0,850 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.20 kW
4.10 kW
El input
0.84 kW
1.30 kW
COP
4.98
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
218 %
171 %
Prated
6.50 kW
6.00 kW
SCOP
5.53
4.35
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
6.47 kW
5.96 kW
COP Tj = +2°C
3.39
2.49
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.12 kW
3.92 kW
COP Tj = +7°C
5.38
3.88
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.92 kW
4.59 kW
COP Tj = 12°C
6.66
5.67
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
6.47 kW
5.96 kW
COP Tj = Tbiv
3.39
2.49
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.47 kW
5.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.39
2.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
0 W
0 W
PTO
9 W
9 W
PSB
8 W
8 W
PCK
9 W
9 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1570 kWh
1844 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
148 %
125 %
Prated
4.50 kW
4.50 kW
SCOP
3.78
3.20
Tbiv
-15 °C
-15 °C
TOL
-15 °C
-15 °C
Pdh Tj = -7°C
2.75 kW
2.48 kW
COP Tj = -7°C
3.80
2.88
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.12 kW
3.42 kW
COP Tj = +2°C
4.80
4.07
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.18 kW
4.06 kW
COP Tj = +7°C
6.13
5.26
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.26 kW
4.81 kW
COP Tj = 12°C
5.29
6.38
Cdh Tj = +12 °C
0.980
0.990
Pdh Tj = Tbiv
3.64 kW
3.71 kW
COP Tj = Tbiv
2.92
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.64 kW
3.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.92
2.24
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
70 °C
70 °C
Poff
0 W
0 W
PTO
9 W
9 W
PSB
8 W
8 W
PCK
9 W
9 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.50 kW
4.50 kW
Annual energy consumption Qhe
2936 kWh
3472 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.64
3.71
COP Tj = -15°C (if TOL<-20°C)
2.92
2.24
Cdh Tj = -15 °C
0.990
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
0 dB(A)
0 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
142 %
Prated
5.00 kW
5.00 kW
SCOP
4.57
3.63
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.32 kW
4.40 kW
COP Tj = -7°C
3.27
2.35
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
3.18 kW
3.41 kW
COP Tj = +2°C
4.49
3.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.07 kW
3.85 kW
COP Tj = +7°C
5.87
4.81
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.11 kW
4.79 kW
COP Tj = 12°C
6.96
6.11
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
5.03 kW
4.40 kW
COP Tj = Tbiv
3.01
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.03 kW
4.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.01
2.19
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
70 °C
70 °C
Poff
0 W
0 W
PTO
9 W
9 W
PSB
8 W
8 W
PCK
9 W
9 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.48 kW
Annual energy consumption Qhe
2258 kWh
2844 kWh