1,250 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.5 kW
6.3 kW
El input
1.23 kW
1.97 kW
COP
5.3
3.2
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
268.2 %
170.9 %
Prated
6.24 kW
6.17 kW
SCOP
6.78
4.35
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.69 kW
6.17 kW
COP Tj = +2°C
4.31
2.77
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.01 kW
3.97 kW
COP Tj = +7°C
6.39
3.9
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
2.07 kW
2.06 kW
COP Tj = 12°C
8.71
5.28
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
4.01 kW
3.97 kW
COP Tj = Tbiv
6.39
3.9
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.69 kW
6.17 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.31
2.77
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.55 kW
0 kW
Annual energy consumption Qhe
1229 kWh
1895 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
173.4 %
113.12 %
Prated
6.13 kW
5.22 kW
SCOP
4.41
2.9
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.11 kW
3.21 kW
COP Tj = -7°C
3.76
2.6
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
2.38 kW
2.03 kW
COP Tj = +2°C
5.33
3.18
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
1.66 kW
1.56 kW
COP Tj = +7°C
5.78
4.5
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
1.87 kW
1.44 kW
COP Tj = 12°C
9.12
5.83
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
5 kW
4.25 kW
COP Tj = Tbiv
3.02
2
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.21 kW
3.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.12
1.32
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.92 kW
1.98 kW
Annual energy consumption Qhe
3425 kWh
4428 kWh
Pdh Tj = -15°C (if TOL<-20°C)
5
4.25
COP Tj = -15°C (if TOL<-20°C)
3.02
2
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201.8 %
140.72 %
Prated
6.52 kW
6.36 kW
SCOP
5.12
3.59
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.77 kW
5.62 kW
COP Tj = -7°C
3.43
2.36
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
3.74 kW
3.52 kW
COP Tj = +2°C
5.04
3.7
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
2.32 kW
2.2 kW
COP Tj = +7°C
6.06
4.21
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
1.87 kW
1.31 kW
COP Tj = 12°C
9.12
4.96
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
5.77 kW
5.62 kW
COP Tj = Tbiv
3.43
2.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.52 kW
6.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3
2.02
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.32 kW
Annual energy consumption Qhe
2631 kWh
3655 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.40 kW
8.20 kW
El input
1.66 kW
2.60 kW
COP
5.05
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
274.74 %
185.3 %
Prated
8.06 kW
8.10 kW
SCOP
6.94
4.71
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.23 kW
7.80 kW
COP Tj = +2°C
4.04
2.68
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.18 kW
5.22 kW
COP Tj = +7°C
6.35
4.07
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
2.46 kW
2.36 kW
COP Tj = 12°C
9.30
6.07
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
5.18 kW
5.22 kW
COP Tj = Tbiv
6.35
4.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.23 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.04
2.68
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.84 kW
0.32 kW
Annual energy consumption Qhe
1551 kWh
2303 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
174.6 %
117.73 %
Prated
7.51 kW
6.06 kW
SCOP
4.44
3.02
Tbiv
-15.00 °C
-15.00 °C
TOL
-22.00 °C
-22.00 °C
Pdh Tj = -7°C
4.42 kW
3.95 kW
COP Tj = -7°C
3.67
2.75
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
2.99 kW
2.25 kW
COP Tj = +2°C
5.50
3.30
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
2.03 kW
1.56 kW
COP Tj = +7°C
6.69
4.50
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
1.87 kW
1.44 kW
COP Tj = 12°C
9.12
5.83
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
6.12 kW
4.94 kW
COP Tj = Tbiv
2.70
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.78 kW
3.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.16
1.32
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.72 kW
2.82 kW
Annual energy consumption Qhe
4166 kWh
4948 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.12
4.94
COP Tj = -15°C (if TOL<-20°C)
2.70
2.08
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203.99 %
143.64 %
Prated
7.90 kW
7.25 kW
SCOP
5.17
3.67
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.99 kW
6.42 kW
COP Tj = -7°C
3.29
2.31
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
4.51 kW
4.03 kW
COP Tj = +2°C
4.99
3.76
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
2.81 kW
2.56 kW
COP Tj = +7°C
6.72
4.48
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
1.87 kW
1.31 kW
COP Tj = 12°C
9.12
4.96
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
6.99 kW
6.42 kW
COP Tj = Tbiv
3.29
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.46 kW
6.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
1.98
WTOL
65.00 °C
65.00 °C
Poff
13.00 W
13.00 W
PTO
20.00 W
20.00 W
PSB
13.00 W
13.00 W
PCK
0.00 W
0.00 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.44 kW
0.40 kW
Annual energy consumption Qhe
3155 kWh
4088 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10 kW
9.4 kW
El input
2.13 kW
3.03 kW
COP
4.7
3.1
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
279.05 %
193.4 %
Prated
9.04 kW
9.03 kW
SCOP
7.05
4.91
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.29 kW
8.42 kW
COP Tj = +2°C
3.85
2.68
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
5.81 kW
5.81 kW
COP Tj = +7°C
6.24
4.16
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
2.67 kW
2.74 kW
COP Tj = 12°C
9.63
6.64
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
5.81 kW
5.81 kW
COP Tj = Tbiv
6.24
4.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.29 kW
8.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.85
2.68
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.75 kW
0.61 kW
Annual energy consumption Qhe
1714 kWh
2458 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
174.6 %
122.4 %
Prated
8.27 kW
7.21 kW
SCOP
4.44
3.14
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.42 kW
4.59 kW
COP Tj = -7°C
3.72
2.72
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
3.14 kW
2.82 kW
COP Tj = +2°C
5.56
3.6
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
2.16 kW
1.76 kW
COP Tj = +7°C
6.55
4.84
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
1.87 kW
1.44 kW
COP Tj = 12°C
9.12
5.83
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
6.75 kW
5.88 kW
COP Tj = Tbiv
2.59
2.1
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.08 kW
3.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.01
1.32
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.19 kW
3.97 kW
Annual energy consumption Qhe
4591 kWh
5665 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.75
5.88
COP Tj = -15°C (if TOL<-20°C)
2.59
2.1
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201.91 %
145.47 %
Prated
9.06 kW
8.16 kW
SCOP
5.12
3.71
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.02 kW
7.21 kW
COP Tj = -7°C
3.09
2.24
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
5.06 kW
4.56 kW
COP Tj = +2°C
4.92
3.86
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
3.22 kW
2.84 kW
COP Tj = +7°C
7.03
4.58
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
1.87 kW
1.31 kW
COP Tj = 12°C
9.12
4.96
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
8.02 kW
7.21 kW
COP Tj = Tbiv
3.09
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.88 kW
7.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
1.97
WTOL
65 °C
65 °C
Poff
13 W
13 W
PTO
20 W
20 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.18 kW
1.14 kW
Annual energy consumption Qhe
3654 kWh
4539 kWh