energy consumption Qhe
31462 kWh
49913 kWh
Pdh Tj = -15°C (if TOL<-20°C)
39.25
42.19
COP Tj = -15°C (if TOL<-20°C)
2.08
1.79
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
125 %
Prated
53.4 kW
58.2 kW
SCOP
4.22
3.2
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
47.21 kW
47.66 kW
COP Tj = -7°C
2.70
1.96
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.76 kW
29.59 kW
COP Tj = +2°C
4.30
3.12
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.04 kW
39.10 kW
COP Tj = +7°C
5.39
4.42
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.87 kW
33.21 kW
COP Tj = 12°C
6.74
6.07
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
47.21 kW
49.09 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
44.78 kW
45.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.59 kW
12.98 kW
Annual energy consumption Qhe
25852 kWh
36978 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
87.4 kW
85.9 kW
El input
22.35 kW
35.06 kW
COP
3.91
2.45
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
154 %
Prated
71.2 kW
64.1 kW
SCOP
5.27
3.94
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
71.2 kW
64.1 kW
COP Tj = +2°C
3.1
2.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
45.2 kW
40.3 kW
COP Tj = +7°C
4.85
3.32
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36.03 kW
33.33 kW
COP Tj = 12°C
6.43
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
71.2 kW
64.1 kW
COP Tj = Tbiv
3.1
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
71.2 kW
64.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.1
2.15
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
18041 kWh
21759 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
145 %
109 %
Prated
54.28 kW
62.74 kW
SCOP
3.69
2.79
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
31.73 kW
37.94 kW
COP Tj = -7°C
3.04
2.18
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.33 kW
27.18 kW
COP Tj = +2°C
4.97
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
33.14 kW
31.06 kW
COP Tj = +7°C
5.76
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.2 kW
34.62 kW
COP Tj = 12°C
6.49
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
44.28 kW
46.23 kW
COP Tj = Tbiv
2.02
1.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
35.94 kW
42.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.55
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
54.28 kW
62.74 kW
Annual energy consumption Qhe
36277 kWh
55405 kWh
Pdh Tj = -15°C (if TOL<-20°C)
44.28
42.94
COP Tj = -15°C (if TOL<-20°C)
2.02
1.52
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
164 %
123 %
Prated
58.9 kW
62.63 kW
SCOP
4.19
3.16
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
52.08 kW
51.45 kW
COP Tj = -7°C
2.65
1.92
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.80 kW
31.11 kW
COP Tj = +2°C
4.25
3.09
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.08 kW
40.31 kW
COP Tj = +7°C
5.32
4.34
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.91 kW
34.24 kW
COP Tj = 12°C
6.65
5.96
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
52.08 kW
53.00 kW
COP Tj = Tbiv
2.65
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.14 kW
48.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.73 kW
14.01 kW
Annual energy consumption Qhe
28792 kWh
40478 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
87.4 kW
85.9 kW
El input
22.35 kW
35.06 kW
COP
3.91
2.45
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
154 %
Prated
71.2 kW
64.1 kW
SCOP
5.27
3.94
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
71.2 kW
64.1 kW
COP Tj = +2°C
3.1
2.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
45.2 kW
40.3 kW
COP Tj = +7°C
4.85
3.32
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36.03 kW
33.33 kW
COP Tj = 12°C
6.43
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
71.2 kW
64.1 kW
COP Tj = Tbiv
3.1
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
71.2 kW
64.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.1
2.15
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
18041 kWh
21759 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
145 %
109 %
Prated
54.28 kW
62.74 kW
SCOP
3.69
2.79
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
31.73 kW
37.94 kW
COP Tj = -7°C
3.04
2.18
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.33 kW
27.18 kW
COP Tj = +2°C
4.97
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
33.14 kW
31.06 kW
COP Tj = +7°C
5.76
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.2 kW
34.62 kW
COP Tj = 12°C
6.49
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
44.28 kW
46.23 kW
COP Tj = Tbiv
2.02
1.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
35.94 kW
42.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.55
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
54.28 kW
62.74 kW
Annual energy consumption Qhe
36277 kWh
55405 kWh
Pdh Tj = -15°C (if TOL<-20°C)
44.28
42.94
COP Tj = -15°C (if TOL<-20°C)
2.02
1.52
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
164 %
123 %
Prated
58.9 kW
62.63 kW
SCOP
4.19
3.16
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
52.08 kW
51.45 kW
COP Tj = -7°C
2.65
1.92
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.80 kW
31.11 kW
COP Tj = +2°C
4.25
3.09
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.08 kW
40.31 kW
COP Tj = +7°C
5.32
4.34
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.91 kW
34.24 kW
COP Tj = 12°C
6.65
5.96
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
52.08 kW
53.00 kW
COP Tj = Tbiv
2.65
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.14 kW
48.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.73 kW
14.01 kW
Annual energy consumption Qhe
28792 kWh
40478 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
87.4 kW
85.9 kW
El input
22.35 kW
35.06 kW
COP
3.91
2.45
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
154 %
Prated
71.2 kW
64.1 kW
SCOP
5.27
3.94
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
71.2 kW
64.1 kW
COP Tj = +2°C
3.1
2.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
45.2 kW
40.3 kW
COP Tj = +7°C
4.85
3.32
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36.03 kW
33.33 kW
COP Tj = 12°C
6.43
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
71.2 kW
64.1 kW
COP Tj = Tbiv
3.1
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
71.2 kW
64.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.1
2.15
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
18041 kWh
21759 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
145 %
109 %
Prated
54.28 kW
62.74 kW
SCOP
3.69
2.79
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
31.73 kW
37.94 kW
COP Tj = -7°C
3.04
2.18
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.33 kW
27.18 kW
COP Tj = +2°C
4.97
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
33.14 kW
31.06 kW
COP Tj = +7°C
5.76
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.2 kW
34.62 kW
COP Tj = 12°C
6.49
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
44.28 kW
46.23 kW
COP Tj = Tbiv
2.02
1.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
35.94 kW
42.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.55
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
54.28 kW
62.74 kW
Annual energy consumption Qhe
36277 kWh
55405 kWh
Pdh Tj = -15°C (if TOL<-20°C)
44.28
42.94
COP Tj = -15°C (if TOL<-20°C)
2.02
1.52
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
164 %
123 %
Prated
58.9 kW
62.63 kW
SCOP
4.19
3.16
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
52.08 kW
51.45 kW
COP Tj = -7°C
2.65
1.92
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.80 kW
31.11 kW
COP Tj = +2°C
4.25
3.09
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.08 kW
40.31 kW
COP Tj = +7°C
5.32
4.34
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.91 kW
34.24 kW
COP Tj = 12°C
6.65
5.96
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
52.08 kW
53.00 kW
COP Tj = Tbiv
2.65
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.14 kW
48.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.73 kW
14.01 kW
Annual energy consumption Qhe
28792 kWh
40478 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
87.4 kW
85.9 kW
El input
22.35 kW
35.06 kW
COP
3.91
2.45
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
154 %
Prated
71.2 kW
64.1 kW
SCOP
5.27
3.94
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
71.2 kW
64.1 kW
COP Tj = +2°C
3.1
2.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
45.2 kW
40.3 kW
COP Tj = +7°C
4.85
3.32
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
36.03 kW
33.33 kW
COP Tj = 12°C
6.43
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
71.2 kW
64.1 kW
COP Tj = Tbiv
3.1
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
71.2 kW
64.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.1
2.15
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
18041 kWh
21759 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
145 %
109 %
Prated
54.28 kW
62.74 kW
SCOP
3.69
2.79
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
31.73 kW
37.94 kW
COP Tj = -7°C
3.04
2.18
Cdh Tj = -7 °C
0.9
0.96
Pdh Tj = +2°C
29.33 kW
27.18 kW
COP Tj = +2°C
4.97
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
33.14 kW
31.06 kW
COP Tj = +7°C
5.76
4.99
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
36.2 kW
34.62 kW
COP Tj = 12°C
6.49
6.11
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
44.28 kW
46.23 kW
COP Tj = Tbiv
2.02
1.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
35.94 kW
42.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.55
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
54.28 kW
62.74 kW
Annual energy consumption Qhe
36277 kWh
55405 kWh
Pdh Tj = -15°C (if TOL<-20°C)
44.28
42.94
COP Tj = -15°C (if TOL<-20°C)
2.02
1.52
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
164 %
123 %
Prated
58.9 kW
62.63 kW
SCOP
4.19
3.16
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
52.08 kW
51.45 kW
COP Tj = -7°C
2.65
1.92
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
30.80 kW
31.11 kW
COP Tj = +2°C
4.25
3.09
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
35.08 kW
40.31 kW
COP Tj = +7°C
5.32
4.34
Cdh Tj = +7 °C
0.96
0.97
Pdh Tj = 12°C
40.91 kW
34.24 kW
COP Tj = 12°C
6.65
5.96
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
52.08 kW
53.00 kW
COP Tj = Tbiv
2.65
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.14 kW
48.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.73 kW
14.01 kW
Annual energy consumption Qhe
28792 kWh
40478 kWh