1,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.2 kW
12 kW
El input
2.49 kW
4 kW
COP
4.9
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
262.3 %
179 %
Prated
12.1 kW
12 kW
SCOP
6.63
4.55
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.1 kW
12 kW
COP Tj = +2°C
3.53
2.39
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
7.78 kW
7.73 kW
COP Tj = +7°C
5.82
3.86
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.64 kW
3.59 kW
COP Tj = 12°C
8.31
5.88
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
7.78 kW
7.73 kW
COP Tj = Tbiv
5.82
3.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.1 kW
12 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.53
2.39
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2437 kWh
3524 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168.8 %
126 %
Prated
12.5 kW
11.3 kW
SCOP
4.3
3.23
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.08 kW
7.09 kW
COP Tj = -7°C
3.64
2.75
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
4.93 kW
4.44 kW
COP Tj = +2°C
5.34
3.88
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
3.17 kW
3 kW
COP Tj = +7°C
5.28
4.88
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.69 kW
3.6 kW
COP Tj = 12°C
9.34
6.61
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.17 kW
9.21 kW
COP Tj = Tbiv
2.66
1.92
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.72 kW
7 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.38
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.78 kW
4.3 kW
Annual energy consumption Qhe
7153 kWh
8628 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.17
9.21
COP Tj = -15°C (if TOL<-20°C)
2.66
1.92
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200.1 %
141.6 %
Prated
12.3 kW
12.5 kW
SCOP
5.08
3.62
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.85 kW
11.06 kW
COP Tj = -7°C
3.11
2.15
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
6.79 kW
6.91 kW
COP Tj = +2°C
4.86
3.59
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.79 kW
4.64 kW
COP Tj = +7°C
6.98
5.07
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.73 kW
2.15 kW
COP Tj = 12°C
9.02
4.52
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.85 kW
11.06 kW
COP Tj = Tbiv
3.11
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.3 kW
10.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.8
1.98
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.53 kW
Annual energy consumption Qhe
5004 kWh
7148 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.10 kW
14.00 kW
El input
3.00 kW
4.75 kW
COP
4.70
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
260.5 %
184.6 %
Prated
13.20 kW
14.20 kW
SCOP
6.59
4.69
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.94 kW
13.01 kW
COP Tj = +2°C
3.51
2.37
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
8.51 kW
9.12 kW
COP Tj = +7°C
5.72
3.95
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.96 kW
4.26 kW
COP Tj = 12°C
8.51
6.37
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
8.51 kW
9.12 kW
COP Tj = Tbiv
5.72
3.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.94 kW
13.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.51
2.37
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.26 kW
1.18 kW
Annual energy consumption Qhe
2684 kWh
4040 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171.3 %
126.6 %
Prated
14.31 kW
12.49 kW
SCOP
4.36
3.24
Tbiv
-15.00 °C
-15.00 °C
TOL
-22.00 °C
-22.00 °C
Pdh Tj = -7°C
8.74 kW
7.80 kW
COP Tj = -7°C
3.59
2.77
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.52 kW
4.64 kW
COP Tj = +2°C
5.35
3.91
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.70 kW
3.00 kW
COP Tj = +7°C
7.06
4.88
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.69 kW
3.61 kW
COP Tj = 12°C
9.34
6.61
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
11.67 kW
10.19 kW
COP Tj = Tbiv
2.58
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.14 kW
7.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.02
1.35
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.17 kW
5.21 kW
Annual energy consumption Qhe
8095 kWh
9496 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.67
10.19
COP Tj = -15°C (if TOL<-20°C)
2.58
1.91
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192.5 %
141.8 %
Prated
14.15 kW
14.15 kW
SCOP
4.89
3.62
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.52 kW
12.52 kW
COP Tj = -7°C
2.97
2.20
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
7.98 kW
7.71 kW
COP Tj = +2°C
4.56
3.58
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.04 kW
5.07 kW
COP Tj = +7°C
7.01
5.06
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.73 kW
2.15 kW
COP Tj = 12°C
9.02
4.52
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.52 kW
12.52 kW
COP Tj = Tbiv
2.97
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.41 kW
11.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
1.96
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.75 kW
2.65 kW
Annual energy consumption Qhe
5984 kWh
8079 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.56 kW
5.61 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
255.4 %
184 %
Prated
14.20 kW
14.50 kW
SCOP
6.46
4.68
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
14.20 kW
13.62 kW
COP Tj = +2°C
3.22
2.35
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
9.15 kW
9.35 kW
COP Tj = +7°C
5.41
3.94
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
4.24 kW
4.26 kW
COP Tj = 12°C
8.56
6.37
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
9.15 kW
9.35 kW
COP Tj = Tbiv
5.41
3.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.20 kW
13.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.22
2.35
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.91 kW
Annual energy consumption Qhe
2937 kWh
4154 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170.9 %
124.3 %
Prated
15.10 kW
13.52 kW
SCOP
4.35
3.18
Tbiv
-15.00 °C
-15.00 °C
TOL
-22.00 °C
-22.00 °C
Pdh Tj = -7°C
9.26 kW
8.43 kW
COP Tj = -7°C
3.59
2.77
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.76 kW
5.20 kW
COP Tj = +2°C
5.35
3.74
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.76 kW
3.53 kW
COP Tj = +7°C
7.04
5.19
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.72 kW
3.61 kW
COP Tj = 12°C
8.78
6.61
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.30 kW
11.03 kW
COP Tj = Tbiv
2.58
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.43 kW
7.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.00
1.30
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.67 kW
6.00 kW
Annual energy consumption Qhe
8546 kWh
10473 kWh
Pdh Tj = -15°C (if TOL<-20°C)
12.30
11.03
COP Tj = -15°C (if TOL<-20°C)
2.58
1.85
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190.5 %
140.6 %
Prated
15.23 kW
14.70 kW
SCOP
4.84
3.59
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.49 kW
13.03 kW
COP Tj = -7°C
2.87
2.16
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.59 kW
8.50 kW
COP Tj = +2°C
4.53
3.55
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.55 kW
5.27 kW
COP Tj = +7°C
7.01
5.05
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.73 kW
2.15 kW
COP Tj = 12°C
9.02
4.52
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
13.49 kW
13.03 kW
COP Tj = Tbiv
2.87
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.05 kW
12.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.94
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.18 kW
2.63 kW
Annual energy consumption Qhe
6510 kWh
8471 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.2 kW
12 kW
El input
2.49 kW
4 kW
COP
4.9
3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
262.5 %
179 %
Prated
12.1 kW
12 kW
SCOP
6.64
4.55
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.1 kW
12 kW
COP Tj = +2°C
3.53
2.39
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
7.78 kW
7.73 kW
COP Tj = +7°C
5.82
3.86
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.64 kW
3.59 kW
COP Tj = 12°C
8.31
5.88
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
7.78 kW
7.73 kW
COP Tj = Tbiv
5.82
3.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.1 kW
12 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.53
2.39
WTOL
65 °C
65 °C
Poff
6 W
6 W
PTO
18 W
18 W
PSB
6 W
6 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2435 kWh
3523 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168.8 %
126 %
Prated
12.5 kW
11.3 kW
SCOP
4.3
3.23
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.08 kW
7.09 kW
COP Tj = -7°C
3.64
2.75
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
4.93 kW
4.44 kW
COP Tj = +2°C
5.34
3.88
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
3.17 kW
3 kW
COP Tj = +7°C
5.28
4.88
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.69 kW
3.6 kW
COP Tj = 12°C
9.34
6.61
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.17 kW
9.21 kW
COP Tj = Tbiv
2.66
1.92
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.72 kW
7 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.38
WTOL
65 °C
65 °C
Poff
6 W
6 W
PTO
18 W
18 W
PSB
6 W
6 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.78 kW
4.3 kW
Annual energy consumption Qhe
7153 kWh
8628 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.17
9.21
COP Tj = -15°C (if TOL<-20°C)
2.66
1.92
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200.2 %
141.6 %
Prated
12.3 kW
12.5 kW
SCOP
5.08
3.62
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.85 kW
11.06 kW
COP Tj = -7°C
3.11
2.15
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
6.79 kW
6.91 kW
COP Tj = +2°C
4.86
3.59
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.79 kW
4.64 kW
COP Tj = +7°C
6.98
5.07
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.73 kW
2.15 kW
COP Tj = 12°C
9.02
4.52
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.85 kW
11.06 kW
COP Tj = Tbiv
3.11
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.3 kW
10.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.8
1.98
WTOL
65 °C
65 °C
Poff
6 W
6 W
PTO
18 W
18 W
PSB
6 W
6 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.53 kW
Annual energy consumption Qhe
5003 kWh
7148 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.10 kW
14.00 kW
El input
3.00 kW
4.75 kW
COP
4.70
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
260.6 %
184.6 %
Prated
13.20 kW
14.20 kW
SCOP
6.59
4.69
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.94 kW
13.01 kW
COP Tj = +2°C
3.51
2.37
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
8.51 kW
9.12 kW
COP Tj = +7°C
5.72
3.95
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.96 kW
4.26 kW
COP Tj = 12°C
8.51
6.37
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
8.51 kW
9.12 kW
COP Tj = Tbiv
5.72
3.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.94 kW
13.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.51
2.37
WTOL
65.00 °C
65.00 °C
Poff
6.00 W
6.00 W
PTO
18.00 W
18.00 W
PSB
6.00 W
6.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.26 kW
1.18 kW
Annual energy consumption Qhe
2683 kWh
4039 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171.3 %
126.6 %
Prated
14.30 kW
12.50 kW
SCOP
4.36
3.24
Tbiv
-15.00 °C
-15.00 °C
TOL
-22.00 °C
-22.00 °C
Pdh Tj = -7°C
8.74 kW
7.80 kW
COP Tj = -7°C
3.59
2.77
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.52 kW
4.64 kW
COP Tj = +2°C
5.35
3.91
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.70 kW
3.00 kW
COP Tj = +7°C
7.06
4.88
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.69 kW
3.61 kW
COP Tj = 12°C
9.34
6.61
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
11.67 kW
10.19 kW
COP Tj = Tbiv
2.58
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.14 kW
7.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.02
1.35
WTOL
65.00 °C
65.00 °C
Poff
6.00 W
6.00 W
PTO
18.00 W
18.00 W
PSB
6.00 W
6.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.16 kW
5.22 kW
Annual energy consumption Qhe
8095 kWh
9496 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.67
10.19
COP Tj = -15°C (if TOL<-20°C)
2.58
1.91
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192.5 %
141.8 %
Prated
14.20 kW
14.20 kW
SCOP
4.89
3.62
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.52 kW
12.52 kW
COP Tj = -7°C
2.97
2.20
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
7.98 kW
7.71 kW
COP Tj = +2°C
4.56
3.58
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.04 kW
5.07 kW
COP Tj = +7°C
7.01
5.06
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.73 kW
2.15 kW
COP Tj = 12°C
9.02
4.52
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.52 kW
12.52 kW
COP Tj = Tbiv
2.97
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.41 kW
11.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
1.96
WTOL
65.00 °C
65.00 °C
Poff
6.00 W
6.00 W
PTO
18.00 W
18.00 W
PSB
6.00 W
6.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.80 kW
2.69 kW
Annual energy consumption Qhe
5984 kWh
8079 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.56 kW
5.61 kW
COP
4.50
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
255.5 %
184 %
Prated
14.20 kW
14.50 kW
SCOP
6.46
4.68
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
14.20 kW
13.62 kW
COP Tj = +2°C
3.22
2.35
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
9.15 kW
9.35 kW
COP Tj = +7°C
5.41
3.94
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
4.24 kW
4.26 kW
COP Tj = 12°C
8.56
6.37
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
9.15 kW
9.35 kW
COP Tj = Tbiv
5.41
3.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.20 kW
13.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.22
2.35
WTOL
65.00 °C
65.00 °C
Poff
6.00 W
13.00 W
PTO
18.00 W
20.00 W
PSB
6.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.91 kW
Annual energy consumption Qhe
2935 kWh
4153 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170.9 %
124.3 %
Prated
15.10 kW
13.50 kW
SCOP
4.35
3.18
Tbiv
-15.00 °C
-15.00 °C
TOL
-22.00 °C
-22.00 °C
Pdh Tj = -7°C
9.26 kW
8.43 kW
COP Tj = -7°C
3.59
2.77
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
5.76 kW
5.20 kW
COP Tj = +2°C
5.35
3.74
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
3.76 kW
3.53 kW
COP Tj = +7°C
7.04
5.19
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.72 kW
3.61 kW
COP Tj = 12°C
8.78
6.61
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.30 kW
11.03 kW
COP Tj = Tbiv
2.58
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.43 kW
7.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.00
1.30
WTOL
65.00 °C
65.00 °C
Poff
6.00 W
6.00 W
PTO
18.00 W
18.00 W
PSB
6.00 W
6.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.67 kW
5.98 kW
Annual energy consumption Qhe
8546 kWh
10473 kWh
Pdh Tj = -15°C (if TOL<-20°C)
12.30
11.03
COP Tj = -15°C (if TOL<-20°C)
2.58
1.85
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190.5 %
140.7 %
Prated
15.20 kW
14.70 kW
SCOP
4.84
3.59
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.49 kW
13.03 kW
COP Tj = -7°C
2.87
2.16
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.59 kW
8.50 kW
COP Tj = +2°C
4.53
3.55
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.55 kW
5.27 kW
COP Tj = +7°C
7.01
5.05
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.73 kW
2.15 kW
COP Tj = 12°C
9.02
4.52
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
13.49 kW
13.03 kW
COP Tj = Tbiv
2.87
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.05 kW
12.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.94
WTOL
65.00 °C
65.00 °C
Poff
6.00 W
6.00 W
PTO
18.00 W
18.00 W
PSB
6.00 W
6.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.15 kW
2.63 kW
Annual energy consumption Qhe
6509 kWh
8460 kWh