1,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
4.94 kW
El input
1.16 kW
1.7 kW
COP
4.81
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
169 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.29
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.67 kW
12.42 kW
COP Tj = +2°C
2.66
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.89 kW
COP Tj = +7°C
5.13
3.66
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.79
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.67 kW
12.42 kW
COP Tj = Tbiv
2.66
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.67 kW
12.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2847 kWh
3859 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.25
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.05 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.35 kW
COP Tj = +2°C
5.38
4.08
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.57 kW
COP Tj = +7°C
5.3
5.18
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.03
5.93
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.83 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.73 kW
7 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.27 kW
5 kW
Annual energy consumption Qhe
7021 kWh
9107 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.83
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.10 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.69 kW
6.27 kW
COP Tj = +2°C
4.69
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.22 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.65 kW
COP Tj = 12°C
8.05
5.84
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.10 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.84 kW
11.14 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.36 kW
0.86 kW
Annual energy consumption Qhe
5428 kWh
7114 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
4.94 kW
El input
1.16 kW
1.7 kW
COP
4.81
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
169 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.29
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.67 kW
12.42 kW
COP Tj = +2°C
2.66
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.89 kW
COP Tj = +7°C
5.13
3.66
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.79
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.67 kW
12.42 kW
COP Tj = Tbiv
2.66
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.67 kW
12.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2847 kWh
3859 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.25
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.05 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.35 kW
COP Tj = +2°C
5.38
4.08
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.57 kW
COP Tj = +7°C
5.3
5.18
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.03
5.93
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.83 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.73 kW
7 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.27 kW
5 kW
Annual energy consumption Qhe
7021 kWh
9107 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.83
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.10 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.69 kW
6.27 kW
COP Tj = +2°C
4.69
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.22 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.65 kW
COP Tj = 12°C
8.05
5.84
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.10 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.84 kW
11.14 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.36 kW
0.86 kW
Annual energy consumption Qhe
5428 kWh
7114 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
4.94 kW
El input
1.16 kW
1.7 kW
COP
4.81
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
169 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.29
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.67 kW
12.42 kW
COP Tj = +2°C
2.66
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.89 kW
COP Tj = +7°C
5.13
3.66
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.79
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.67 kW
12.42 kW
COP Tj = Tbiv
2.66
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.67 kW
12.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2847 kWh
3859 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.25
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.05 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.35 kW
COP Tj = +2°C
5.38
4.08
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.57 kW
COP Tj = +7°C
5.3
5.18
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.03
5.93
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.83 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.73 kW
7 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.27 kW
5 kW
Annual energy consumption Qhe
7021 kWh
9107 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.83
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.10 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.69 kW
6.27 kW
COP Tj = +2°C
4.69
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.22 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.65 kW
COP Tj = 12°C
8.05
5.84
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.10 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.84 kW
11.14 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.36 kW
0.86 kW
Annual energy consumption Qhe
5428 kWh
7114 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
4.94 kW
El input
1.16 kW
1.7 kW
COP
4.81
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
169 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.29
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.67 kW
12.42 kW
COP Tj = +2°C
2.66
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.89 kW
COP Tj = +7°C
5.13
3.66
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.79
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.67 kW
12.42 kW
COP Tj = Tbiv
2.66
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.67 kW
12.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2847 kWh
3859 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.25
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.05 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.35 kW
COP Tj = +2°C
5.38
4.08
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.57 kW
COP Tj = +7°C
5.3
5.18
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.03
5.93
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.83 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.73 kW
7 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.27 kW
5 kW
Annual energy consumption Qhe
7021 kWh
9107 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.83
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.10 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.69 kW
6.27 kW
COP Tj = +2°C
4.69
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.22 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.65 kW
COP Tj = 12°C
8.05
5.84
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.10 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.84 kW
11.14 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.36 kW
0.86 kW
Annual energy consumption Qhe
5428 kWh
7114 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
4.96 kW
El input
1.15 kW
1.69 kW
COP
4.84
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
235 %
170 %
Prated
12.6 kW
12.4 kW
SCOP
5.95
4.32
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.61 kW
12.43 kW
COP Tj = +2°C
2.64
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.91 kW
COP Tj = +7°C
5.17
3.67
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.45 kW
3.58 kW
COP Tj = 12°C
8.07
5.84
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.61 kW
12.43 kW
COP Tj = Tbiv
2.64
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.61 kW
12.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2829 kWh
3834 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
128 %
Prated
12 kW
12 kW
SCOP
4.24
3.27
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.07 kW
COP Tj = -7°C
3.6
2.58
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.36 kW
COP Tj = +2°C
5.42
4.1
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.86 kW
2.59 kW
COP Tj = +7°C
5.35
5.35
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.1 kW
2.87 kW
COP Tj = 12°C
8.1
6.09
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.44 kW
9.85 kW
COP Tj = Tbiv
2.37
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.74 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.27
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.26 kW
4.98 kW
Annual energy consumption Qhe
6979 kWh
9035 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.44
9.85
COP Tj = -15°C (if TOL<-20°C)
2.37
1.94
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
137 %
Prated
12.2 kW
12 kW
SCOP
4.66
3.51
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.73 kW
11.11 kW
COP Tj = -7°C
2.44
1.91
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.70 kW
6.28 kW
COP Tj = +2°C
4.72
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.23 kW
COP Tj = +7°C
6.28
4.48
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.02 kW
3.67 kW
COP Tj = 12°C
8.12
5.99
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.73 kW
11.11 kW
COP Tj = Tbiv
2.44
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.82 kW
11.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.46
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.38 kW
0.84 kW
Annual energy consumption Qhe
5405 kWh
7071 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
4.96 kW
El input
1.15 kW
1.69 kW
COP
4.84
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
235 %
170 %
Prated
12.6 kW
12.4 kW
SCOP
5.95
4.32
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.61 kW
12.43 kW
COP Tj = +2°C
2.64
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.91 kW
COP Tj = +7°C
5.17
3.67
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.45 kW
3.58 kW
COP Tj = 12°C
8.07
5.84
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.61 kW
12.43 kW
COP Tj = Tbiv
2.64
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.61 kW
12.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2829 kWh
3834 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
128 %
Prated
12 kW
12 kW
SCOP
4.24
3.27
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.07 kW
COP Tj = -7°C
3.6
2.58
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.36 kW
COP Tj = +2°C
5.42
4.1
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.86 kW
2.59 kW
COP Tj = +7°C
5.35
5.35
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.1 kW
2.87 kW
COP Tj = 12°C
8.1
6.09
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.44 kW
9.85 kW
COP Tj = Tbiv
2.37
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.74 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.27
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.26 kW
4.98 kW
Annual energy consumption Qhe
6979 kWh
9035 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.44
9.85
COP Tj = -15°C (if TOL<-20°C)
2.37
1.94
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
137 %
Prated
12.2 kW
12 kW
SCOP
4.66
3.51
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.73 kW
11.11 kW
COP Tj = -7°C
2.44
1.91
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.70 kW
6.28 kW
COP Tj = +2°C
4.72
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.23 kW
COP Tj = +7°C
6.28
4.48
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.02 kW
3.67 kW
COP Tj = 12°C
8.12
5.99
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.73 kW
11.11 kW
COP Tj = Tbiv
2.44
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.82 kW
11.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.46
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.38 kW
0.84 kW
Annual energy consumption Qhe
5405 kWh
7071 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
4.96 kW
El input
1.15 kW
1.69 kW
COP
4.84
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
235 %
170 %
Prated
12.6 kW
12.4 kW
SCOP
5.95
4.32
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.61 kW
12.43 kW
COP Tj = +2°C
2.64
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.91 kW
COP Tj = +7°C
5.17
3.67
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.45 kW
3.58 kW
COP Tj = 12°C
8.07
5.84
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.61 kW
12.43 kW
COP Tj = Tbiv
2.64
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.61 kW
12.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2829 kWh
3834 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
128 %
Prated
12 kW
12 kW
SCOP
4.24
3.27
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.07 kW
COP Tj = -7°C
3.6
2.58
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.36 kW
COP Tj = +2°C
5.42
4.1
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.86 kW
2.59 kW
COP Tj = +7°C
5.35
5.35
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.1 kW
2.87 kW
COP Tj = 12°C
8.1
6.09
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.44 kW
9.85 kW
COP Tj = Tbiv
2.37
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.74 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.27
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.26 kW
4.98 kW
Annual energy consumption Qhe
6979 kWh
9035 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.44
9.85
COP Tj = -15°C (if TOL<-20°C)
2.37
1.94
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
137 %
Prated
12.2 kW
12 kW
SCOP
4.66
3.51
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.73 kW
11.11 kW
COP Tj = -7°C
2.44
1.91
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.70 kW
6.28 kW
COP Tj = +2°C
4.72
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.23 kW
COP Tj = +7°C
6.28
4.48
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.02 kW
3.67 kW
COP Tj = 12°C
8.12
5.99
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.73 kW
11.11 kW
COP Tj = Tbiv
2.44
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.82 kW
11.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.46
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.38 kW
0.84 kW
Annual energy consumption Qhe
5405 kWh
7071 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
4.96 kW
El input
1.15 kW
1.69 kW
COP
4.84
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
235 %
170 %
Prated
12.6 kW
12.4 kW
SCOP
5.95
4.32
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.61 kW
12.43 kW
COP Tj = +2°C
2.64
2.04
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.91 kW
COP Tj = +7°C
5.17
3.67
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.45 kW
3.58 kW
COP Tj = 12°C
8.07
5.84
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.61 kW
12.43 kW
COP Tj = Tbiv
2.64
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.61 kW
12.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2829 kWh
3834 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
128 %
Prated
12 kW
12 kW
SCOP
4.24
3.27
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.07 kW
COP Tj = -7°C
3.6
2.58
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.72 kW
4.36 kW
COP Tj = +2°C
5.42
4.1
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.86 kW
2.59 kW
COP Tj = +7°C
5.35
5.35
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.1 kW
2.87 kW
COP Tj = 12°C
8.1
6.09
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.44 kW
9.85 kW
COP Tj = Tbiv
2.37
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.74 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.27
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.26 kW
4.98 kW
Annual energy consumption Qhe
6979 kWh
9035 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.44
9.85
COP Tj = -15°C (if TOL<-20°C)
2.37
1.94
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
137 %
Prated
12.2 kW
12 kW
SCOP
4.66
3.51
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.73 kW
11.11 kW
COP Tj = -7°C
2.44
1.91
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.70 kW
6.28 kW
COP Tj = +2°C
4.72
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.23 kW
COP Tj = +7°C
6.28
4.48
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.02 kW
3.67 kW
COP Tj = 12°C
8.12
5.99
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.73 kW
11.11 kW
COP Tj = Tbiv
2.44
1.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.82 kW
11.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.46
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.38 kW
0.84 kW
Annual energy consumption Qhe
5405 kWh
7071 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
3.46 kW
El input
1.16 kW
1.2 kW
COP
4.81
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
243 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.57 kW
9.78 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.95 kW
COP Tj = +7°C
5.19
3.57
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.32
5.8
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.57 kW
9.78 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.57 kW
9.78 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2306 kWh
3059 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.3
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.42 kW
5.91 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.93 kW
COP Tj = +2°C
5.28
4.03
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.46 kW
COP Tj = +7°C
6.84
5.18
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.86 kW
COP Tj = 12°C
7.81
6.05
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.72 kW
COP Tj = Tbiv
2.57
2.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.72 kW
Annual energy consumption Qhe
5681 kWh
7474 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.72
COP Tj = -15°C (if TOL<-20°C)
2.57
2.07
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.74
3.61
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.07 kW
9.29 kW
COP Tj = -7°C
2.66
2.21
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.46 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.40 kW
COP Tj = +7°C
6.12
4.58
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.99 kW
COP Tj = 12°C
7.85
5.87
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.07 kW
9.29 kW
COP Tj = Tbiv
2.66
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.26 kW
Annual energy consumption Qhe
4361 kWh
5728 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
3.46 kW
El input
1.16 kW
1.2 kW
COP
4.81
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
243 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.57 kW
9.78 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.95 kW
COP Tj = +7°C
5.19
3.57
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.32
5.8
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.57 kW
9.78 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.57 kW
9.78 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2306 kWh
3059 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.3
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.42 kW
5.91 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.93 kW
COP Tj = +2°C
5.28
4.03
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.46 kW
COP Tj = +7°C
6.84
5.18
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.86 kW
COP Tj = 12°C
7.81
6.05
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.72 kW
COP Tj = Tbiv
2.57
2.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.72 kW
Annual energy consumption Qhe
5681 kWh
7474 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.72
COP Tj = -15°C (if TOL<-20°C)
2.57
2.07
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.74
3.61
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.07 kW
9.29 kW
COP Tj = -7°C
2.66
2.21
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.46 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.40 kW
COP Tj = +7°C
6.12
4.58
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.99 kW
COP Tj = 12°C
7.85
5.87
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.07 kW
9.29 kW
COP Tj = Tbiv
2.66
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.26 kW
Annual energy consumption Qhe
4361 kWh
5728 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
3.46 kW
El input
1.16 kW
1.2 kW
COP
4.81
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
243 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.57 kW
9.78 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.95 kW
COP Tj = +7°C
5.19
3.57
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.32
5.8
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.57 kW
9.78 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.57 kW
9.78 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2306 kWh
3059 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.3
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.42 kW
5.91 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.93 kW
COP Tj = +2°C
5.28
4.03
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.46 kW
COP Tj = +7°C
6.84
5.18
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.86 kW
COP Tj = 12°C
7.81
6.05
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.72 kW
COP Tj = Tbiv
2.57
2.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.72 kW
Annual energy consumption Qhe
5681 kWh
7474 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.72
COP Tj = -15°C (if TOL<-20°C)
2.57
2.07
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.74
3.61
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.07 kW
9.29 kW
COP Tj = -7°C
2.66
2.21
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.46 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.40 kW
COP Tj = +7°C
6.12
4.58
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.99 kW
COP Tj = 12°C
7.85
5.87
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.07 kW
9.29 kW
COP Tj = Tbiv
2.66
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.26 kW
Annual energy consumption Qhe
4361 kWh
5728 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.57 kW
3.46 kW
El input
1.16 kW
1.2 kW
COP
4.81
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
243 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.57 kW
9.78 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.95 kW
COP Tj = +7°C
5.19
3.57
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.32
5.8
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.57 kW
9.78 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.57 kW
9.78 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2306 kWh
3059 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.3
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.42 kW
5.91 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.93 kW
COP Tj = +2°C
5.28
4.03
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.46 kW
COP Tj = +7°C
6.84
5.18
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.86 kW
COP Tj = 12°C
7.81
6.05
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.72 kW
COP Tj = Tbiv
2.57
2.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.72 kW
Annual energy consumption Qhe
5681 kWh
7474 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.72
COP Tj = -15°C (if TOL<-20°C)
2.57
2.07
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.74
3.61
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.07 kW
9.29 kW
COP Tj = -7°C
2.66
2.21
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.46 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.40 kW
COP Tj = +7°C
6.12
4.58
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.99 kW
COP Tj = 12°C
7.85
5.87
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.07 kW
9.29 kW
COP Tj = Tbiv
2.66
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.26 kW
Annual energy consumption Qhe
4361 kWh
5728 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
3.49 kW
El input
1.15 kW
1.2 kW
COP
4.84
2.92
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
244 %
171 %
Prated
10.6 kW
9.8 kW
SCOP
6.18
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.58 kW
9.8 kW
COP Tj = +2°C
2.95
2.13
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.97 kW
COP Tj = +7°C
5.23
3.59
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.86 kW
COP Tj = 12°C
8.39
5.95
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.58 kW
9.8 kW
COP Tj = Tbiv
2.95
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.58 kW
9.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2292 kWh
3017 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
130 %
Prated
10 kW
10 kW
SCOP
4.36
3.33
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.43 kW
5.93 kW
COP Tj = -7°C
3.68
2.67
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.62 kW
3.94 kW
COP Tj = +2°C
5.31
4.08
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.68 kW
2.48 kW
COP Tj = +7°C
6.89
5.35
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.88 kW
COP Tj = 12°C
7.87
6.21
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.09 kW
7.75 kW
COP Tj = Tbiv
2.58
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.31 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.69 kW
Annual energy consumption Qhe
5648 kWh
7392 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.09
7.75
COP Tj = -15°C (if TOL<-20°C)
2.58
2.08
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
142 %
Prated
10 kW
10 kW
SCOP
4.77
3.64
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.04 kW
9.32 kW
COP Tj = -7°C
2.68
2.22
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.89 kW
5.47 kW
COP Tj = +2°C
4.84
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.64 kW
3.41 kW
COP Tj = +7°C
6.16
4.64
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.13 kW
3.01 kW
COP Tj = 12°C
7.92
6.02
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.04 kW
9.32 kW
COP Tj = Tbiv
2.68
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.69
2.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.23 kW
Annual energy consumption Qhe
4333 kWh
5681 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
3.49 kW
El input
1.15 kW
1.2 kW
COP
4.84
2.92
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
244 %
171 %
Prated
10.6 kW
9.8 kW
SCOP
6.18
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.58 kW
9.8 kW
COP Tj = +2°C
2.95
2.13
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.97 kW
COP Tj = +7°C
5.23
3.59
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.86 kW
COP Tj = 12°C
8.39
5.95
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.58 kW
9.8 kW
COP Tj = Tbiv
2.95
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.58 kW
9.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2292 kWh
3017 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
130 %
Prated
10 kW
10 kW
SCOP
4.36
3.33
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.43 kW
5.93 kW
COP Tj = -7°C
3.68
2.67
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.62 kW
3.94 kW
COP Tj = +2°C
5.31
4.08
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.68 kW
2.48 kW
COP Tj = +7°C
6.89
5.35
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.88 kW
COP Tj = 12°C
7.87
6.21
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.09 kW
7.75 kW
COP Tj = Tbiv
2.58
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.31 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.69 kW
Annual energy consumption Qhe
5648 kWh
7392 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.09
7.75
COP Tj = -15°C (if TOL<-20°C)
2.58
2.08
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
142 %
Prated
10 kW
10 kW
SCOP
4.77
3.64
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.04 kW
9.32 kW
COP Tj = -7°C
2.68
2.22
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.89 kW
5.47 kW
COP Tj = +2°C
4.84
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.64 kW
3.41 kW
COP Tj = +7°C
6.16
4.64
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.13 kW
3.01 kW
COP Tj = 12°C
7.92
6.02
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.04 kW
9.32 kW
COP Tj = Tbiv
2.68
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.69
2.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.23 kW
Annual energy consumption Qhe
4333 kWh
5681 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
3.49 kW
El input
1.15 kW
1.2 kW
COP
4.84
2.92
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
244 %
171 %
Prated
10.6 kW
9.8 kW
SCOP
6.18
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.58 kW
9.8 kW
COP Tj = +2°C
2.95
2.13
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.97 kW
COP Tj = +7°C
5.23
3.59
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.86 kW
COP Tj = 12°C
8.39
5.95
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.58 kW
9.8 kW
COP Tj = Tbiv
2.95
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.58 kW
9.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2292 kWh
3017 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
130 %
Prated
10 kW
10 kW
SCOP
4.36
3.33
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.43 kW
5.93 kW
COP Tj = -7°C
3.68
2.67
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.62 kW
3.94 kW
COP Tj = +2°C
5.31
4.08
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.68 kW
2.48 kW
COP Tj = +7°C
6.89
5.35
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.88 kW
COP Tj = 12°C
7.87
6.21
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.09 kW
7.75 kW
COP Tj = Tbiv
2.58
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.31 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.69 kW
Annual energy consumption Qhe
5648 kWh
7392 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.09
7.75
COP Tj = -15°C (if TOL<-20°C)
2.58
2.08
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
142 %
Prated
10 kW
10 kW
SCOP
4.77
3.64
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.04 kW
9.32 kW
COP Tj = -7°C
2.68
2.22
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.89 kW
5.47 kW
COP Tj = +2°C
4.84
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.64 kW
3.41 kW
COP Tj = +7°C
6.16
4.64
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.13 kW
3.01 kW
COP Tj = 12°C
7.92
6.02
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.04 kW
9.32 kW
COP Tj = Tbiv
2.68
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.69
2.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.23 kW
Annual energy consumption Qhe
4333 kWh
5681 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.58 kW
3.49 kW
El input
1.15 kW
1.2 kW
COP
4.84
2.92
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
244 %
171 %
Prated
10.6 kW
9.8 kW
SCOP
6.18
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.58 kW
9.8 kW
COP Tj = +2°C
2.95
2.13
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.42 kW
5.97 kW
COP Tj = +7°C
5.23
3.59
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.86 kW
COP Tj = 12°C
8.39
5.95
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.58 kW
9.8 kW
COP Tj = Tbiv
2.95
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.58 kW
9.8 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2292 kWh
3017 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
130 %
Prated
10 kW
10 kW
SCOP
4.36
3.33
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.43 kW
5.93 kW
COP Tj = -7°C
3.68
2.67
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.62 kW
3.94 kW
COP Tj = +2°C
5.31
4.08
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.68 kW
2.48 kW
COP Tj = +7°C
6.89
5.35
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.88 kW
COP Tj = 12°C
7.87
6.21
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.09 kW
7.75 kW
COP Tj = Tbiv
2.58
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.6 kW
6.31 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.4 kW
3.69 kW
Annual energy consumption Qhe
5648 kWh
7392 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.09
7.75
COP Tj = -15°C (if TOL<-20°C)
2.58
2.08
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
31 dB(A)
31 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
142 %
Prated
10 kW
10 kW
SCOP
4.77
3.64
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.04 kW
9.32 kW
COP Tj = -7°C
2.68
2.22
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.89 kW
5.47 kW
COP Tj = +2°C
4.84
3.60
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.64 kW
3.41 kW
COP Tj = +7°C
6.16
4.64
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.13 kW
3.01 kW
COP Tj = 12°C
7.92
6.02
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.04 kW
9.32 kW
COP Tj = Tbiv
2.68
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.29 kW
8.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.69
2.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.71 kW
1.23 kW
Annual energy consumption Qhe
4333 kWh
5681 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
3.44 kW
El input
1.16 kW
1.2 kW
COP
4.8
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
242 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.27
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.56 kW
9.76 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.41 kW
5.93 kW
COP Tj = +7°C
5.19
3.56
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.31
5.79
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.56 kW
9.76 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.56 kW
9.76 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2308 kWh
3067 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.29
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.41 kW
5.89 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.92 kW
COP Tj = +2°C
5.27
4.02
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.45 kW
COP Tj = +7°C
6.83
5.17
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.85 kW
COP Tj = 12°C
7.8
6.04
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.71 kW
COP Tj = Tbiv
2.57
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.59 kW
6.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.71
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.41 kW
3.75 kW
Annual energy consumption Qhe
5685 kWh
7492 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.71
COP Tj = -15°C (if TOL<-20°C)
2.57
2.06
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.73
3.6
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.06 kW
9.27 kW
COP Tj = -7°C
2.66
2.20
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.45 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.39 kW
COP Tj = +7°C
6.11
4.57
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.98 kW
COP Tj = 12°C
7.84
5.86
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.06 kW
9.27 kW
COP Tj = Tbiv
2.66
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.28 kW
8.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.72 kW
1.29 kW
Annual energy consumption Qhe
4365 kWh
5742 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.88
Heating up time
2:15 h:min
Standby power input
90 W
Reference hot water temperature
52.8 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
2.02
Heating up time
2:34 h:min
Standby power input
128.6 W
Reference hot water temperature
52.6 °C
Mixed water at 40°C
237 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.33
Heating up time
2:56 h:min
Standby power input
106 W
Reference hot water temperature
52.7 °C
Mixed water at 40°C
235 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
3.44 kW
El input
1.16 kW
1.2 kW
COP
4.8
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
242 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.27
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.56 kW
9.76 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.41 kW
5.93 kW
COP Tj = +7°C
5.19
3.56
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.31
5.79
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.56 kW
9.76 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.56 kW
9.76 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2308 kWh
3067 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.29
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.41 kW
5.89 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.92 kW
COP Tj = +2°C
5.27
4.02
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.45 kW
COP Tj = +7°C
6.83
5.17
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.85 kW
COP Tj = 12°C
7.8
6.04
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.71 kW
COP Tj = Tbiv
2.57
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.59 kW
6.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.71
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.41 kW
3.75 kW
Annual energy consumption Qhe
5685 kWh
7492 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.71
COP Tj = -15°C (if TOL<-20°C)
2.57
2.06
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.73
3.6
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.06 kW
9.27 kW
COP Tj = -7°C
2.66
2.20
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.45 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.39 kW
COP Tj = +7°C
6.11
4.57
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.98 kW
COP Tj = 12°C
7.84
5.86
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.06 kW
9.27 kW
COP Tj = Tbiv
2.66
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.28 kW
8.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.72 kW
1.29 kW
Annual energy consumption Qhe
4365 kWh
5742 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.88
Heating up time
2:15 h:min
Standby power input
90 W
Reference hot water temperature
52.8 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
2.02
Heating up time
2:34 h:min
Standby power input
128.6 W
Reference hot water temperature
52.6 °C
Mixed water at 40°C
237 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.33
Heating up time
2:56 h:min
Standby power input
106 W
Reference hot water temperature
52.7 °C
Mixed water at 40°C
235 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
3.44 kW
El input
1.16 kW
1.2 kW
COP
4.8
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
242 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.27
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.56 kW
9.76 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.41 kW
5.93 kW
COP Tj = +7°C
5.19
3.56
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.31
5.79
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.56 kW
9.76 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.56 kW
9.76 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2308 kWh
3067 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.29
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.41 kW
5.89 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.92 kW
COP Tj = +2°C
5.27
4.02
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.45 kW
COP Tj = +7°C
6.83
5.17
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.85 kW
COP Tj = 12°C
7.8
6.04
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.71 kW
COP Tj = Tbiv
2.57
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.59 kW
6.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.71
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.41 kW
3.75 kW
Annual energy consumption Qhe
5685 kWh
7492 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.71
COP Tj = -15°C (if TOL<-20°C)
2.57
2.06
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.73
3.6
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.06 kW
9.27 kW
COP Tj = -7°C
2.66
2.20
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.45 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.39 kW
COP Tj = +7°C
6.11
4.57
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.98 kW
COP Tj = 12°C
7.84
5.86
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.06 kW
9.27 kW
COP Tj = Tbiv
2.66
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.28 kW
8.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.72 kW
1.29 kW
Annual energy consumption Qhe
4365 kWh
5742 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.88
Heating up time
2:15 h:min
Standby power input
90 W
Reference hot water temperature
52.8 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
2.02
Heating up time
2:34 h:min
Standby power input
128.6 W
Reference hot water temperature
52.6 °C
Mixed water at 40°C
237 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.33
Heating up time
2:56 h:min
Standby power input
106 W
Reference hot water temperature
52.7 °C
Mixed water at 40°C
235 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
3.44 kW
El input
1.16 kW
1.2 kW
COP
4.8
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
242 %
168 %
Prated
10.6 kW
9.8 kW
SCOP
6.14
4.27
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
10.56 kW
9.76 kW
COP Tj = +2°C
2.98
2.12
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
6.41 kW
5.93 kW
COP Tj = +7°C
5.19
3.56
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.1 kW
2.84 kW
COP Tj = 12°C
8.31
5.79
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.56 kW
9.76 kW
COP Tj = Tbiv
2.98
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.56 kW
9.76 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2308 kWh
3067 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
170 %
129 %
Prated
10 kW
10 kW
SCOP
4.34
3.29
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.41 kW
5.89 kW
COP Tj = -7°C
3.66
2.65
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.61 kW
3.92 kW
COP Tj = +2°C
5.27
4.02
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.67 kW
2.45 kW
COP Tj = +7°C
6.83
5.17
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
3.05 kW
2.85 kW
COP Tj = 12°C
7.8
6.04
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
8.08 kW
7.71 kW
COP Tj = Tbiv
2.57
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.59 kW
6.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.71
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.41 kW
3.75 kW
Annual energy consumption Qhe
5685 kWh
7492 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.08
7.71
COP Tj = -15°C (if TOL<-20°C)
2.57
2.06
Cdh Tj = -15 °C
0.99
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
42 dB(A)
42 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
141 %
Prated
10 kW
10 kW
SCOP
4.73
3.6
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.06 kW
9.27 kW
COP Tj = -7°C
2.66
2.20
Cdh Tj = -7 °C
0.99
1
Pdh Tj = +2°C
5.88 kW
5.45 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.63 kW
3.39 kW
COP Tj = +7°C
6.11
4.57
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.12 kW
2.98 kW
COP Tj = 12°C
7.84
5.86
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
9.06 kW
9.27 kW
COP Tj = Tbiv
2.66
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.28 kW
8.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
34 W
34 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.72 kW
1.29 kW
Annual energy consumption Qhe
4365 kWh
5742 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.88
Heating up time
2:15 h:min
Standby power input
90 W
Reference hot water temperature
52.8 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
2.02
Heating up time
2:34 h:min
Standby power input
128.6 W
Reference hot water temperature
52.6 °C
Mixed water at 40°C
237 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.33
Heating up time
2:56 h:min
Standby power input
106 W
Reference hot water temperature
52.7 °C
Mixed water at 40°C
235 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
4.91 kW
El input
1.16 kW
1.7 kW
COP
4.8
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233 %
168 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.66 kW
12.4 kW
COP Tj = +2°C
2.66
2.03
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.87 kW
COP Tj = +7°C
5.13
3.65
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.78
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.66 kW
12.4 kW
COP Tj = Tbiv
2.66
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.66 kW
12.4 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2848 kWh
3866 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.24
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.03 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.71 kW
4.34 kW
COP Tj = +2°C
5.38
4.07
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.56 kW
COP Tj = +7°C
5.3
5.17
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.02
5.92
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.81 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.72 kW
6.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.28 kW
5.03 kW
Annual energy consumption Qhe
7025 kWh
9125 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.81
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.07 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.68 kW
6.25 kW
COP Tj = +2°C
4.68
3.57
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.21 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.64 kW
COP Tj = 12°C
8.04
5.83
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.07 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.83 kW
11.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
60 °C
60 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.37 kW
0.89 kW
Annual energy consumption Qhe
5432 kWh
7130 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.87
Heating up time
2:03 h:min
Standby power input
90 W
Reference hot water temperature
53 °C
Mixed water at 40°C
244 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
1.99
Heating up time
2:24 h:min
Standby power input
170 W
Reference hot water temperature
52.9 °C
Mixed water at 40°C
238 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.34
Heating up time
2:12 h:min
Standby power input
100 W
Reference hot water temperature
53.1 °C
Mixed water at 40°C
235 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
4.91 kW
El input
1.16 kW
1.7 kW
COP
4.8
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233 %
168 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.66 kW
12.4 kW
COP Tj = +2°C
2.66
2.03
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.87 kW
COP Tj = +7°C
5.13
3.65
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.78
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.66 kW
12.4 kW
COP Tj = Tbiv
2.66
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.66 kW
12.4 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2848 kWh
3866 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.24
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.03 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.71 kW
4.34 kW
COP Tj = +2°C
5.38
4.07
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.56 kW
COP Tj = +7°C
5.3
5.17
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.02
5.92
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.81 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.72 kW
6.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.28 kW
5.03 kW
Annual energy consumption Qhe
7025 kWh
9125 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.81
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.07 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.68 kW
6.25 kW
COP Tj = +2°C
4.68
3.57
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.21 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.64 kW
COP Tj = 12°C
8.04
5.83
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.07 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.83 kW
11.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.37 kW
0.89 kW
Annual energy consumption Qhe
5432 kWh
7130 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.87
Heating up time
2:03 h:min
Standby power input
90 W
Reference hot water temperature
53 °C
Mixed water at 40°C
244 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
1.99
Heating up time
2:24 h:min
Standby power input
170 W
Reference hot water temperature
52.9 °C
Mixed water at 40°C
238 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.34
Heating up time
2:12 h:min
Standby power input
100 W
Reference hot water temperature
53.1 °C
Mixed water at 40°C
235 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
4.91 kW
El input
1.16 kW
1.7 kW
COP
4.8
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233 %
168 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.66 kW
12.4 kW
COP Tj = +2°C
2.66
2.03
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.87 kW
COP Tj = +7°C
5.13
3.65
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.78
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.66 kW
12.4 kW
COP Tj = Tbiv
2.66
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.66 kW
12.4 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2848 kWh
3866 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.24
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.03 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.71 kW
4.34 kW
COP Tj = +2°C
5.38
4.07
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.56 kW
COP Tj = +7°C
5.3
5.17
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.02
5.92
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.81 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.72 kW
6.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.28 kW
5.03 kW
Annual energy consumption Qhe
7025 kWh
9125 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.81
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.07 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.68 kW
6.25 kW
COP Tj = +2°C
4.68
3.57
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.21 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.64 kW
COP Tj = 12°C
8.04
5.83
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.07 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.83 kW
11.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.37 kW
0.89 kW
Annual energy consumption Qhe
5432 kWh
7130 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.87
Heating up time
2:03 h:min
Standby power input
90 W
Reference hot water temperature
53 °C
Mixed water at 40°C
244 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
1.99
Heating up time
2:24 h:min
Standby power input
170 W
Reference hot water temperature
52.9 °C
Mixed water at 40°C
238 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.34
Heating up time
2:12 h:min
Standby power input
100 W
Reference hot water temperature
53.1 °C
Mixed water at 40°C
235 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.56 kW
4.91 kW
El input
1.16 kW
1.7 kW
COP
4.8
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233 %
168 %
Prated
12.6 kW
12.4 kW
SCOP
5.91
4.28
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.66 kW
12.4 kW
COP Tj = +2°C
2.66
2.03
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
8.66 kW
7.87 kW
COP Tj = +7°C
5.13
3.65
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.44 kW
3.57 kW
COP Tj = 12°C
8
5.78
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
12.66 kW
12.4 kW
COP Tj = Tbiv
2.66
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.66 kW
12.4 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2848 kWh
3866 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
127 %
Prated
12 kW
12 kW
SCOP
4.21
3.24
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.3 kW
7.03 kW
COP Tj = -7°C
3.58
2.56
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
4.71 kW
4.34 kW
COP Tj = +2°C
5.38
4.07
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
2.85 kW
2.56 kW
COP Tj = +7°C
5.3
5.17
Cdh Tj = +7 °C
0.97
0.96
Pdh Tj = 12°C
3.09 kW
2.85 kW
COP Tj = 12°C
8.02
5.92
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
10.47 kW
9.81 kW
COP Tj = Tbiv
2.35
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.72 kW
6.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.28 kW
5.03 kW
Annual energy consumption Qhe
7025 kWh
9125 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.47
9.81
COP Tj = -15°C (if TOL<-20°C)
2.35
1.93
Cdh Tj = -15 °C
1
1
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
136 %
Prated
12.2 kW
12 kW
SCOP
4.64
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.69 kW
11.07 kW
COP Tj = -7°C
2.45
1.90
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
6.68 kW
6.25 kW
COP Tj = +2°C
4.68
3.57
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
4.10 kW
4.21 kW
COP Tj = +7°C
6.24
4.45
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
3.01 kW
3.64 kW
COP Tj = 12°C
8.04
5.83
Cdh Tj = +12 °C
0.95
0.97
Pdh Tj = Tbiv
11.69 kW
11.07 kW
COP Tj = Tbiv
2.45
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.83 kW
11.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
33 W
33 W
PTO
18 W
18 W
PSB
33 W
33 W
PCK
67 W
67 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.37 kW
0.89 kW
Annual energy consumption Qhe
5432 kWh
7130 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.87
Heating up time
2:03 h:min
Standby power input
90 W
Reference hot water temperature
53 °C
Mixed water at 40°C
244 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
83 %
COP
1.99
Heating up time
2:24 h:min
Standby power input
170 W
Reference hot water temperature
52.9 °C
Mixed water at 40°C
238 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
95 %
COP
2.34
Heating up time
2:12 h:min
Standby power input
100 W
Reference hot water temperature
53.1 °C
Mixed water at 40°C
235 l