Login

Subtype

Sherpa Aquadue Tower S3 E 12 - 14 - 16 - 12T - 14T - 16T

Certificate Holder
Olimpia Splendid S.p.A.
Via Industriale, 1/3
25060 Cellatica (BS)
Italy
Registration number
ICIM-PDC-000190
Certification Body
ICIM S.p.A.
Subtype title
Sherpa Aquadue Tower S3 E 12 - 14 - 16 - 12T - 14T - 16T
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,840 kg

Certification Date
23.01.2023
Testing basis
Heat Pump KEYMARK V11
Generate PDF Export model CSV Download certificate
  • Number of models 6

Models

SHERPA AQUADUE TOWER S3 E 12
Configure model
Model name
SHERPA AQUADUE TOWER S3 E 12
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.10 kW

12.00 kW

El input

2.44 kW

3.87 kW

COP

4.95

3.10

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

4.22 kW

3.00 kW

Cooling capacity

11.60

12.00

EER

2.75

4.00

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

11.30 kW

11.80 kW

SEER

4.89

7.10

Pdc Tj = 35°C

11.31 kW

11.77 kW

EER Tj = 35°C

2.61

3.87

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

8.76 kW

9.21 kW

EER Tj = 30°C

3.93

5.50

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.81 kW

5.74 kW

EER Tj = 25°C

5.73

8.66

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

2.63 kW

3.33 kW

EER Tj = 20°C

6.75

10.07

Cdc Tj = 20 °C

0.900

0.900

Poff

14 W

14 W

PTO

10 W

10 W

PSB

14 W

14 W

PCK

0 W

0 W

Annual energy consumption Qce

1387 kWh

997 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

135 %

Prated

12.00 kW

11.60 kW

SCOP

4.81

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.61 kW

10.24 kW

COP Tj = -7°C

2.88

2.01

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.69 kW

6.52 kW

COP Tj = +2°C

4.65

3.44

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.44 kW

4.36 kW

COP Tj = +7°C

6.62

4.59

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.74 kW

3.29 kW

COP Tj = 12°C

8.47

6.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.61 kW

10.27 kW

COP Tj = Tbiv

2.88

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.74 kW

9.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.77

1.79

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.26 kW

2.50 kW

Annual energy consumption Qhe

5156 kWh

6927 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

81 %

COP

1.88

Heating up time

01:07 h:min

Standby power input

76.0 W

Reference hot water temperature

43.1 °C

Mixed water at 40°C

156 l

SHERPA AQUADUE TOWER SE E 14
Configure model
Model name
SHERPA AQUADUE TOWER SE E 14
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.50 kW

13.80 kW

El input

3.09 kW

4.60 kW

COP

4.70

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

4.98 kW

3.50 kW

Cooling capacity

12.70

13.00

EER

2.55

3.70

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

12.20 kW

13.30 kW

SEER

4.86

6.90

Pdc Tj = 35°C

12.19 kW

13.30 kW

EER Tj = 35°C

2.46

3.46

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

9.41 kW

10.20 kW

EER Tj = 30°C

3.85

5.26

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

6.16 kW

6.57 kW

EER Tj = 25°C

5.80

8.45

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

2.63 kW

3.33 kW

EER Tj = 20°C

6.74

10.07

Cdc Tj = 20 °C

0.900

0.900

Poff

14 W

14 W

PTO

10 W

10 W

PSB

14 W

14 W

PCK

0 W

0 W

Annual energy consumption Qce

1505 kWh

1157 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

186 %

135 %

Prated

13.70 kW

12.10 kW

SCOP

4.72

3.47

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.14 kW

10.68 kW

COP Tj = -7°C

2.79

2.01

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.94 kW

6.86 kW

COP Tj = +2°C

4.52

3.43

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.20 kW

4.63 kW

COP Tj = +7°C

6.68

4.66

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.75 kW

3.31 kW

COP Tj = 12°C

8.52

6.13

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.14 kW

10.68 kW

COP Tj = Tbiv

2.79

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.47 kW

9.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.59

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.23 kW

2.91 kW

Annual energy consumption Qhe

6012 kWh

7202 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

81 %

COP

1.88

Heating up time

01:07 h:min

Standby power input

76.0 W

Reference hot water temperature

43.1 °C

Mixed water at 40°C

156 l

SHERPA AQUADUE TOWER S3 E 16
Configure model
Model name
SHERPA AQUADUE TOWER S3 E 16
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.56 kW

5.52 kW

COP

4.50

2.90

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

5.71 kW

3.74 kW

Cooling capacity

14.00

13.50

EER

2.45

3.61

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

14.30 kW

15.40 kW

SEER

4.69

6.75

Pdc Tj = 35°C

14.31 kW

15.40 kW

EER Tj = 35°C

2.47

3.50

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

10.68 kW

11.42 kW

EER Tj = 30°C

3.63

5.14

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

6.76 kW

7.27 kW

EER Tj = 25°C

5.27

7.83

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.41 kW

3.40 kW

EER Tj = 20°C

7.29

10.35

Cdc Tj = 20 °C

0.900

0.900

Poff

14 W

14 W

PTO

10 W

10 W

PSB

14 W

14 W

PCK

0 W

0 W

Annual energy consumption Qce

1830 kWh

1369 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

133 %

Prated

15.20 kW

13.00 kW

SCOP

4.62

3.41

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.45 kW

11.52 kW

COP Tj = -7°C

2.72

1.99

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.56 kW

7.18 kW

COP Tj = +2°C

4.41

3.34

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.70 kW

4.67 kW

COP Tj = +7°C

6.56

4.61

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.78 kW

3.32 kW

COP Tj = 12°C

8.51

6.07

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.45 kW

11.52 kW

COP Tj = Tbiv

2.72

1.99

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.52 kW

10.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.68 kW

2.67 kW

Annual energy consumption Qhe

6804 kWh

7895 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

81 %

COP

1.88

Heating up time

01:07 h:min

Standby power input

76.0 W

Reference hot water temperature

43.1 °C

Mixed water at 40°C

156 l

SHERPA AQUADUE TOWER S3 E 12T
Configure model
Model name
SHERPA AQUADUE TOWER S3 E 12T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.10 kW

12.00 kW

El input

2.44 kW

3.87 kW

COP

4.95

3.10

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

4.22 kW

3.00 kW

Cooling capacity

11.60

12.00

EER

2.75

4.00

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

11.30 kW

11.80 kW

SEER

4.86

7.04

Pdc Tj = 35°C

11.31 kW

11.77 kW

EER Tj = 35°C

2.61

3.87

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

8.76 kW

9.21 kW

EER Tj = 30°C

3.93

5.50

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.81 kW

5.74 kW

EER Tj = 25°C

5.73

8.66

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

2.63 kW

3.33 kW

EER Tj = 20°C

6.75

10.07

Cdc Tj = 20 °C

0.900

0.900

Poff

20 W

20 W

PTO

30 W

30 W

PSB

20 W

20 W

PCK

0 W

0 W

Annual energy consumption Qce

1395 kWh

1006 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

135 %

Prated

12.00 kW

11.60 kW

SCOP

4.81

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.61 kW

10.24 kW

COP Tj = -7°C

2.88

2.01

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.69 kW

6.52 kW

COP Tj = +2°C

4.65

3.44

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.44 kW

4.36 kW

COP Tj = +7°C

6.62

4.59

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.74 kW

3.29 kW

COP Tj = 12°C

8.47

6.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.61 kW

10.27 kW

COP Tj = Tbiv

2.88

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.74 kW

9.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.77

1.79

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

20 W

20 W

PTO

30 W

30 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.26 kW

2.50 kW

Annual energy consumption Qhe

5153 kWh

6928 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

81 %

COP

1.88

Heating up time

01:07 h:min

Standby power input

76.0 W

Reference hot water temperature

43.1 °C

Mixed water at 40°C

156 l

SHERPA AQUADUE TOWER SE E 14T
Configure model
Model name
SHERPA AQUADUE TOWER SE E 14T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.50 kW

13.80 kW

El input

3.09 kW

4.59 kW

COP

4.70

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

4.98 kW

3.50 kW

Cooling capacity

12.70

13.00

EER

2.55

3.70

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

12.20 kW

13.30 kW

SEER

4.83

6.85

Pdc Tj = 35°C

12.19 kW

13.30 kW

EER Tj = 35°C

2.46

3.47

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

9.41 kW

10.20 kW

EER Tj = 30°C

3.85

5.26

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

6.16 kW

6.57 kW

EER Tj = 25°C

5.80

8.45

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

2.63 kW

3.33 kW

EER Tj = 20°C

6.74

10.07

Cdc Tj = 20 °C

0.900

0.900

Poff

20 W

20 W

PTO

30 W

30 W

PSB

20 W

20 W

PCK

0 W

0 W

Annual energy consumption Qce

1515 kWh

1165 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

135 %

Prated

13.70 kW

12.10 kW

SCOP

4.72

3.47

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.14 kW

10.68 kW

COP Tj = -7°C

2.79

2.01

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.94 kW

6.86 kW

COP Tj = +2°C

4.52

3.43

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.20 kW

4.63 kW

COP Tj = +7°C

6.68

4.66

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.75 kW

3.31 kW

COP Tj = 12°C

8.52

6.13

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.14 kW

10.68 kW

COP Tj = Tbiv

2.79

2.01

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.47 kW

9.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.59

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

20 W

20 W

PTO

30 W

30 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.23 kW

2.91 kW

Annual energy consumption Qhe

6013 kWh

7203 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

81 %

COP

1.88

Heating up time

01:07 h:min

Standby power input

76.0 W

Reference hot water temperature

43.1 °C

Mixed water at 40°C

156 l

SHERPA AQUADUE TOWER 16T
Configure model
Model name
SHERPA AQUADUE TOWER 16T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.56 kW

5.52 kW

COP

4.50

2.90

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

5.71 kW

3.74 kW

Cooling capacity

13.99

13.50

EER

2.45

3.61

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

14.30 kW

15.40 kW

SEER

4.67

6.71

Pdc Tj = 35°C

14.31 kW

15.40 kW

EER Tj = 35°C

2.47

3.50

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

10.68 kW

11.42 kW

EER Tj = 30°C

3.63

5.14

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

6.76 kW

7.27 kW

EER Tj = 25°C

5.27

7.83

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.41 kW

3.40 kW

EER Tj = 20°C

7.29

10.35

Cdc Tj = 20 °C

0.900

0.900

Poff

20 W

20 W

PTO

10 W

10 W

PSB

20 W

20 W

PCK

0 W

0 W

Annual energy consumption Qce

1838 kWh

1377 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

133 %

Prated

15.20 kW

13.00 kW

SCOP

4.62

3.41

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.45 kW

11.52 kW

COP Tj = -7°C

2.72

1.99

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.56 kW

7.18 kW

COP Tj = +2°C

4.41

3.34

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.70 kW

4.67 kW

COP Tj = +7°C

6.56

4.61

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.78 kW

3.32 kW

COP Tj = 12°C

8.51

6.07

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.45 kW

11.52 kW

COP Tj = Tbiv

2.72

1.99

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.52 kW

10.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

20 W

20 W

PTO

30 W

30 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.68 kW

2.67 kW

Annual energy consumption Qhe

6805 kWh

7896 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

81 %

COP

1.88

Heating up time

01:07 h:min

Standby power input

76.0 W

Reference hot water temperature

43.1 °C

Mixed water at 40°C

156 l