1,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.84 kW
8.22 kW
El input
1.69 kW
3.05 kW
COP
4.65
2.69
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
127 %
Prated
7.00 kW
7.19 kW
SCOP
4.46
3.25
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
6.19 kW
6.36 kW
COP Tj = -7°C
2.98
2.39
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.98 kW
4.01 kW
COP Tj = +2°C
4.50
3.28
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.19 kW
4.17 kW
COP Tj = +7°C
5.81
4.06
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.65 kW
4.95 kW
COP Tj = 12°C
7.79
5.62
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.19 kW
6.36 kW
COP Tj = Tbiv
2.98
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.74 kW
5.57 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
50 °C
50 °C
Poff
6 W
6 W
PTO
7 W
7 W
PSB
6 W
6 W
PCK
40 W
40 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.25 kW
1.62 kW
Annual energy consumption Qhe
3244 kWh
4566 kWh