Login

Subtype

ECL-PAC-14

Certificate Holder
ECL Nexus
13, Boulevard Pereire
75017 Paris
France
Registration number
ICIM-PDC-000144
Certification Body
ICIM S.p.A.
Subtype title
ECL-PAC-14
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

3,600 kg

Certification Date
20.05.2022
Testing basis
HP KEYMARK certification scheme rules rev. no. 7
Generate PDF Export model CSV
  • Number of models 2

Models

ECLPAC14X.ST ; ECLPAC14X.KA
Configure model
Model name
ECLPAC14X.ST ; ECLPAC14X.KA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Cooling

EN 14511-2

+7°C/+12°C

El input

3.53 kW

Cooling capacity

11.48

EER

3.25

EN 14825

+7°C/+12°C

Pdesignc

11.48 kW

SEER

4.77

Pdc Tj = 35°C

11.48 kW

EER Tj = 35°C

3.25

Pdc Tj = 30°C

8.47 kW

EER Tj = 30°C

4.31

Cdc Tj = 30 °C

1.000

Pdc Tj = 25°C

5.41 kW

EER Tj = 25°C

4.91

Cdc Tj = 25 °C

0.983

Pdc Tj = 20°C

5.53 kW

EER Tj = 20°C

6.72

Cdc Tj = 20 °C

0.977

Poff

22 W

PTO

0 W

PSB

28 W

PCK

0 W

Annual energy consumption Qce

1444 kWh

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.10 kW

13.44 kW

El input

2.91 kW

4.35 kW

COP

4.85

3.09

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

dB(A)

dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

130 %

Prated

12.00 kW

12.00 kW

SCOP

4.48

3.31

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

10.70 kW

10.30 kW

COP Tj = -7°C

2.98

2.10

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

6.50 kW

6.20 kW

COP Tj = +2°C

4.20

3.21

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

5.80 kW

5.70 kW

COP Tj = +7°C

5.98

4.19

Cdh Tj = +7 °C

0.980

0.986

Pdh Tj = 12°C

6.70 kW

6.60 kW

COP Tj = 12°C

8.16

6.17

Cdh Tj = +12 °C

0.977

0.982

Pdh Tj = Tbiv

10.70 kW

10.30 kW

COP Tj = Tbiv

2.98

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

10.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.69

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

22 W

22 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.50 kW

1.80 kW

Annual energy consumption Qhe

5583 kWh

7259 kWh

ECLPAC14TX.ST ; ECLPAC14T.KA
Configure model
Model name
ECLPAC14TX.ST ; ECLPAC14T.KA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Cooling

EN 14511-2

+7°C/+12°C

El input

3.53 kW

Cooling capacity

11.48

EER

3.25

EN 14825

+7°C/+12°C

Pdesignc

11.48 kW

SEER

4.77

Pdc Tj = 35°C

11.48 kW

EER Tj = 35°C

3.25

Pdc Tj = 30°C

8.47 kW

EER Tj = 30°C

4.31

Cdc Tj = 30 °C

1.000

Pdc Tj = 25°C

5.41 kW

EER Tj = 25°C

4.91

Cdc Tj = 25 °C

0.983

Pdc Tj = 20°C

5.53 kW

EER Tj = 20°C

6.72

Cdc Tj = 20 °C

0.977

Poff

22 W

PTO

0 W

PSB

28 W

PCK

0 W

Annual energy consumption Qce

1444 kWh

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.10 kW

13.44 kW

El input

2.91 kW

4.35 kW

COP

4.85

3.09

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

dB(A)

dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

130 %

Prated

12.00 kW

12.00 kW

SCOP

4.48

3.31

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

10.70 kW

10.30 kW

COP Tj = -7°C

2.98

2.10

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

6.50 kW

6.20 kW

COP Tj = +2°C

4.20

3.21

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

5.80 kW

5.70 kW

COP Tj = +7°C

5.98

4.19

Cdh Tj = +7 °C

0.980

0.986

Pdh Tj = 12°C

6.70 kW

6.60 kW

COP Tj = 12°C

8.16

6.17

Cdh Tj = +12 °C

0.977

0.982

Pdh Tj = Tbiv

10.70 kW

10.30 kW

COP Tj = Tbiv

2.98

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

10.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.69

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

22 W

22 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.50 kW

1.80 kW

Annual energy consumption Qhe

5583 kWh

7259 kWh