1,150 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.82 kW
7.91 kW
El input
2.05 kW
2.87 kW
COP
4.30
2.76
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
129 %
Prated
8.49 kW
7.45 kW
SCOP
4.53
3.29
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.51 kW
6.59 kW
COP Tj = -7°C
2.99
1.93
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.60 kW
4.13 kW
COP Tj = +2°C
4.44
3.35
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.59 kW
4.32 kW
COP Tj = +7°C
6.27
4.64
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.20 kW
5.14 kW
COP Tj = 12°C
8.10
6.24
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.51 kW
6.59 kW
COP Tj = Tbiv
2.99
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.90 kW
6.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
58 °C
58 °C
Poff
8 W
8 W
PTO
32 W
32 W
PSB
8 W
8 W
PCK
41 W
41 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.59 kW
1.22 kW
Annual energy consumption Qhe
3874 kWh
4675 kWh