Login

Subtype

AHP60-32

Certificate Holder
GUILLOT INDUSTRIES SAS - Groupe ATLANTIC
1, Route de Fleurville
01190 Ponte De Vaux
France
Registration number
ICIM-PDC-000163-00
Certification Body
ICIM S.p.A.
Subtype title
AHP60-32
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

5,100 kg

Certification Date
24.06.2022
Testing basis
V9
Generate PDF Export model CSV
  • Number of models 1

Models

EFFIPAC AHP60-32 (brand ATLANTIC) ; TYNEHAM AHP60-32 (brand HAMWORTHY) ; ECOMOD AHP60-32 (brand IDEAL) ; HEATPAC MAX AHP60-32 (brand ACV)
Configure model
Model name
EFFIPAC AHP60-32 (brand ATLANTIC) ; TYNEHAM AHP60-32 (brand HAMWORTHY) ; ECOMOD AHP60-32 (brand IDEAL) ; HEATPAC MAX AHP60-32 (brand ACV)
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

32.10 kW

31.80 kW

El input

7.84 kW

12.10 kW

COP

4.09

2.64

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

8.65 kW

Cooling capacity

26.00

EER

3.01

EN 14825

+7°C/+12°C

Pdesignc

26.00 kW

SEER

4.81

Pdc Tj = 35°C

26.00 kW

EER Tj = 35°C

3.01

Pdc Tj = 30°C

19.10 kW

EER Tj = 30°C

4.15

Cdc Tj = 30 °C

1.000

Pdc Tj = 25°C

12.27 kW

EER Tj = 25°C

5.35

Cdc Tj = 25 °C

1.000

Pdc Tj = 20°C

12.56 kW

EER Tj = 20°C

6.63

Cdc Tj = 20 °C

0.900

Poff

22 W

PTO

0 W

PSB

28 W

PCK

0 W

Annual energy consumption Qce

3241 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

158 %

122 %

Prated

24.00 kW

25.00 kW

SCOP

4.02

3.14

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-10 °C

Pdh Tj = -7°C

21.30 kW

21.70 kW

COP Tj = -7°C

2.57

1.90

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

13.00 kW

13.30 kW

COP Tj = +2°C

3.94

3.09

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

11.60 kW

11.90 kW

COP Tj = +7°C

5.03

3.96

Cdh Tj = +7 °C

0.993

0.995

Pdh Tj = 12°C

13.50 kW

14.00 kW

COP Tj = 12°C

6.96

5.51

Cdh Tj = +12 °C

0.992

0.994

Pdh Tj = Tbiv

21.30 kW

21.70 kW

COP Tj = Tbiv

2.57

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.80 kW

19.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.29

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

5.20 kW

5.50 kW

Annual energy consumption Qhe

12369 kWh

16150 kWh