Login

Subtype

ECL-PAC-16-18

Certificate Holder
ECL Nexus
13, Boulevard Pereire
75017 Paris
France
Registration number
ICIM-PDC-000145
Certification Body
ICIM S.p.A.
Subtype title
ECL-PAC-16-18
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

4,000 kg

Certification Date
20.05.2022
Testing basis
HP KEYMARK certification scheme rules rev. no. 7
Generate PDF Export model CSV
  • Number of models 3

Models

ECLPAC16X.ST ; ECLPAC16X.KA
Configure model
Model name
ECLPAC16X.ST ; ECLPAC16X.KA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Cooling

EN 14511-2

+7°C/+12°C

El input

4.38 kW

Cooling capacity

13.80

EER

3.15

EN 14825

+7°C/+12°C

Pdesignc

13.80 kW

SEER

4.80

Pdc Tj = 35°C

13.80 kW

EER Tj = 35°C

3.15

Pdc Tj = 30°C

10.17 kW

EER Tj = 30°C

4.36

Cdc Tj = 30 °C

1.0

Pdc Tj = 25°C

6.47 kW

EER Tj = 25°C

5.30

Cdc Tj = 25 °C

1.0

Pdc Tj = 20°C

5.53 kW

EER Tj = 20°C

6.67

Cdc Tj = 20 °C

1.0

Poff

19 W

PTO

0 W

PSB

19 W

PCK

30 W

Annual energy consumption Qce

1726 kWh

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.30 kW

15.63 kW

El input

3.49 kW

5.18 kW

COP

4.67

3.02

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

dB(A)

dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

126 %

Prated

14.00 kW

13.00 kW

SCOP

4.50

3.22

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

12.00 kW

11.50 kW

COP Tj = -7°C

2.88

2.09

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.30 kW

6.90 kW

COP Tj = +2°C

4.33

3.06

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

5.70 kW

5.50 kW

COP Tj = +7°C

5.83

4.11

Cdh Tj = +7 °C

0.981

0.986

Pdh Tj = 12°C

6.70 kW

6.60 kW

COP Tj = 12°C

8.12

6.30

Cdh Tj = +12 °C

0.977

0.982

Pdh Tj = Tbiv

12.00 kW

11.50 kW

COP Tj = Tbiv

2.88

2.09

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

11.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.94

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

22 W

22 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

2.30 kW

1.50 kW

Annual energy consumption Qhe

6209 kWh

8357 kWh

ECLPAC18T.ST ; ECLPAC18T.KA
Configure model
Model name
ECLPAC18T.ST ; ECLPAC18T.KA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Cooling

EN 14511-2

+7°C/+12°C

El input

4.88 kW

Cooling capacity

15.04

EER

3.08

EN 14825

+7°C/+12°C

Pdesignc

15.04 kW

SEER

5.05

Pdc Tj = 35°C

15.04 kW

EER Tj = 35°C

3.08

Pdc Tj = 30°C

10.96 kW

EER Tj = 30°C

4.38

Cdc Tj = 30 °C

1.000

Pdc Tj = 25°C

7.06 kW

EER Tj = 25°C

5.52

Cdc Tj = 25 °C

0.985

Pdc Tj = 20°C

5.54 kW

EER Tj = 20°C

6.80

Cdc Tj = 20 °C

0.977

Poff

22 W

PTO

0 W

PSB

28 W

PCK

0 W

Annual energy consumption Qce

1788 kWh

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

17.90 kW

17.25 kW

El input

4.07 kW

5.99 kW

COP

4.40

2.88

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

131 %

Prated

15.00 kW

14.00 kW

SCOP

4.46

3.36

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

12.80 kW

12.50 kW

COP Tj = -7°C

2.83

2.03

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.80 kW

7.60 kW

COP Tj = +2°C

4.34

3.34

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

5.80 kW

5.70 kW

COP Tj = +7°C

5.67

4.14

Cdh Tj = +7 °C

0.981

0.990

Pdh Tj = 12°C

6.70 kW

6.60 kW

COP Tj = 12°C

7.94

6.15

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

12.80 kW

12.50 kW

COP Tj = Tbiv

2.83

2.03

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.80 kW

12.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.59

1.93

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

22 W

22 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

2.20 kW

1.40 kW

Annual energy consumption Qhe

6720 kWh

8659 kWh

ECLPAC16T.ST ; ECLPAC16T.KA
Configure model
Model name
ECLPAC16T.ST ; ECLPAC16T.KA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Cooling

EN 14511-2

+7°C/+12°C

El input

4.38 kW

Cooling capacity

13.80

EER

3.15

EN 14825

+7°C/+12°C

Pdesignc

13.80 kW

SEER

4.80

Pdc Tj = 35°C

13.80 kW

EER Tj = 35°C

3.15

Pdc Tj = 30°C

10.17 kW

EER Tj = 30°C

4.36

Cdc Tj = 30 °C

1.0

Pdc Tj = 25°C

6.47 kW

EER Tj = 25°C

5.30

Cdc Tj = 25 °C

1.0

Pdc Tj = 20°C

5.53 kW

EER Tj = 20°C

6.67

Cdc Tj = 20 °C

1.0

Poff

19 W

PTO

0 W

PSB

19 W

PCK

30 W

Annual energy consumption Qce

1726 kWh

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.30 kW

15.63 kW

El input

3.49 kW

5.18 kW

COP

4.67

3.02

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

dB(A)

dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

126 %

Prated

14.00 kW

13.00 kW

SCOP

4.49

3.22

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

12.00 kW

11.50 kW

COP Tj = -7°C

2.88

2.09

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.30 kW

6.90 kW

COP Tj = +2°C

4.33

3.06

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

5.70 kW

5.50 kW

COP Tj = +7°C

5.83

4.11

Cdh Tj = +7 °C

0.981

0.986

Pdh Tj = 12°C

6.70 kW

6.60 kW

COP Tj = 12°C

8.12

6.30

Cdh Tj = +12 °C

0.977

0.982

Pdh Tj = Tbiv

12.00 kW

11.50 kW

COP Tj = Tbiv

2.88

2.09

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

11.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.94

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

22 W

22 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

2.30 kW

1.50 kW

Annual energy consumption Qhe

6209 kWh

8357 kWh